“Our climate is warming at a faster rate than ever before recorded.”
D. James Baker
NOAA Administrator, 1993–2004
Introduction
The quotes below provide a profound lesson in the need for housing to provide protection
from both the heat and cold.
“France heat wave death toll set at 14,802:
The death toll in France from August’s blistering heat wave has reached nearly
15,000, according to a government-commissioned report released Thursday, surpassing
a prior tally by more than 3,000.” USA Today, September 25, 2003.
“In the study of the 1995 Chicago heat wave, those at greatest risk of dying
from the heat were people with medical illnesses who were socially isolated
and did not have access to air conditioning.” Centers for Disease Control and
Prevention, Morbidity and Mortality Weekly Report, July 4, 2003.
“3 Deaths tied to cold . . .The bitter cold that gripped the Northeast through
the weekend and iced over roads was blamed for at least three deaths, including
that of a Philadelphia man found inside a home without heat.” Lexington
[Kentucky] Herald Leader, January 12, 2004.
“In many temperate countries, death rates during the winter season are 10%–25%
higher than those in the summer.” World Health Organization, Health Evidence
Network, November 1, 2004.
This chapter provides a general overview of the heating
and cooling of today’s homes. Heating and cooling are not merely a matter of comfort,
but of survival. Both very cold and very hot temperatures can threaten health. Excessive
exposure to heat is referred to as heat stress and excessive exposure to cold is
referred to as cold stress.
In a very hot environment, the most serious health risk is heat stroke. Heat stroke
requires immediate medical attention and can be fatal or leave permanent damage.
Heat stroke fatalities occur every summer. Heat exhaustion and fainting are less
serious types of illnesses. Typically they are not fatal, but they do interfere
with a person’s ability to work.
At very cold temperatures, the most serious concern is the risk for hypothermia
or dangerous overcooling of the body. Another serious effect of cold exposure is
frostbite or freezing of exposed extremities, such as fingers, toes, nose, and ear
lobes. Hypothermia can be fatal if immediate medical attention is not received.
Heat and cold are dangerous because the victims of heat stroke and hypothermia often
do not notice the symptoms. This means that family, neighbors, and friends are essential
for early recognition of the onset of the conditions. The affected individual’s
survival depends on others to identify symptoms and to seek medical help. Family,
neighbors, and friends must be particularly diligent during heat or cold waves to
check on individuals who live alone.
Although symptoms vary from person to person, the warning signs of heat exhaustion
include confusion and profuse and prolonged sweating. The person should be removed
from the heat, cooled, and heavily hydrated. Heat stroke signs and symptoms include
sudden and severe fatigue, nausea, dizziness, rapid pulse, lightheadedness, confusion,
unconsciousness, extremely high temperature, and hot and dry skin surface. An individual
who appears disorientated or confused, seems euphoric or unaccountably irritable,
or suffers from malaise or flulike symptoms should be moved to a cool location and
medical advice should be sought immediately.
Warning signs of hypothermia include nausea, fatigue, dizziness, irritability, or
euphoria. Individuals also experience pain in their extremities (e.g., hands, feet,
ears) and severe shivering. People who exhibit these symptoms, particularly the
elderly and young, should be moved to a heated shelter and medical advice should
be sought when appropriate.
The function of a heating, ventilation, and air conditioning (HVAC) system is to
provide for more than human health and comfort. The HVAC system produces heat, cool
air, and ventilation, and helps control dust and moisture, which can lead to adverse
health effects. The variables to be controlled are temperature, air quality, air
motion, and relative humidity. Temperature must be maintained uniformly throughout
the heated/cooled area. There is a 6ºF to 10ºF (-14ºC to -12ºC) variation in room
temperature from floor to ceiling. The adequacy of the HVAC system and the air-tightness
of the structure or room determine the degree of personal safety and comfort within
the dwelling.
Gas, electricity, oil, coal, wood, and solar energy are the main energy sources
for home heating and cooling. Heating systems commonly used are steam, hot water
and hot air. A housing inspector should have knowledge of the various heating fuels
and systems to be able to determine their adequacy and safety in operation. To cover
fully all aspects of the heating and cooling system, the entire area and physical
components of the system must be considered.
Click here for definition of terms related to HVAC systems.
Heating
Fifty-one percent of the homes in the United States are heated with natural gas,
30% are heated with electricity, and 9% with fuel oil. The remaining 11% are heated
with bottled fuel, wood, coal, solar, geothermal, wind, or solar energy [1].
Any home using combustion as a source of heating, cooling, or cooking or that has
an attached garage should have appropriately located and maintained carbon monoxide
(CO) gas detectors. According to the U.S. Consumer Product Safety Commission (CPSC),
from data collected in 2000, CO kills 200 people and sends more than 10,000 to the
hospital each year.
The standard fuels for heating are discussed below.
Standard Fuels
Gas
More than 50% of American homes use gas fuel. Gas fuels are colorless gases. Some
have a characteristic pungent odor; others are odorless and cannot be detected by
smell. Although gas fuels are easily handled in heating equipment, their presence
in air in appreciable quantities becomes a serious health hazard. Gases diffuse
readily in the air, making explosive mixtures possible. A proportion of combustible
gas and air that is ignited burns with such a high velocity that an explosive force
is created. Because of these characteristics of gas fuels, precautions must be taken
to prevent leaks, and care must be exercised when gas-fired equipment is lit.
Gas is broadly classified as natural or manufactured.
Natural gas—This
gas is a mixture of several combustible and inert gases. It is one of the richest
gases and is obtained from wells ordinarily located in petroleum-producing areas.
The heat content may vary from 700 to 1,300 British thermal units (BTUs) per cubic
foot, with a generally accepted average figure of 1,000 BTUs per cubic foot. Natural
gases are distributed through pipelines to the point of use and are often mixed
with manufactured gas to maintain a guaranteed BTU content.
Manufactured gas—This gas, as distributed, is usually a combination of certain
proportions of gases produced from coke, coal, and petroleum. Its BTU value per
cubic foot is generally closely regulated, and costs are determined on a guaranteed
BTU basis, usually 520 to 540 BTUs per cubic foot.
Liquefied petroleum gas—Principal products of liquefied petroleum gas are
butane and propane. Butane and propane are derived from natural gas or petroleum
refinery gas and are chemically classified as hydrocarbon gases. Specifically, butane
and propane are on the borderline between a liquid and a gaseous state. At ordinary
atmospheric pressure, butane is a gas above 33°F (0.6ºC) and propane a gas at -42°F
(-41ºC). These gases are mixed to produce commercial gas suitable for various climatic
conditions. Butane and propane are heavier than air. The heat content of butane
is 3,274 BTUs per cubic foot, whereas that of propane is 2,519 BTUs per cubic foot.
