Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Caribbean Princess Cruise line: Princess Cruises Inspection Date: 11/02/2008 Score: 100
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
06Halogen analyzer chart recorder maintained, operated, records; Sampling, records0
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
19Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
27Equipment / utensils non-food-contact surfaces clean0
33Decks / bulkheads / deckheads construction, repair, clean0
Selected Item Details
Item No.: 06
Site: Potable Water-Distribution Nework - Aft
Violation: The ship's potable water distribution network was divided into forward and aft distribution loops from the lower to upper decks. According to staff, there was no piping which joined these loops, but there was only a single monitoring analyzer and chart recorder installed for the forward loop on the bridge on deck 14. There was no analyzer or chart recorder at the far point for the aft distribution loop.
Recommendation:Ensure that a halogen analyzer-chart recorder is installed at a distant point in the potable water distribution system where a significant water flow exists. In cases where dual distribution loops exist, and no pipes connec the loops, ensure that an analyzer and chart recorder is installed on each loop.
*Inspections scores of 85 or lower are NOT satisfactory