"Accessibility requirements
can vary across a wide range. A standard of total accessibility would require
that every entrance, doorway, bathroom, parking space, and portion of buildings
and grounds be accessible. Many designers and builders have interpreted the term
`accessible' to mean this type of standard. The Committee does not intend to impose
such a standard. Rather, the Committee intends to use a standard of `adaptable'
design, a standard developed in recent years by the building industry and by advocates
for handicapped individuals to provide usable housing for handicapped persons
without necessarily being significantly different from conventional housing."
(House Report at 26)
The
Department has determined that a requirement that units with lofts or multiple
stories in elevator buildings be equipped with internal elevators, chair lifts,
or other means of access to lofts or upper stories would make accessible housing
under the Fair Housing Act significantly different from conventional housing,
and would be inconsistent with the Act's "modest accessibility requirements".
(See House Report at 25.)
The Department also has determined that a requirement that dwelling units with
design features, such as sunken living rooms, must provide some means of access,
such as ramps or lifts, as submitted in the proposed guidelines (55 FR 24380)
is inconsistent with the Act's modest accessibility requirements. Sunken living
rooms are not an uncommon design feature. To require a ramp or other means of
access to such an area, at the time of construction, would reduce, perhaps significantly,
the space provided by the area. The reduced space might interfere with the use
and enjoyment of this area by a resident who is not disabled, or whose disability
does not require access by means of a ramp or lift. The Department believes that
had it maintained in the final Guidelines the access specifications for design
features, such as sunken living rooms, as set forth in the proposed guidelines,
the final Guidelines would have interfered unduly with a developer's choice of
design, or would have eliminated a popular design choice. Accordingly, the final
Guidelines provide that access is not required to design features, such as a sunken
living room, provided that the area does not have the effect of interrupting the
accessible route through the remainder of the unit.
The Department believes
that the installation of a ramp or deck in order to make a sunken room accessible
is the type of later adaptation that easily can be made by a tenant. The Department,
however, does require that design features, such as a split-level entry, which
is critical to providing an accessible route into and through the unit, must provide
a ramp or other means of access to the accessible route.
In order to comply
with the Act's requirement of an accessible route into and through covered dwelling
units, the Department has revised the Guidelines for Requirement 4 to provide
separate technical guidance for two types of dwelling units:
- single-story
dwelling units, including single-story dwelling units with design features such
as a loft or a sunken living room; and
-
multistory dwelling units in elevator buildings. (Definitions for "single-story
dwelling unit," "loft," "multistory dwelling unit" and "story" have been included
in Section 2 of the final Guidelines.)
"Single-story
dwelling unit" is defined as a dwelling unit with all finished living space located
on one floor.
"Loft"
is defined as an intermediate level between the floor and ceiling of any story,
located within a room or rooms of a dwelling.
"Multistory
dwelling unit" is defined as a dwelling unit with finished living space located
on one floor and the floor or floors immediately above or below it.
"Story" is defined
as that portion of a dwelling unit between the upper surface of any floor and
the upper surface of the floor next above, or the roof of the unit. Within the
context of dwelling units, the terms "story" and "floor" are synonymous.
For single-story
dwelling units and multistory dwelling units, the Guidelines for Requirement 4
are as follows:
-
For single-story dwelling units, the design specifications for changes in level,
are the same as proposed in the Option One guidelines. Changes in level within
the dwelling unit with heights between 1/4 inch and 1/2 inch are beveled with
a slope no greater than 1:2. Changes in level greater than 1/2 inch (excluding
changes in level resulting from design features such as a loft or a sunken living
room) must be ramped or must provide other means of access. For example, split-level
entries must be ramped or use other means of providing and accessible route into
and through the dwelling unit.
For single-story dwelling units with design
features such as a loft or a raised or sunken functional area, such as a sunken
living room, the Guidelines specify that:
-
access to lofts is not required, provided that all spaces other than the loft
are on an accessible route; and
-
design features such as a sunken living room are also exempt from the access specifications,
provided that the sunken area does not interrupt the accessible route through
the remainder of the unit.