Gas burners should be equipped with an automatic shutoff
in case the flame fails. Shutoff valves should be located within 1 foot of the burner
connection and on the output side of the meter.
Caution: Liquefied petroleum gas is heavier than air; therefore, the gas will accumulate
at the bottom of confined areas. If a leak develops, care should be taken to ventilate
the appliance before lighting it.
Electricity
Electricity has gained popularity for heating in many regions, particularly where
costs are competitive with other sources of heat energy, with usage increasing from
2% in 1960 to 30% in 2000. With an electric system, the housing inspector should
rely mainly on the electrical inspector to determine proper installation. There
are a few items, however, to be concerned with to ensure safe use of the equipment.
Check to see that the units are approved by an accredited testing agency and installed
according to the manufacturer’s specifications. Most convector-type units must be
installed at least 2 inches above the floor level, not only to ensure that proper
convection currents are established through the unit, but also to allow sufficient
air insulation from any combustible flooring material. The housing inspector should
check for curtains that extend too close to the unit or loose, long-pile rugs that
are too close. A distance of 6 inches on the floor and 12 inches on the walls should
separate rugs or curtains from the appliance.
Heat pumps are air conditioners that contain a valve that allows switching between
air conditioner and heater. When the valve is switched one way, the heat pump acts
like an air conditioner; when it is switched the other way, it reverses the flow
of refrigerants and acts like a heater. Cold is the absence of energy or calories
of heat. To cool something, the heat must be removed; to warm something, energy
or calories of heat must be provided. Heat pumps do both.
A heat pump has a few additions beyond the typical air conditioner: a reversing
valve, two thermal expansion valves, and two bypass valves. The reversing valve
allows the unit to provide both cooling and heating.
Figure 12.1 shows a heat pump in cooling mode. The unit operates as follows:
- The compressor compacts the refrigerant vapor
and pumps it to the reversing valve.
- The reversing valve directs the compressed
vapor to flow to the outside heat exchanger (condenser), where the refrigerant
is cooled and condensed to a liquid.
- The air blowing through the condenser coil
removes heat from the refrigerant.
- The liquid refrigerant bypasses the first
thermal expansion valve and flows to the second thermal expansion valve at the
inside heat exchanger (evaporator) where it expands into the evaporator and
becomes vapor.
- The refrigerant picks up heat energy from
the air blowing across the evaporator coil and cool air comes out at the other
side of the coil. The cool air is ducted to the occupied space as air-conditioned
air.
- The refrigerant vapor then goes back to the
reversing valve to be directed to the compressor to start the refrigeration
cycle all over again.
Heat pumps [3] are quite
efficient in their use of energy. However, heat pumps often freeze up; that is,
the coils in the outside air collect ice. The heat pump has to melt this ice periodically,
so it switches itself back to air conditioner mode to heat up the coils. To avoid
pumping cold air into the house in air conditioner mode, the heat pump also uses
electric strip heaters to heat the cold air that the air conditioner is pumping
out. Once the ice is melted, the heat pump switches back to heating mode and turns
off the burners.
Radiant heat warms objects directly with longwave
electromagnetic energy. The heating panels diffuse heating energy rays in a 160º
arc, distributing warmth evenly. The goal is to achieve no more than a 4°F (-16ºC)
difference in temperature between floor level and ceiling level. When properly installed,
radiant heat warms a room sooner and at lower temperature settings than do other
kinds of heat. Extreme care must be taken to protect against fire hazards from objects
in close proximity to the infrared radiation reflectors. Inspectors dealing with
this heat source should have specialized training. Radiant heating is plastered
into the ceiling or wall in some homes or in the brick or ceramic floors of bathrooms.
If wires are bare in the plaster, they should be treated as open and exposed wiring.
The inspector should be knowledgeable about these systems, which are technical and
relatively new.
Fuel Oil
Fuel oils are derived from petroleum, which consists primarily of compounds of hydrogen
and carbon (hydrocarbons) and smaller amounts of nitrogen and sulfur. Domestic fuel
oils are controlled by rigid specifications. Six grades of fuel oil—numbered 1 through
6—are generally used in heating systems; the lighter two grades are used primarily
for domestic heating:
Grade Number 1—a
volatile, distillate oil for use in burners that prepare fuel for burning solely
by vaporization (oil-fired space heaters).
Grade Number 2—a moderate weight, volatile, distillate oil used for burners
that prepare oil for burning by a combination of vaporization and atomization. This
grade of oil is commonly used in domestic heating furnaces.
Heating values of oil vary from approximately 152,000
BTU per gallon for number 6 oil to 136,000 BTU per gallon for number 1 oil. Oil
is more widely used today than coal and provides a more automatic source of heat
and comfort. It also requires more complicated systems and controls. If the oil
supply is in the basement or cellar area, certain code regulations must be followed
(Figure
12.2) [4-7]. No more than two 275-gallon tanks
may be installed above ground in the lowest story of any one building. The IRC recommends
a maximum fuel oil storage of 660 gallons. The tank shall not be closer than 7 feet
horizontally to any boiler, furnace, stove, or exposed flame(s).
Fuel oil lines should be embedded in a concrete or cement floor or protected against
damage if they run across the floor. Each tank must have a shutoff valve that will
stop the flow if a leak develops in the line to or in the burner itself. A leak-tight
liner or pan should be installed under tanks and lines located above the floor.
They contain potential leaks so the oil does not spread over the floor, creating
a fire hazard.
The tank or tanks must be vented to the outside, and a gauge showing the quantity
of oil in the tank or tanks must be tight and operative. Steel tanks constructed
before 1985 had a life expectancy of 12–20 years. Tanks must be off the floor and
on a stable base to prevent settlement or movement that may rupture the connections.
Figure 12.3 shows a buried outside tank installation. In 1985, federal legislation
was passed requiring that the exterior components of underground storage tanks (USTs)
installed after 1985 resist the effects of pressure, vibration, and movement. Federal
regulations for USTs exclude the following: farm and residential tanks of 1,100
gallons or less capacity; tanks storing heating oil used on the premises; tanks
on or above the floor of basements; septic tanks; flow-through process tanks; all
tanks with capacity of 110 gallons or less; and emergency spill and overfill tanks
[8]. A review of local and state regulations should be completed
before installing underground tanks because many jurisdictions do not allow burial
of gas or oil tanks.
