Item No. | Description | Points Deducted |
05 | PW system halogen analyzer maintained, operated, calibrated | 0 |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
09 | Swimming pools / spas halogen residuals | 0 |
19 | Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored | 0 |
20 | PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated | 2 |
22 | Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits | 0 |
41 | Child Activity Centers facilities, diaper changing, operation | 0 |
|
Selected Item Details
|
Item No.:
05
|
|
Site:
Potable Water-FAR POINT |
Violation:
THE MANUAL READINGS AT THE POTABLE WATER DISTRIBUTION FAR POINT WERE 1.5 PPM (ENGINEER) 1.6 PPM (INSPECTOR) AND THE HALOGENATION CHART-RECORDER SHOWED A READING OF 1.2 PPM. |
Recommendation:Ensure that the free residual halogen measured by the halogen analyzer is ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test. |
|
|