-
In multistory dwelling units in buildings with elevators, access to the additional
story, or stories, is not required, provided that the story of the unit that is
served by the building elevator
-
is the primary entry to the unit;
-
complies with Requirements 2 through 7 with respect to the rooms located on the
entry/accessible level; and (3) contains a bathroom or powder room which complies
with Requirement 7. (As previously noted, multistory units in buildings without
elevators are not considered ground floor units, and therefore are exempt.)
The
Department believes that the foregoing revisions to the Guidelines for Requirement
4 will provide individuals with handicaps the degree of accessibility intended
by the Fair Housing Act, without increasing significantly the cost of multifamily
housing.
Comment.
Two commenters suggested that the same adaptability requirement that is applied
to bathrooms should be applied to dwelling units with more than one story, or
with lofts, i.e. that stairs, and the wall along the stairs, contain the appropriate
reinforcement to provide for later installation of a wheelchair lift by a disabled
resident, if so desired.
Response: The only blocking or wall reinforcement
required by the Fair Housing Act is the reinforcement in bathroom walls for later
installation of grab bars. As noted earlier in this preamble, the Fair Housing
Act does not actually require that features in covered units be "adaptable", except
for bathrooms. The adaptable feature is the reinforcement in bathroom walls which
allows later installation of grab bars. Accordingly, the Department believes that
a specification for reinforcement of the walls along stairs would exceed the Act's
requirements, because the necessary reinforcement could vary by type of lift chosen,
and more appropriately would be specified and installed as part of the installation
of the lift.
Thresholds
at Exterior Doors/Thresholds to Balconies or Decks
Comment.
A number of commenters from the building industry objected to the provision of
the Option One guidelines that specified that an exterior deck, balcony, patio,
or similar surface may be no more than 3/4 inch below the adjacent threshold.
Several commenters stated that, in many situations, this height is unworkable
for balconies and decks because of waterproofing and safety concerns. This was
a particular concern among commenters from the South Florida building industry,
who stated that the 3/4" height is ineffective for upper floors of high rise buildings
in a coastal environment and invites water control problems. Others noted that
the suggestion of a wooden decking insert, or the specification of a 3/4 inch
maximum change in level, in general, might conflict with fire codes.
Response:
In response to these concerns, and mindful that Congress did not intend the accessibility
requirements of the Act to override the need to protect the physical integrity
of multifamily housing, the Department has included two additional provisions
for changes in level at thresholds leading to certain exterior surfaces, as a
protective measure against possible water damage. The final Guidelines provide
that exterior deck, patio or balcony surfaces should be no more than 1/2 inch
below the floor level of the interior of the dwelling unit, unless they are constructed
of impervious material such as concrete, brick or flagstone. In such case, the
surface should be no more than 4 inches below the floor level of the interior
dwelling unit, unless the local code requires a lower drop. Additionally, the
final Guidelines provide that at the primary entry doors to dwelling units with
direct exterior access, outside landing surfaces constructed of impervious materials
such as concrete, brick, or flagstone should be no more than 1/2 inch below the
floor level of the interior of the dwelling unit. The Guidelines further provide
that the finished surface of this area, located immediately outside the entry
door, may be sloped for drainage, but the sloping may be no more than 1/8 inch
per foot.
In response to commenters' concern that the Guidelines for an accessible route
to balconies and decks may conflict with certain building codes that require higher
thresholds, or balconies or decks lower than the 3/4 inch specified by the Guidelines,
the Department notes that the Guidelines are "recommended" design specifications,
not building code "requirements". Accordingly, the Guidelines cannot preempt State
or local law. However, the builder confronted with local requirements that thwart
the particular means of providing accessibility suggested by the Guidelines is
under a duty to take reasonable steps to provide for accessibility by other means
consistent with local law constraints and considerations of cost-effectiveness,
in order to provide dwelling units that meet the specific accessibility requirements
of the Fair Housing Act.
Guidelines
for Requirement 5
The Guidelines for Requirement 5 present design
specifications for providing dwelling units that contain light switches, electrical
outlets, thermostats, and other environmental controls in accessible locations,
as required by §100.205(c)(2)(ii).