Coal
The four types of coal are anthracite, bituminous, sub-bituminous, and lignite.
Coal is prepared in many sizes and combinations of sizes. The combustible portions
of the coal are fixed carbons, volatile matter (hydrocarbons), and small amounts
of sulfur. In combination with these are noncombustible elements composed of moisture
and impurities that form ash. The various types differ in heat content. Heat content
is determined by analysis and is expressed in British thermal units per pound.
Improper coal furnace operation can result in an extremely hazardous and unhealthy
home. Ventilation of the area surrounding the furnace is very important to prevent
heat buildup and to supply air for combustion.
Solar Energy
Solar energy has gained popularity in the last 25 years as the cost of installation
of solar panels and battery storage has decreased. Improved technology with panels,
installation of panels, piping, and batteries has created a much larger market.
Solar energy largely has been used to heat water. Today, there are more than a million
solar water-heating systems in the United States. Solar water heaters use direct
sun to heat either water or a heat-transfer fluid in collectors [3].
That water is then stored for use as needed, with a conventional system providing
any necessary additional heating. A typical system will reduce the need for conventional
water heating by about two-thirds, minimizing the cost of electricity or the use
of fossil fuel and thus the environmental impact associated with their use. The
U.S. Department of Housing and Urban Development and the U.S. Department of Energy
(DOE) have instituted initiatives to deploy new solar technologies in the next generation
of American housing [3]. For example, DOE has the Million
Solar Roofs Initiative begun in 1997 to install solar energy systems in more than
1 million U.S. buildings by 2010.
Central Heating Units
The boiler should be placed in a separate room whenever possible, which is usually
required in new construction. In most housing inspections, however, the inspector
is dealing with existing conditions and must adapt the situation as closely as possible
to acceptable safety standards. In many old buildings, the furnace is located in
the center of the cellar or basement. This location does not lend itself to practical
conversion to a boiler room.
Consider the physical requirements for a boiler or furnace.
Ventilation—More
circulating air is required for the boiler room than for a habitable room, to reduce
the heat buildup caused by the boiler or furnace and to supply oxygen for combustion.
Fire protection rating—As specified by various codes (fire code, building
code, and insurance underwriters), the fire regulations must be strictly adhered
to in areas surrounding the boiler or furnace. This minimum clearance for a boiler
or furnace from a wall or ceiling is shown in
Figures 12.4 and
12.5.
Asbestos was used in numerous places on furnaces
to protect buildings from fire and to prevent lost heat.
Figure 12.6 shows asbestos-coated heating ducts, for example. Where asbestos
insulation is found, it must be handled with care (breathing protection and protective
clothing) and care must be taken to prevent or contain release into the air [10].
The furnace or boiler makes it difficult to supply air and ventilation for the room.
Where codes and local authority permit, it may be more practical to place the furnace
or boiler in an open area. The ceiling above the furnace should be protected to
a distance of 3 feet (914.4 mm) beyond all furnace or boiler appurtenances, and
this area should be free of all storage material. The furnace or boiler should be
on a firm foundation of concrete if located in the cellar or basement. If codes
permit furnace installations on the first floor, then they must be consulted for
proper setting and location.
Heating Boilers
The term boiler is applied to the single heat source that can supply either steam
or hot water (a boiler is often called a heater).
Boilers may be classified according to several kinds of characteristics. They are
typically made from cast iron or steel. Their construction design may be sectional,
portable, fire-tube, water-tube, or special. Domestic heating boilers are generally
of low-pressure type with a maximum working pressure of 15 pounds per square inch
(psi) for steam and 30 psi for hot water. All boilers have a combustion chamber
for burning fuel. Automatic fuel-firing devices help supply the fuel and control
the combustion. Hand firing is accomplished by the provision of a grate, ash pit,
and controllable drafts to admit air under the fuel bed and over it through slots
in the firing door. A check draft is required at the smoke pipe connection to control
chimney draft. The gas passes from the combustion chamber to the flue passages (smoke
pipe) designed for maximum possible transfer of heat from the gas. Provisions must
be made for cleaning flue passages.
Cast-iron boilers are usually shipped in sections and assembled at the site.
They are generally classified as
- square or rectangular boilers with vertical
sections; and
- round, square, or rectangular boilers with
horizontal pancake sections.
Most steel boilers are assembled units with welded
steel construction and are called portable boilers. Large boilers are installed
in refractory brick settings on the site. Above the combustion chamber, a group
of tubes is suspended, usually horizontally, between two headers. If flue gases
pass through the tubes and water surrounds them, the boiler is designated as the
fire-tube type. When water flows through the tubes, it is termed water-tube. Fire-tube
is the predominant type.
Heating Furnaces
Heating furnaces are the heat sources used when air is the heat-carrying medium.
When air circulates because of the different densities of the heated and cooled
air, the furnace is a gravity type. A fan may be included for the air circulation;
this type is called a mechanical warm-air furnace. Furnaces may be of cast iron
or steel and burn various types of fuel.
Some new furnaces are as fuel efficient as 95%. Furnaces with an efficiency of 90%
or greater use two heat exchangers instead of one. Energy savings come not only
from the increased efficiency, but also from improved comfort at lower thermostat
settings.
Fuel-burning Furnaces
Some localities throughout the United States still use coal as a heating fuel, including
residences, schools, colleges and universities, small manufacturing facilities,
and other facilities located near coal sources.
In many older furnaces, the coal is stoked or fed into the firebox by hand. The
single-retort, underfeed-type bituminous coal stoker is the most commonly used domestic
automatic-stoking steam or hot-water boiler
Figure 12.7. The stoker consists of a coal hopper, a screw for conveying
coal from hopper to retort, a fan that supplies air for combustion, a transmission
for driving coal feed and fan, and an electric motor for supplying power. The air
for combustion is admitted to the fuel through tuyeres (air inlets) at the top of
the retort. The stoker feeds coal to the furnace intermittently in accordance with
temperature or pressure demands.
Oil burners are broadly designated as distillate, domestic, and commercial or industrial.
Distillate burners are usually found in oil-fired space heaters. Domestic oil burners
are usually power driven and are used in domestic heating plants. Commercial or
industrial burners are used in larger central-heating plants for steam or power
generation.
Domestic oil burners vaporize and atomize the oil and deliver a predetermined quantity
of oil and air to the combustion chambers. Domestic oil burners operate automatically
to maintain a desired temperature.
