Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Oosterdam Cruise line: Holland America Line Inspection Date: 05/05/2007 Score: 95
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
16Potentially hazardous food temperatures storage, preparation display, service, transportation5
19Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored0
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated0
21Nonfood-contact surfaces designed, constructed, maintained, installed, located0
24Sanitizing rinse temperature, concentration, time0
28Equipment / utensil / linen / single / service storage, handling, dispensed; Clean frequency0
33Decks / bulkheads / deckheads construction, repair, clean0
34Plumbing fixtures / supply lines / drain lines / drains installed, repair0
36Lighting provided, shielded0
999Miscellaneous0
Selected Item Details
Item No.: 08
Site: Potable Water-Cross-Connection Control Program
Violation: The various Ecolab chemical dispensers located in pantries, lockers, galleys and other areas throughout the ship have potable water connections and manufacturer installed backflow prevention devices, but these devices are not on the ship's list of cross-connections and no inspection records are provided either.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Galley-Deck 3 Glass Wash
Violation: There was steady leak at the backflow prevention device on the glasswash machine.
Recommendation:Ensure that backflow prevention devices are periodically inspected and any failed units are replaced.
*Inspections scores of 85 or lower are NOT satisfactory