The Department has adopted the Option One guidelines for Requirement 5 with minor
technical changes. The final Guidelines clarify that to be in an accessible location
within the meaning of the Act, the maximum height for an environmental control,
for which reach is over an obstruction, is 44 inches for forward approach (as
was proposed in the Option One guidelines), or 46 inches for side approach, provided
that the obstruction is no more than 24 inches in depth. The inclusion of this
additional specification for side approach is consistent with the comparable provisions
in the ANSI Standard.
Specific comments on the Guidelines for Requirement 5 are as follows:
Comments.
Three commenters stated that lowered thermostats could pose a safety hazard for
children. However, the majority of comments requested clarification as to what
is meant by "other environmental controls". Several commenters from the disability
community requested that circuit breakers be categorized as environmental controls.
Other commenters asked whether light and fan switches on range hoods fall within
the category of light switches and environmental controls.
Response: With
regard to concerns about lowered thermostats, the Act specifically identifies
"thermostats" as one of the controls that must be in accessible locations, and
the mounting heights specified in the Guidelines are necessary for an accessible
location. The only other environmental controls covered by the Guidelines for
Requirement 5 would be heating, air conditioning or ventilation controls (e.g.,
ceiling fan controls). The Department interprets the Act's requirement of placing
environmental controls in accessible locations as referring to those environmental
controls that are used by residents or tenants on a daily or regular basis. Circuit
breakers do not fall into this category, and therefore are not subject to accessible
location specifications. Light and fan switches on range hoods are appliance controls
and therefore are not covered by the Act.
Comment.
Other commenters asked whether light switches and electrical outlets in the inside
corners of kitchen counter areas, and floor outlets are permissible.
Response:
Light switches and electrical outlets in the inside corners of kitchen counters,
and floor outlets, are permissible, if they are not the only light switches and
electrical outlets provided for the area.
Comment.
Another commenter pointed out that some electrical outlets that are installed
specifically to serve individual appliances, such as refrigerators or microwave
ovens, cannot realistically be mounted in an accessible location.
Response:
Electrical outlets installed to serve individual appliances, such as refrigerators
or built-in microwave ovens, may be mounted in non- accessible locations. These
are not the type of electrical outlets which a disabled resident or tenant would
need access to on a regular or frequent basis.
Comment.
One commenter stated that Figure 3 in the proposed guidelines (Figure 2 in the
final Guidelines) specifies a reach requirement more stringent than the ANSI Standard.
Response:The ANSI Standard presents reach ranges for both forward
and side approaches for two situations:
-
unobstructed; and
-
over an obstruction.
The proposed guidelines specified only the heights for forward reach, because
those heights also are usable in side approach. The diagram in Figure 2 (formerly
Figure 3) showing forward reach is identical to that of Figure 5 in the ANSI Standard.
The ANSI Standard also includes a figure (Figure 6) for side reach that permits
higher placement. The reach range for forward approach was the only one referenced
in the proposed guidelines for use in the dwelling unit, because it was considered
simpler and easier to use a single specification that would work in all situations.
The reach range for forward approach has been retained in the final Guidelines
for situations where there is no built-in obstruction in order to assure usability
when the unit was furnished. However, the final Guidelines have added the specification
for side reach over a built-in obstruction that is consistent with the ANSI requirement,
and that permits placement two inches higher than forward reach.
Guidelines
for Requirement 6
The Guidelines for Requirement 6 present design
standards for installation of reinforcement in bathroom walls to allow for later
installation of grab bars around the toilet, tub, shower stall and shower seat
where such facilities are provided, as required by §100.205(c)(3)(iii).
The Department
adopted the Option One guidelines for Requirement 6 with two modifications. First,
the final Guidelines provide that a powder room is subject to the requirement
for reinforced walls for grab bars when the powder room is the only toilet facility
located on the accessible level of a covered multistory dwelling unit. Second,
the final Guidelines further clarify that reinforced bathroom walls will meet
the accessibility requirement of §100.205(c)(3)(iii), if reinforced areas are
provided at least at those points where grab bars will be mounted.