Gun-type burners atomize the oil either by oil pressure or by low-pressure air forced
through a nozzle. The oil system pressure-atomizing burner consists of a strainer,
pump, pressure-regulating valve, shutoff valve and atomizing nozzle. The air system
consists of a power-driven fan and an air tube that surrounds the nozzle and electrode
assembly.
The fan and oil pump are generally connected directly to the motor. Oil pressures
normally used are about 100 psi, but pressures considerably in excess of this are
sometimes used.
The form and parts of low-pressure, air-atomizing burners are similar to high-pressure
atomizing (gun) burners (Figure
12.8) except for addition of a small air pump and a different way of delivering
air and oil to the nozzle or orifice.
The atomizing type burner, sometimes known as a radiant or suspended flame burner,
atomizes oil by throwing it from the circumference of a rapidly rotating motor-driven
cup. The burner is installed so that the driving parts are protected from the heat
of the flame by a hearth of refractory material at about the grate elevation. Oil
is fed by pump or gravity; the draft is mechanical or a combination of natural and
mechanical.
Horizontal rotary burners were originally designed for commercial and industrial
use but are available in sizes suitable for domestic use. In this burner, fuel oil
being thrown in a conical spray from a rapidly rotating cup is atomized. Horizontal
rotary burners use electric gas or gas-pilot ignition and operate with a wide range
of fuels, primarily Numbers 1 and 2 fuel oil. Primary safety controls for burner
operation are necessary. An antiflooding device must be a part of the system to
stop oil flow if ignition in the burner should fail. Likewise, a stack control is
necessary to shut off the burner if the stack temperatures are exceeded, thus cutting
off all power to the burner. This button must be reset before starting can be attempted.
The newer models now use electric eye-type control on the burner itself.
On the basis of the method used to ignite fuels, burners are divided into five groups:
Electric—A high-voltage electric spark in the path of an oil and air mixture
causes ignition. This electric spark may be continuous or may operate only long
enough to ignite the oil. Electric ignition is almost universally used. Electrodes
are located near the nozzles, but not in the path of the oil spray.
Gas pilot—A small gas pilot light that burns continuously is frequently used.
Gas pilots usually have expanded gas valves that automatically increase flame size
when a motor circuit starts. After a fixed interval, the flame reverts to normal
size (Figure
12.9).
Electric gas—An electric spark ignites a gas jet, which in turn ignites the
oil-air mixture.
Oil pilot—A small oil flame is used.
Manual—A burning wick or torch is placed in the combustion space through
peepholes and thus ignites the charge. The operator should stand to one side of
the fire door to guard against injury from chance explosion.
The refractory lining or material should be an insulating fireproof bricklike substance,
never ordinary firebrick. The insulating brick should be set on end to build a 2½-inch
thick wall from furnace to furnace. The size and shape of the refractory pot vary
from furnace to furnace. The shape can be either round or square, whichever is more
convenient to build. It is more important to use a special cement having properties
similar to that of the insulating refractory-type brick.
Steam Heating Systems
Steam heating systems are classified according to the pipe arrangement, accessories
used, method of returning the condensate to the boiler, method of expelling air
from the system, or the type of control used. The successful operation of a steam
heating system consists of generating steam in sufficient quantity to equalize building
heat loss at maximum efficiency, expelling entrapped air, and returning all condensate
to the boiler rapidly. Steam cannot enter a space filled with air or water at pressure
equal to the steam pressure. It is important, therefore, to eliminate air and remove
water from the distribution system. All hot pipelines exposed to contact by residents
must be properly insulated or guarded. Steam heating systems use the following methods
to return the condensate to the boiler:
Gravity one-pipe air-vent system—One of the earliest types used, this method
returns condensate to the boiler by gravity. This system is generally found in one-building-type
heating systems. The steam is supplied by the boiler and carried through a single
system or pipe to radiators, as shown in
Figure 12.10. Return of the condensate is dependent on hydrostatic head.
Therefore, the end of the stream main, where it attaches to the boiler, must be
full of water (termed a wet return) for a distance above the boiler line to create
a pressure drop balance between the boiler and the stream main.
Radiators are equipped with an inlet valve and an air valve. The air valve permits
venting of air from the radiator and its displacement by steam. Condensate is drained
from the radiator through the same pipe that supplies steam.
Two-pipe steam vapor system with return trap—The two-pipe vapor system with
boiler return trap and air eliminator is an improvement of the one-pipe system.
The return connection of the radiator has a thermostatic trap that permits flow
of condensate and air only from the radiator and prevents steam from leaving the
radiator. Because the return main is at atmospheric pressure or less, a boiler return
trap is installed to equalize condensate return pressure with boiler pressure.
Water Heating Systems
All water heating systems are similar in design and operating principle. The one-pipe
gravity water heating system is the most elementary of the gravity systems and is
shown in
Figure 12.10. Water is heated at the lowest point in the system. It rises
through a single main because of a difference in density between hot and cold water.
The supply rise or radiator branch takes off from the top of the main to supply
water to the radiators. After the water gives up heat in the radiator, it goes back
to the same main through return piping from the radiator. This cooler return water
mixes with water in the supply main and causes the water to cool a little. As a
result, the next radiator on the system has a lower emission rate and must be larger.
Note in
Figure 12.11 that the high points of the hot water system are vented and
the low points are drained. In this case, the radiators are the high points and
the heater is the low point. `One-pipe
forced-feed system—If a pump or circulator is introduced
in the main near the heater of the one-pipe system, it becomes a forced system that
can be used for much larger applications than can the gravity type. This system
can operate at higher water temperatures than the gravity system can. When the water
is moving faster and at higher temperatures, it makes a more responsive system,
with smaller temperature drops and smaller radiators for the same heating load.
Two-pipe gravity system—A one-pipe gravity system may become a two-pipe system
if the return radiator branch connects to a second main that returns water to the
heater (Figure
12.12). Water temperature is practically the same in the entire radiator.
Two-pipe forced-circulation system—This system is similar to a one-pipe forced-circulation
system except that it uses the same piping arrangement found in the two-pipe gravity
system.
Expansion tanks—When water is heated, it tends to expand. Therefore, an expansion
tank is necessary in a hot water system. The expansion tank, either open or closed,
must be of sufficient size to permit a change in water volume within the heating
system. If the expansion tank is open, it must be placed at least 3 feet above the
highest point of the system. It will require a vent and an overflow. The open tank
is usually in an attic, where it needs protection from freezing.
