Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: MSC Lirica Cruise line: MSC Cruises (Mediterranean Shipping Company) Inspection Date: 11/18/2006 Score: 94
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
05PW system halogen analyzer maintained, operated, calibrated0
06Halogen analyzer chart recorder maintained, operated, records; Sampling, records0
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
13Management, knowledge, monitoring3
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
17Temperature practices storage, preparation display, service, transportation; Thawing0
19Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored0
21Nonfood-contact surfaces designed, constructed, maintained, installed, located0
26Food-contact surfaces equipment / utensils clean; Safe0
29Facilities convenient, accessible, designed, installed3
33Decks / bulkheads / deckheads construction, repair, clean0
36Lighting provided, shielded0
Selected Item Details
Item No.: 05
Site: Potable Water-Halogen Analyzer (Distribution)
Violation: A manual test by the inspector at the far point measured the halogen residual at 0.48 ppm. The halogen analyzer read 0.72 ppm. The halogen analyzer was out of calibration by at least 0.24 ppm.
Recommendation:Ensure that the free residual halogen measured by the halogen analyzer is ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
*Inspections scores of 85 or lower are NOT satisfactory