Specific comments on this guideline were as follows:
Comment.
A number of commenters requested that the Department specify the dimensions for
grab bar reinforcement, and suggested that grab bar reinforcing material run horizontally
throughout the entire length of the space given for grab bars, as provided by
the ANSI standard. These commenters stated that if this type of reinforcement
was required, residents could locate more easily the studs for future grab bar
installation, and have flexibility in the placement of grab bars for optimal use,
and safety in bathrooms. One commenter noted that many grab bars are of such a
length that they require an intermediate fastener, but the proposed standard does
not permit intermediate fastening. Two commenters recommended that the final Guidelines
follow ANSI and UFAS standards for requirements for mounting grab bars. One commenter
recommended the installation of panels of plywood behind bathroom walls because
this would provide greater flexibility in the installation of grab bars.
Response: The illustrations of grab bar wall reinforcement accompanying
the Guidelines for Requirement 6 are intended only to show where reinforcement
for grab bars is needed. The illustrations are not intended to prescribe how the
reinforcing should be provided, or that the bathtub or shower is required to be
surrounded by three walls of reinforcement. The additional language added to the
Guidelines is to clarify that the Act's accessibility requirement for grab bar
reinforcement is met if reinforced areas are provided, at a minimum, at those
points where grab bars will be mounted. The Department recognizes that reinforcing
for grab bars may be accomplished in a variety of ways, such as by providing plywood
panels in the areas illustrated, or by installing vertical reinforcement (in the
form of double studs, for example) at the points noted on the figures accompanying
the Guidelines.
Comment.
Several commenters stated that the final Guidelines should incorporate Option
Two's specification of reinforcement for shower seats when shower stalls are provided.
Response:The Fair Housing Act only requires reinforcement for later
installation of grab bars. The Act does not cover reinforcement for shower seats;
rather, it mentions shower seats (if provided) as an area where grab bar reinforcement
would be needed. However, as will be discussed more fully in the following section
concerning the Guidelines for Requirement 7 (Usable Bathrooms), reinforcement
for shower seats would provide adaptability to increase usability of shower stalls,
and is a design option available to builders and developers in designing "usable"
bathrooms.
Comment.
One commenter recommended that the final Guidelines incorporate Option Two's specification
that prefabricated tub/shower enclosures would have to be fabricated with reinforcement
for grab bar enclosures.
Response: The Department did not incorporate
this specification in the final Guidelines. The Department believes that it is
inappropriate to specify product design. A builder should have the flexibility
to choose how reinforcement for grab bars will be provided.
Comment.
Two commenters stated that half-baths should also contain grab-bar reinforcements.
Response: Half-baths are not considered "bathrooms", as this term
is commonly used, and, therefore are not subject to the bathroom wall reinforcement
requirement, unless a half-bath facility is the only restroom facility on the
accessible level of a covered multistory dwelling unit.
Comment.
One commenter requested that the final Guidelines incorporate language clearly
to specify that the builder's responsibility is limited solely to wall reinforcement,
and later installation is the responsibility of the resident or tenant.
Response:
It is unnecessary to incorporate the suggested language in the final Guidelines.
The Guidelines for Requirement 6 are solely directed to reinforcement. No guidelines
are provided for the actual installation of grab bars. Accordingly, there should
be no confusion on this issue.
Guidelines
for Requirement 7
The Guidelines for Requirement 7 present design
specifications for providing usable kitchens and bathrooms such that an individual
in a wheelchair can maneuver about the space, as required by §100.205(c)(3)(iv).
For usable kitchens, the Department adopted the Option One guidelines with
one change. The Department has eliminated the specification that controls for
ranges and cooktops be placed so that reaching across burners is not required.
For usable
bathrooms, the final Guidelines provide two alternative sets of design specifications.
The Fair Housing Act requires that an accessible or "usable" bathroom is one which
provides sufficient space for an individual in a wheelchair to maneuver about.