The closed expansion tank is found in modern installations.
An air cushion in the tank compresses and expands according to the change of volume
and pressure in the system. Closed tanks are usually at the low point in the system
and close to the heater. They can, however, be placed at almost any location within
the heating system.
Air Heating Systems
Gravity Warm-air Heating Systems. These operate because of the difference
in specific gravity of warm air and cold air. Warm air is lighter than cold air
and rises if cold air is available to replace it (Figure
12.13).
Operation—Satisfactory
operation of a gravity warm-air heating system depends on three factors: size of
warm air and cold air ducts, heat loss of the building, and heat available from
the furnace.
Heat distribution—The most common source of trouble in these systems is insufficient
pipe area, usually in the return or cold air duct. The total cross-section area
of the cold duct or ducts must be at least equal to the total cross-section area
of all warm ducts.
Pipeless furnaces—The pipeless hot-air furnace is the simplest type of hot-air
furnace and is suitable for small homes where all rooms can be grouped about a single
large register. Other pipeless gravity furnaces are often installed at floor level.
These are really oversized jacketed space heaters. The most common difficulty experienced
with this type of furnace is supplying a return air opening of sufficient size on
the floor.
Forced-Warm-Air Heating Systems. The mechanical warm-air furnace is the most
modern type of warm-air equipment (Figures
12.13 and
12.14). It is the safest type because it operates at low temperatures. The
principle of a forced-warm-air heating system is very similar to that of the gravity
system, except that a fan or blower is added to increase air movement. Because of
the assistance of the fan or blower, the pitch of the ducts or leaders can be disregarded;
therefore, it is practical to deliver heated air in the most convenient places.
Operation—In a forced-air system, operation of the fan or blower must be
controlled by air temperature in a bonnet or by a blower control furnace stat. The
blower control starts the fan or blower when the temperature reaches a certain point
and turns the fan or blower off when the temperature drops to a predetermined point.
Heat distribution—Dampers in the various warm-air ducts control distribution
of warm air either at the branch takeoff or at the warm-air outlet. Humidifiers
are often mounted in the supply bonnet to regulate the humidity within the residence.
Space Heaters
Space heaters are the least desirable type of heating from the viewpoint of fire
safety and housing inspection. A space heater is a self-contained, free-standing
air-heating appliance intended for installation in the space being heated and not
intended for duct connection. According to the CPSC, consumers are not using care
when purchasing and using space heaters. Approximately 21,800 residential fires
are caused by space heaters a year, and 300 people die in these fires. An estimated
6,000 persons receive hospital emergency room care for burn injuries associated
with contacting hot surfaces of space heaters, mostly in nonfire situations.
Individuals using space heaters should use the heaters in accordance with the following
precautions:
- Read and follow the manufacturer’s operating
instructions. A good practice is to read aloud the instructions and warning
labels to all members of the household to be certain that everyone understands
how to operate the heater safely. Keep the owner’s manual in a convenient place
to refer to when needed.
- Choose a space heater that has been tested
and certified by a nationally recognized testing laboratory. These heaters meet
specific safety standards.
- Buy a heater that is the correct size for
the area you want to heat. The wrong size heater could produce more pollutants
and may not be an efficient use of energy.
- Choose models that have automatic safety switches
that turn off the unit if it is tipped over accidentally.
- Select a space heater with a guard around
the flame area or heating element. Place the heater on a level, hard, nonflammable
surface, not on rugs or carpets or near bedding or drapes. Keep the heater at
least 3 feet from bedding, drapes, furniture, or other flammable materials.
- Keep doors open to the rest of the house if
you are using an unvented fuel-burning space heater. This helps prevent pollutant
build-up and promotes proper combustion. Follow the manufacturer’s instructions
for oil heaters to provide sufficient combustion air to prevent CO production.
- Never leave a space heater on when you go
to sleep. Never place a space heater close to any sleeping person.
- Turn the space heater off if you leave the
area. Keep children and pets away from space heaters. Children should not be
permitted to either adjust the controls or move the heater.
- Keep any portable heater as least 3 feet away
from curtains, newspapers, or anything that might burn.
- Have a smoke detector with fresh batteries
on each level of the house and a CO detector outside the sleeping area. Install
a CO monitor near oil space heaters at the height recommended by the manufacturer.
- Be aware that mobile homes require specially
designed heating equipment. Only electric or vented fuel-fired heaters should
be used.
- Have gas and kerosene space heaters inspected
annually.
- Do not hang items to dry above or on the heater.
- Keep all heaters out of exit and high-traffic
areas.
- Keep portable electric heaters away from sinks,
tubs, and other wet or damp places to avoid deadly electric shocks.
- Never use or store flammable liquids (such
as gasoline) around a space heater. The flammable vapors can flow from one part
of the room to another and be ignited by the open flame or by an electrical
spark.
Coal-fired Space Heaters (Cannon Stove)
A coal stove is made entirely of cast iron. Coal on the grates receives primary
air for combustion through the grates from the ash-door draft intake. Combustible
gases driven from the coal by heat burn in the barrel of the stove, where they receive
additional or secondary air through the feed door. The side and top of the stove
absorb the heat of combustion and radiate it to the surrounding space. Coal stoves
must be vented to the flue.
Oil-fired Space Heaters
Oil-fired space heaters have atmospheric vaporizing-type burners. The burners require
a light grade of fuel oil that vaporizes easily and in comparatively low temperatures.
In addition, the oil must be such that it leaves only a small amount of carbon residue
and ash within the heater. Oil stoves must be vented.
The burner of an oil-fired space heater consists essentially of a bowl, 8 to 13
inches in diameter, with perforations in the side that admit air for combustion.
The upper part of the bowl has a flame ring or collar.
Figure 12.15 shows a perforated-sleeve burner. When several space heaters
are installed in a building, an oil supply from an outside tank to all heaters is
often desirable.
Figure 12.16 shows the condition of a burner
flame with different rates of fuel flow and indicates the ideal flame height.
Electric Space Heaters
Electric space heaters do not need to be vented.
Gas-fired Space Heaters
The three types of gas-fired space heaters (natural, manufactured, and liquefied
petroleum gas) have a similar construction. All gas-fired space heaters must be
vented to prevent a dangerous buildup of poisonous gases. Each unit console consists
of an enamel steel cabinet with top and bottom circulating grilles or openings,
gas burners, heating elements, gas pilot, and a gas valve. The heating element or
combustion chamber is usually cast iron.
