Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Celebrity Infinity Cruise line: Celebrity Cruises Inspection Date: 06/29/2007 Score: 96
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment1
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated2
21Nonfood-contact surfaces designed, constructed, maintained, installed, located0
26Food-contact surfaces equipment / utensils clean; Safe0
27Equipment / utensils non-food-contact surfaces clean0
33Decks / bulkheads / deckheads construction, repair, clean1
34Plumbing fixtures / supply lines / drain lines / drains installed, repair0
36Lighting provided, shielded0
41Child Activity Centers facilities, diaper changing, operation0
Selected Item Details
Item No.: 08
Site: Potable Water-
Violation: The comprehensive cross-connection control program did not list the location and the method/device used.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-
Violation: A backflow protection device was not installed on the potable water line supplying the hose in the photography laboratory.
Recommendation:Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Site: Potable Water-
Violation: Potable water lines were not striped blue in the aft whirlpool pump room or the garbage room.
Recommendation:Ensure that potable water piping and fittings are painted or stripped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
*Inspections scores of 85 or lower are NOT satisfactory