The two sets of specifications provide different approaches as to how compliance
with this maneuvering space requirement may be accomplished. The first set of
specifications also includes size dimensions for shower stalls, but only when
a shower stall is the only bathing facility provided in a dwelling unit. Additionally,
either set of specifications is applicable to powder rooms, when a powder room
is the only restroom facility on the accessible level of a covered multistory
dwelling unit.
With the exception of the inclusion of shower stall dimensions,
the first set of "usable bathroom" specifications remain the same as the Option
One guidelines for usable bathrooms. The second set of "usable bathroom" specifications
provide somewhat greater accessibility than the first set, but would be applicable
only to one bathroom in a dwelling unit that has two or more bathrooms. The second
set of specifications include clear space specifications for bathrooms with in-swinging
doors and for bathrooms with outswinging doors. This second set of specifications
also provides that toilets must be located in a manner that permits a grab bar
to be installed on one side of the fixture, and provides specifications on the
installation of vanities and lavatories.
To meet the Act's requirements
for usable bathrooms, the final Guidelines provide that
-
in a dwelling unit with a single bathroom, either set of specifications may be
used; and
-
in a dwelling unit with more than one bathroom, all bathrooms in the unit must
comply with the first set of specifications, or, alternatively, at least one bathroom
must comply with the second set of specifications, and all other bathrooms must
be on an accessible route, and must have a usable entry door in accordance with
the guidelines for Requirements 3 and 4.
However, in multistory dwelling units, only those bathrooms on the accessible
level are subject to the Act's requirements for usable bathrooms. Where a powder
room is the only restroom facility provided on the accessible level of a multistory
dwelling unit, the powder must meet either the first set of specifications or
the second set of specifications. All bathrooms and powder rooms that are subject
to Requirement 7, must have reinforcements for grab bars as provided in the Guideline
for Requirement 6.
In developing the final Guidelines for the usable bathroom
requirement, the Department recognized that the Option One guidelines for usable
bathrooms presented the minimum specifications necessary to meet the Act's requirements.
Accordingly, the Department believes that it is appropriate to provide a second
set of specifications which provide somewhat different accessibility accommodations
than the Option One guidelines. The Department believes that by offering two sets
of specifications for usable bathrooms, the Department is providing builders and
developers with more development choices in designing dwelling units that contain
more than one bathroom; and it is providing individuals and families with more
housing options. Builders and developers may design all bathrooms to meet the
minimal specifications of the first set of specifications, or they may design
only one bathroom to meet the somewhat greater accessibility specifications of
the second set. Regardless of which set of usable bathroom specifications is selected
by a builder or developer, all doors to bathrooms and powder rooms must meet the
minimum door width specifications of Requirement 3.
The following presents
a discussion of the specific comments received on usable kitchens and usable bathrooms.
Controls
for Ranges and Cooktops
Comment.
A few commenters stated that the Department lacks authority under the Fair Housing
Act to impose design standards on appliances. The commenter stated that standards
that specify certain design features for appliances in individual dwelling units
exceed the scope of the Department's statutory authority. Other commenters objected
to front range controls as a safety hazard for children. Commenters from the disability
community were strongly supportive of this design specification.
Response.
With respect to usable kitchens, the Act solely requires that kitchens have sufficient
space such that an individual in a wheelchair can maneuver about. Accordingly,
a specification that controls for ranges and cooktops be placed so that they can
be used without reaching across burners is not consistent with the Act's requirement
for usable kitchens.
In the proposed guidelines, the Option One guidelines for usable kitchens specified
that controls should be located so as to be usable without reaching across burners.
As the preamble to the proposed guidelines noted, many standard styles of ranges
and cooktops meeting this specification (other than those with front controls)
are available on the market. However, in reviewing the entire rulemaking history
on the design and constructions requirements, the Department has concluded that
the requirements of the Fair Housing Act did not cover any appliance controls.
Accordingly, this specification was not included in the final Guidelines.
Maneuvering
Space, Adjustable Cabinetry, Fixtures and Plumbing
Comment.