Caution: All gas-fired space heaters and their connections must be approved by the
American Gas Association (AGA). They must be installed in accordance with the recommendations
of that organization or the local code.
Venting
Use of proper venting materials and correct installation of venting for gas-fired
space heaters is necessary to minimize harmful effects of condensation and to ensure
that combustion products are carried off. (Approximately 12 gallons of water are
produced in the burning of 1,000 cubic feet of natural gas. The inner surface of
the vent must therefore be heated above the dew point of the combustion products
to prevent water from forming in the flue.) A horizontal vent must be given an upward
pitch of at least 1 inch per foot of horizontal distance.
When the smoke pipe extends through floors or walls, the metal pipe must be insulated
from the floor or wall system by an air space (Figure
12.17). Sharp bends should be avoided. A 9° vent elbow has a resistance
to flow equivalent to that of a straight section of pipe with a length 10 times
the elbow diameter. Be sure that vents are of rigid construction and resistant to
corrosion by flue gas products. Several types of venting material are available
such as B-vent and other ceramic-type materials. A chimney lined with firebrick
type of terra cotta must be relined with an acceptable vent material if it is to
be used for venting gas-fired appliances.
The same size vent pipe should be used throughout its length. A vent should never
be smaller than the heater outlet except when two or more vents converge from separate
heaters. To determine the size of vents beyond the point of convergence, one-half
the area of each vent should be added to the area of the largest heater’s vent.
Vents should be installed with male ends of inner liner down to ensure condensate
is kept within pipes on a cold start. The vertical length of each vent or stack
should be at least 2 feet greater than the length between horizontal connection
and stack. Remember that the more conductive the unit, the lower the temperature
of combustion and the more byproducts of combustion are likely to be produced. These
by-products are sometimes referred to as soot and creosote. These by-products will
build up in vents, stacks, and chimneys. They are extremely flammable and can result
in fire in these units that is hot enough to penetrate the heat shielding and throw
burning material onto the roof of the home.
The vent should be run at least 3 feet above any projection within 20 feet of the
building to place it above a possible pressure zone due to wind currents (Figure
12.18). A weather cap should prevent entrance of rain and snow. Gas-fired
space heaters, as well as gas furnaces and water heaters, must be equipped with
a backdraft diverter (Figure
12.19) to protect heaters against downdrafts and excessive updrafts. Only
draft diverters approved by the AGA should be used.
The combustion chamber or firebox must be insulated from the floor, usually with
airspace of 15 to 18 inches. The firebox is sometimes insulated within the unit
and thus allows for lesser clearance firebox combustibles.
Floors should be protected where coal space heaters are located. The floor protection
allows hot coals and ashes to cool off if dropped while being removed from the ash
chamber. Noncombustible walls and materials should be used when they are exposed
to heated surfaces. For space heaters, a top or ceiling clearance of 36 inches,
a wall clearance of 18 inches, and a smoke pipe clearance of 18 inches are recommended.
Hydronic Systems
Hydronic (circulating water) systems involving traditional baseboards can be single-pipe
or two-pipe. Radiant systems are also an option. All hydronic systems require an
expansion tank to compensate for the increase in water volume when it is heated
(i.e., the volume of 50ºF [10ºC] water increases almost 4% when it is heated to
200ºF [93ºC]). Single-pipe hydronic systems are most commonly used in residences.
They use a single pipe with hot water flowing in a series loop from radiator to
radiator. Massachusetts has a prototype set of hydronic systems requirements
(11).
The drawback to this arrangement is that the temperature of the water decreases
as it moves through each radiator. Thus, larger radiators are needed for those locations
downstream in the loop. A common solution to this is multiple loops or zones. Each
zone has its own temperature control with circulation provided by a small pump or
zone valve in each loop. Two-pipe hydronic systems use a pipe for supplying hot
water to the radiators and a second pipe for returning the water from the radiators
to the boiler.
There are also direct- and reverse-return arrangements. The direct-return system
can be difficult to balance because the pressure drop through the nearest radiator
piping can be significantly less than for the farthest radiator. Reverse-return
systems take care of the balancing problem, but require the expense of additional
piping. Orifice plates at radiator inlets or balancing valves at radiator outlets
can also be used to balance the pressure drops in a direct-return system.
Direct Vent Wall Furnaces
Direct vent wall furnaces are specifically designed for areas where flues or
chimneys are not available or cannot be used. the furnace is directly vented
to the outside and external air is used to support combustion. The air on
the inside is warmed as it recirculates around a sealed chamber.
Cooling
Air Conditioning
Many old homes relied on passive cooling—opening windows and doors and using shading
devices—during the summer months. Homes were designed with windows on opposite walls
to encourage cross ventilation and large shade trees reduced solar heat gains. This
approach is still viable, and improved thermal performance (insulating value) windows
are available that allow for larger window areas to let in more air in the summer
without the heat loss penalty in the winter. However, increased outdoor noise levels,
pollution, and security issues make relying on open windows a less attractive option
in some locations today.
An air conditioning system of some kind may be installed in the home. It may be
a window air conditioner or through-the-wall unit for cooling one or two rooms,
or a central split-system air conditioner or heat pump. In any event, the performance
of these systems, in terms of providing adequate comfort without excessive energy
use, should be investigated. The age of the equipment alone will provide some indication.
If the existing system is more than 10 years old, replacement should be considered
because it is much less efficient than today’s systems and nearing the end of its
useful life.
The refrigerant commonly used in today’s residential air conditioners is R-22. Because
of the suspicion that R-22 depletes the ozone layer, manufacturers will be prohibited
from producing units with R-22 in 2010. The leading replacements for R-22 are R-134A
and R-410A, and new products are now available with these nonozone-depleting refrigerants.
The performance measure for electric air conditioners with capacities less than
65,000 BTU is the seasonal energy efficiency ratio (SEER). SEER is a rating of cooling
performance based on representative residential loads. It is reported in units of
BTU of cooling per watt per hour of electric energy consumption. It includes energy
used by the unit’s compressor, fans, and controls. The higher the SEER, the more
efficient the system. However, the highest SEER unit may not provide the most comfort.
In humid climates, some of the highest SEER units exhibit poor dehumidification
capability because they operate at higher evaporator temperatures to attain the
higher efficiency. A SEER of at least 10 is required by the National Appliance Energy
Conservation Act of 1987 for conventional central split-system air-cooled systems.
The Department of Energy announced a SEER of 13 effective January 2006.
