Item No. | Description | Points Deducted |
05 | PW system halogen analyzer maintained, operated, calibrated | 0 |
06 | Halogen analyzer chart recorder maintained, operated, records; Sampling, records | 0 |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
10 | Swimming pools / spas maintained, safety equipment | 0 |
13 | Management, knowledge, monitoring | 3 |
16 | Potentially hazardous food temperatures storage, preparation display, service, transportation | 0 |
17 | Temperature practices storage, preparation display, service, transportation; Thawing | 0 |
19 | Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 0 |
26 | Food-contact surfaces equipment / utensils clean; Safe | 0 |
29 | Facilities convenient, accessible, designed, installed | 3 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
36 | Lighting provided, shielded | 0 |
|
Selected Item Details
|
Item No.:
05
|
|
Site:
Potable Water-Halogen Analyzer (Distribution) |
Violation:
A manual test by the inspector at the far point measured the halogen residual at 0.48 ppm. The halogen analyzer read 0.72 ppm. The halogen analyzer was out of calibration by at least 0.24 ppm. |
Recommendation:Ensure that the free residual halogen measured by the halogen analyzer is ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test. |
|
|