A number of commenters from the disability community stated that it was important
that the Guidelines for both kitchens and bathrooms specify a five-foot turning
radius; adjustable cabinetry, fixtures and plumbing; and fixture controls that
comply with the appropriate provisions of the ANSI Standard.
Response:
The legislative history of the Fair Housing Act clearly indicates that Congress
did not envision usable kitchens and bathrooms to be designed in accordance with
the specifications suggested by the commenters. In House Report No. 711, the Congress
stated as follows:
"The
fourth feature is that kitchens and bathrooms be usable such that an individual
in a wheelchair can maneuver about the space. This provision is carefully worded
to provide a living environment usable by all. Design of standard sized kitchens
and bathrooms can be done in such a way as to assure usability by persons with
disabilities without necessarily increasing the size of space. The Committee intends
that such space be usable by handicapped persons, but this does not necessarily
require that a turning radius be provided in every situation. This provision also
does not require that fixtures, cabinetry or plumbing be of such design as to
be adjustable." (House Report at 27)
Accordingly, the Department is unable to adopt any of the proposals suggested
by the commenters. The Act's requirement for usable kitchens and bathrooms only
specifies maneuverability for wheelchair users, and this maneuverability does
not require the specification advocated by the commenters. (See previous discussion
of this issue in the preamble to the proposed Fair Housing regulations at 53 FR
45005.)
Comment.
Two commenters requested clarification concerning what is meant by "sufficient
maneuvering space". One of the commenters recommended that this term be defined
to include "such space as shall permit a person in a wheelchair to use the features
and appliances of a room without having to leave the room to obtain an approach
to an appliance, work surface, or cabinet".
Response: The Guidelines
for Requirement 7 (usable kitchens and bathrooms) describe what constitutes sufficient
maneuvering space in the kitchen and the bathroom. Additionally, the preamble
to the proposed guidelines explicitly states that sufficient maneuvering space
for kitchens does not require a wheelchair turning radius (55 FR 24381). As noted
in response to the preceding comment, a wheelchair turning radius also is not
required for either usable kitchens or usable bathrooms. The Guidelines for usable
bathroom state that sufficient maneuvering space is provided within the bathroom
for a person using a wheelchair or other assistive device to enter and close the
door, use the fixtures, reopen the door and exit. This specification was not changed
in the final Guidelines.
Kitchen
Work Surfaces
Comment.
One commenter stated that "Element 12" in the chart accompanying the Guidelines
for Requirement 2 (public and common use areas) seems to require a portion of
the kitchen counters to be accessible since they are work surfaces. This commenter
stated that if this interpretation is correct then it should be made clear in
the Guidelines.
Response: The commenter's interpretation is not correct.
The chart accompanying the Guidelines for Requirement 2 is only applicable to
the public and common use areas, not to individual dwelling units.
Showers
Comments.
Several commenters requested that the final Guidelines provide dimensions on the
appropriate width and height of showers and shower doors. Another commenter asked
whether showers were required to comply with dimensions specified by the ANSI
Standard.
Response: The final Guidelines for usable bathrooms (the
first set of specifications) specify size dimensions for shower stalls in only
one situation -- when the shower stall is the only bathing facility provided in
a covered dwelling unit. The Department believes that, where a shower stall is
the only bathing facility provided, size specification for the shower stall is
consistent with the Act's requirement for usable bathrooms. However, if a shower
stall is not the only bathing facility provided in the dwelling unit, then the
only specification for showers, appropriate under the Act, concerns reinforced
walls in showers. (The titles under the illustrations (figures) related to showers
in the final Guidelines for Requirement 6 have been revised to make it clear that
the figures are specifying only the different areas required to be reinforced
in showers of different sizes, not the required sizes of the shower stalls.)
In-swinging
Bathroom Doors
Comment.
One commenter stated that in-swinging bathroom doors generally are problematic,
unless the bathroom is unusually large. The commenter noted that an in-swinging
door makes it extremely difficult to enter and exit. The commenter recommended
that in-swinging doors be prohibited unless there is sufficient internal bathroom
space, exclusive of the swing of the door, which allows either a five foot turning
radius or two mutually exclusive 30" x 48" wheelchair spaces. Another commenter
stated that in-swinging bathroom doors create a serious obstacle for the wheelchair
user.