Cooling system options vary widely, depending on the level of control and comfort
desired by the homeowner. Fans can increase circulation and reduce cooling loads,
but they may be unsatisfactory in hot climates because their cooling capability
is directly limited by outdoor conditions. Radiant barriers can reduce cooling loads
in very hot climates. Evaporative coolers can be a relatively inexpensive and effective
method of cooling in dry climates, such as the Southwest. Electric air conditioning
maintains a comfortable indoor temperature and humidity even under the most severe
outdoor conditions. More than 75% of new homes in the United States are equipped
with some form of central air conditioning: 50% of the homes in the Northeast, 75%
in the Midwest, 95% in the South, and approximately 60% in the West. Electric air
conditioning removes moisture from the air and reduces its temperature. It can be
a good investment because, in most parts of the country, the payback is significant
when the house is sold.
Electric air conditioners that use the vapor-compression, refrigeration cycle are
available in a variety of sizes and configurations, ranging from small window units
to large central systems. The most common form of central air conditioning is a
split-system with a warm air furnace (Figure
12.20). The same ductwork is used for distributing conditioned air during
the heating and cooling seasons. Supply air is cooled and dehumidified as it passes
over an A-shaped evaporator coil. The liquid refrigerant evaporates inside the coil
as it absorbs heat from the air. The refrigerant gas then travels through refrigerant
piping to the outdoor unit, where it is pressurized in an electrically driven compressor,
raising its temperature and pressure, and returned to a liquid state in the condenser
as it releases, or dumps, the heat to the outdoors. A fan draws outdoor air in over
the condenser coil. The use of two-speed indoor fans can be advantageous in this
type of system because the cooling load often requires higher airflows than the
heating load. The lower speed can be used for the heating season and for improved
dehumidification performance during the cooling season. The condenser unit for a
house air conditioner is shown in
Figure 12.21.
Circulation Fans
Air movement can make a person feel comfortable even when dry-bulb temperatures
are elevated. A circulation fan (ceiling or portable) that creates an airspeed of
150 to 200 feet per minute can compensate for a 4ºF (-16ºC) increase in temperature.
Ceiling circulation fans also can be beneficial in the heating season by redistributing
warm air that collects along the ceiling, but they can be noisy.
Evaporation Coolers
In dry climates, as in the southwestern United States, an evaporative cooler or
“swamp” cooler may provide sufficient cooling. This system cools an airstream by
evaporating water into it; the airstream’s relative humidity increases while the
dry-bulb temperature decreases. A 95ºF (35ºC), 15% relative humidity airstream can
be conditioned to 75ºF (24ºC), 50% relative humidity. The simplest direct systems
are centrally located and use a pump to supply water to a saturated pad over which
the supply air is blown. Indirect systems use a heat exchanger between the airstream
that is cooled by evaporating water and the supply airstream. The moisture level
of the supply airstream is not affected as it is cooled.
Evaporation coolers have lower installation and operating costs than electric air
conditioning. No ozone-depleting refrigerant is involved. They provide high levels
of ventilation because they typically condition and supply 100% outside air.
The disadvantages are that bacterial contamination can result if not properly maintained
and they are only appropriate for dry, hot climates.
Safety
Cooling homes with window air conditioners requires attention to the maintenance
requirements of the unit. The filter must be cleaned or replaced as recommended
by the manufacturer, and the drip pan should be checked to ensure that proper drainage
from the unit is occurring. The pans should be rinsed and disinfected as recommended
by the manufacturer. Both bacteria and fungi can establish themselves in these areas
and present serious health hazards.
Condensation forms on the cooling coils of central air units inside and outside
the home. These units should have a properly installed drip pan and should be drained
according to the manufacturer’s instructions. They also should receive routine maintenance,
flushing, and disinfection. In the spring, before starting the air conditioner,
the unit should be checked by a professional or someone familiar with the operation
of the system. This is a good time to check drip line(s) for conditions such as
plugs, cracks, or bacterial contamination because many of these lines are plastic.
The drip pan should be cleaned thoroughly and disinfected if necessary or replaced.
A plugged drip line can cause water damage by overflow from the drip pan. In the
fall, the heat unit also should be checked before starting the system. Care should
be taken with both window air conditioning units and central air systems to use
quality air filters that are designed for the specific units and meet the specifications
required by the system’s manufacturer.
The housing inspector should be on the alert for unvented, open flame heaters. Coil-type,
wall-mounted water heaters that do not have safety relief valves are not permitted.
Kerosene (portable) units for cooking or heating should be prohibited. Generally,
open-flame portable units are not allowed under fire safety regulations.
In oil heating units, other than integral tank units, the oil must be filled and
vented outside the building. Filling oil within buildings is prohibited. Cutoff
switches should be close to the entry but outside of a boiler room.
Chimneys
Chimneys (Figure
12.22) are often an integral part of a building. Masonry chimneys must be
tight and sound; flues should be terra cotta-lined; and, where no linings are installed,
the brick should be tight to permit proper draft and elimination of combustion gases.
Chimneys that act as flues for gas-fired equipment must be lined with either B vent
or terra cotta. When a portion of the chimney above the roof either loses insulation
or the insulation peels back, it indicates potential poisonous gas release or water
leakage problems and a need for rebuilding. Exterior deterioration of the chimney,
if neglected too long, will permit erosion from within the flues and eventually
block the flue opening.
Rusted flashing at the roof level will also contribute to the chimney’s deterioration.
Efflorescence on the inside wall of the chimney below the roof and on the outside
of the chimney, if exposed, will show salt accumulations—a telltale sign of water
penetration and flue gas escape and a sign of chimney deterioration. During rainy
seasons, if terra cotta chimneys leak, dark areas show the number of flues inside
the masonry chimney so they can actually be counted. When this condition occurs,
it usually requires 2 or 3 months to dry out. After drying out, the mortar joints
are discolored (brown). After a few years of this type of deterioration, the joints
can be distinguished whether the chimney is wet or dry. These conditions usually
develop when coal is used and become more pronounced 2 to 5 years after conversion
to oil or gas.
An unlined chimney can be checked for deterioration below the roofline by looking
for residue deposited at the base of the chimney, usually accessible through a cleanout
(door or plug) or breaching. Red granular or fine powder showing through coal or
oil soot will generally indicate, if in quantity (a handful), that deterioration
is excessive and repairs are needed.
Unlined chimneys with attached gas units will be devoid of soot, but will usually
show similar telltale brick powder and deterioration. Manufactured gas has a greater
tendency to dehydrate and decompose brick in chimney flues than does natural gas.