Response: The Department declines to prohibit in-swinging bathroom
doors. Adjusting an in-swinging door to swing out is the type of later adaptation
that can be made fairly easily by a resident or tenant. Once a minimum door width
is provided, a tenant who finds a bathroom not readily usable can have the door
rehung as an outswinging door. Note, however, that the second set of guidelines
for usable bathrooms specifies clear space for bathrooms with in-swinging doors.
Bathroom
Design Illustrations
Comment.
A number of commenters from the disability community stated that two of the six
bathroom drawings in the preamble to the proposed guidelines (numbers 4 and 6
at 55 FR 24374-24375) did not allow for a parallel approach to the tub. These
commenters requested that these drawings be removed from the final Guidelines.
Other commenters stated that the Department's bathroom design illustrations at
55 FR 24374-24375 are not consistent with the Figure 8 bathroom design illustrations
at 55 FR 24401.
Response: While a parallel approach to the tub would
provide somewhat greater accessibility, the Department believes that to indicate,
through the Guidelines, that a parallel approach to the tub is necessary to meet
the Act's requirements, exceeds the Fair Housing Act's minimal design expectations
for bathrooms. Accordingly, the first set of specifications for usable bathrooms
does not specify a parallel approach to the tub. However, the second set of specifications
provides for a clear access aisle adjacent to the tub that would permit a parallel
approach to the tub. Either method would meet the Act's requirements. With respect
to the comments on the bathroom design illustrations, these illustrations have
been revised to make the clear floor space requirements more readily understood.
The illustrations are adapted from ANSI A117.1.
Number
of Accessible Bathrooms
Comment.
A number of comments were received on how many bathrooms in a dwelling unit should
be subject to the Act's "usable" bathroom requirement. Many commenters recommended
that all full bathrooms be made accessible. Other commenters recommended that
only one full bathroom be required to be made accessible. A few commenters recommended
that half-baths/powder rooms also be subject to the Act's requirement.
Response:
In House Report No. 711, the Congress distinguished between "total accessibility"
and the level of accessibility required by the Fair Housing Act. The report referred
to standards requiring every aspect or portion of buildings to be totally accessible,
and pointed out that this was not the level of accessibility required by the Act.
The final Guidelines for bathrooms are consistent with the Act's usable bathroom
requirement, and provide the level of accessibility intended by Congress. As discussed
previously in this preamble, the final Guidelines for usable bathrooms provide
two sets of specifications. The second set of specifications provides somewhat
greater accessibility than the first set of specifications. In view of this fact,
the final Guidelines provide that in a dwelling unit with a single bathroom, the
bathroom may be designed in accordance with either set of specifications -- the
first set or the second set. However, in a dwelling unit with more than one bathroom,
all bathrooms in the unit must comply with the first set of specifications, or
a minimum of one bathroom must comply with the second set of specifications, and
all other bathrooms must be on an accessible route, and must have a usable entry
door in accordance with the guidelines for Requirements 3 and 4. Additionally,
the final Guidelines provide that a powder room must comply with the Act's usable
bathroom requirements when the powder room is the only restroom facility provided
on the accessible level of a multistory dwelling unit.
Discussion of Comments on Related Fair Housing Issues Compliance Deadline
Section 100.205 of the Fair Housing regulations incorporates the Act's design
and construction requirements, including the requirement that multifamily dwellings
for first occupancy after March 13, 1991 be designed and constructed in accordance
with the Act's accessibility requirements. Section 100.205(a) provides that covered
multifamily dwellings shall be deemed to be designed and constructed for first
occupancy on or before March 13, 1991 (and, therefore, exempt from Act's accessibility
requirements), if they are occupied by that date, or if the last building permit
or renewal thereof for the covered multifamily dwellings is issued by a State,
County, or local government on or before January 13, 1990. Comment.
The Department received a number of comments on the March 13, 1991 compliance
deadline, and on methods of achieving compliance. Many commenters objected to
the March 13, 1991 compliance deadline on the basis that this deadline was unreasonable.