For gas installations in older homes, utility companies usually specify chimney
requirements before installlation; therefore, older chimneys may require the installation
of terra cotta liners, nonlead-lined copper liners, stainless steel liners, or transit
pipe. Black carbon deposits around the top of the chimney usually indicate an oil
burner operation using a low air ratio and high oil consumption. Prolonged operation
in this burner setting results in long carbon water deposits down the chimney for
4 to 6 feet or more and should indicate to the inspector a possibility of poor burner
maintenance. This will accent the need to be more thorough on the next inspection.
This type of condition can result from other causes, such as improper chimney height,
or exterior obstructions, such as trees or buildings, that will cause downdrafts
or insufficient draft or contribute to a faulty heating operation. Rust spots and
soot-mold usually occur on deteriorated galvanized smoke pipe.
Fireplaces
Careful attention should be given to construction of the fireplace (Figure
12.23). Improperly built fireplaces are a serious safety and fire hazard.
The most common causes of fireplace fires are thin walls, combustible materials
such as studding or trim against sides and back of the fireplace, wood mantels,
and unsafe hearths.
Fireplace walls should be no less than 8 inches thick; if built of stone or hollow
masonry units, they should be no less than 12 inches thick. The faces of all walls
exposed to fire should be lined with firebrick or other suitable fire-resistant
material. When the lining consists of 4 inches of firebrick, such lining thickness
may be included in the required minimum thickness of the wall.
The fireplace hearth should be constructed of brick, stone, tile, or similar incombustible
material and should be supported on a fireproof slab or on a brick arch. The hearth
should extend at least 20 inches beyond the chimney breast and no less than 12 inches
beyond each side of the fireplace opening along the chimney breast. The combined
thickness of the hearth and its supporting construction should be no less than 6
inches at any point.
It is important that all wooden beams, joists, and studs are set off from the fireplace
and chimney so that there is no less than 2 inches of clearance between the wood
members and the sidewalls of the fireplace or chimney and no less than 4 inches
of clearance between wood members and the back wall of the fireplace.
A gas-log set is primarily a decorative appliance. It includes a grate holding ceramic
logs, simulated embers, a gas burner, and a variable flame controller. These sets
can be installed in most existing fireplaces. There are two principal types: vented
and unvented. Vented types require a chimney flue for exhausting the gases. They
are only 20% to 30% efficient; and most codes require that the flue be welded open,
which results in an easy exit path for heated room air. Unvented types operate like
the burner on a gas stove and the combustion products are emitted into the room.
They are more efficient because no heat is lost up the flue and most are equipped
with oxygen-depletion sensors. However, unvented types are banned in some states,
including Massachusetts and California. Gas fireplaces incorporate a gas-log set
into a complete firebox unit with a glass door. Some have built-in dampers, smoke
shelves, and heat-circulating features that allow them to provide both radiant and
convective heat. Units can have push-button ignition, remote control, variable heat
controls, and thermostats. Gas fireplaces are more efficient than gas logs, with
efficiencies of 60% to 80%. Many draw combustion air in from the outside and are
direct vented, eliminating the need for a chimney. Some of these units are wall-furnace
rated. There are also electric fireplaces that provide the ambience of a fire and,
if desired, a small amount of resistance heat. These units have no venting requirements.
The advantages are that there are no ashes or flying sparks that occur with wood-burning
fireplaces. They are not affected by wood-burning bans imposed in some areas when
air quality standards are not met. Direct-vented gas or electric models eliminate
the need for a chimney.
The disadvantages are that the cost for equipment and running the gas line can be
high.
References
- US Census Bureau. Rooms, number
of bedrooms, and house heating fuel: 2000. Census 2000 Summary File 4 (SF4).
Washington, DC: US Census Bureau; 2000. Available from URL:
http://factfinder.census.gov
[select Data Sets, then select Census 2000 Summary File 4 (SF 4) - Sample Data].
- National Energy Efficiency Committee.
Building: heat pumps; application of heat pumps in Singapore. Singapore:
National Environment Agency; 2003. Available from URL:
http://www.neec.gov.sg/building/heat_pump.shtm.
- National Energy Efficiency Committee.
Renewables: solar energy. Singapore: National Environment Agency; no date.
Available from URL:
http://www.neec.gov.sg/renewables/solar.shtm.
- Center for Disease Control.
Basic housing inspection. Atlanta: US Department of Health and Human Services;
1976.
- Fairfax County. Fuel storage
tanks. Fairfax, VA: Fairfax County; 2004. Available from URL:
http://www.co.fairfax.va.us/dpwes/construction/fuel_tanks.htm.
- Wisconsin Department of Commerce.
Environmental services—residential fuel oil and gasoline storage tanks.
Madison, WI: Wisconsin Department of Commerce; 2004. Available from URL:
http://www.commerce.state.wi.us/ER/ER-BST-ResTk.html.
- Michigan Department of Environmental
Quality. FAQ: Home heating oil tanks, Lansing, MI: Michigan Department of
Environmental Quality; no date. Available from URL:
http://www.michigan.gov/deq/0,1607,7-135-3311
4115_4238-9379--,00.html.
- US Environmental Protection
Agency. Overview of the federal underground storage tank program. Washington,
DC: U.S. Environmental Protection Agency; no date. Available from URL:
http://www.epa.gov/swerust1/overview.htm.
- US Department of Housing and
Urban Development. Initiatives Programs. Washington, DC: US Department of
Housing and Urban Development; 2004. Available from URL:
http://www.hud.gov/offices/cpd/energyenviron/energy/initiatives.
- US Environmental Protection
Agency. Sources of indoor air pollution—asbestos. Washington, DC: U.S. Environmental
Protection Agency; no date. Available from URL:
http://www.epa.gov/iaq/asbestos.html.
- The Commonwealth of Massachusetts
Board of Building Regulations and Standards (BBRS). Hydronic system requirements.
Boston: The Commonwealth of Massachusetts Board of Building Regulations and
Standards (BBRS); no date. Available from URL:
http://www.mass.gov/bbrs/commntry/cmpxhydr.htm.
Additional Sources of Information
McQuiston FC, Parker JD, Spitler JD. Heating, ventilation, and air conditioning:
analysis and design. 5th ed. Hoboken, NJ: John Wiley and Sons, Inc.; 2000.
Kittle JL. Home heating and air conditioning systems. New York: McGraw-Hill; 1990.
Pita EG. Air conditioning principles and systems: an energy approach. 4th ed. New
York: Prentice Hall; 2001.