Several commenters from the building industry stated that, in many cases, design
plans for buildings now under construction were submitted over two years ago,
and it would be very expensive to make changes to buildings near completion. Other
commenters stated that it is unreasonable to impose additional requirements on
a substantially completed project that unexpectedly has been delayed for occupancy
beyond the March 13, 1991 effective date.
Response: Section 804(f)(3)(C)
of the Fair Housing Act states that the design and construction standards will
be applied to covered multifamily dwelling units for first occupancy after the
date that is 30 months after the date of enactment of the Fair Housing Amendments
Act. The Fair Housing Act was enacted on September 13, 1988. The date that is
30 months from that date is March 13, 1991. Accordingly, the inclusion of a March
13, 1991 compliance date in §100.205 is a codification of the Act's compliance
deadline. The Department has no authority to change that date. Only Congress may
extend the March 13, 1991 deadline.
The Department, however, has been attentive
to the concerns of the building industry, and has addressed these concerns, to
the extent that it could, in prior published documents. In the preamble to the
final Fair Housing rule, the Department addressed the objections of the building
industry to the Department's reliance on "actual occupancy" as the sole basis
for determining "first occupancy". (See 54 FR 3251; 24 CFR Ch. I, Subch. A, App.
I at 585 (1990).) Commenters to the proposed Fair Housing rule, like the commenters
to the proposed guidelines, argued that coverage of the design and construction
requirements must be determinable at the beginning of planning and development,
and that projects delayed by unplanned and uncontrollable events (labor strikes,
Acts of God, etc.) should not be subject to the Act.
In order to accommodate
the "legitimate concerns on the part of the building industry" the Department
expanded §100.205 of the final rule to provide that covered multifamily dwellings
would be deemed to be for first occupancy if the last building permit or renewal
thereof was issued on or before January 13, 1990. A date of fourteen months before
the March 13, 1991 deadline was selected because the median construction time
for multifamily housing projects of all sizes was determined to be fourteen months,
based on data provided by the Marshall Valuation Service.
More recently, the
Department addressed similar concerns of the building industry in the preamble
to the proposed accessibility guidelines. In the June 15, 1990 publication, the
Department recognized that projects designed in advance of the publication of
the final Guidelines, may not become available for first occupancy until after
March 13, 1991. To provide some guidance, the Department stated in the June 15,
1990 notice that compliance with the Option One guidelines would be considered
as evidence of compliance with the Act, in projects designed before the issuance
of the final Guidelines. The Department restated its position on this issue in
a supplementary notice published in the Federal Register on August 1, 1990 (55
FR 31131). The specific circumstances under which the Department would consider
compliance with the Option One guidelines as compliance with the accessibility
requirements of the Act were more fully addressed in the August 1, 1990 notice.
Comment.
A number of commenters requested extending the date of issuance of the last building
permit from January 13, 1990 to some other date, such as June 15, 1990, the date
of publication of the proposed guidelines; August 1, 1990, the date of publication
of the supplementary notice; or today's date, the date publication of the final
Guidelines.
Response: The date of January 13, 1990 was not randomly
selected by the Department. This date was selected because it was fourteen months
before the compliance deadline of March 13, 1991. As previously noted in this
preamble, fourteen months was found to represent a reasonable median construction
time for multifamily housing projects of all sizes, based on data contained in
the Marshall Valuation Service. Builders have been on notice since January 23,
1989 -- the publication date of the final Fair Housing rule, that undertaking
construction after January 13, 1990 without adequate attention to accessibility
considerations would be at the builder's risk.
Comment.
One commenter requested that the applicable building permit be the "primary" building
permit for a particular building. Other commenters inquired about the status of
building permits that are issued in stages, or about small modifications to building
plans during construction which necessitate a reissued building permit.
Response:
Following publication of the proposed Fair Housing regulation, and the many comments
received at that time from the building industry expressing concern that "actual
occupancy" was the only standard for determining "first occupancy", the Department
gave careful consideration to the steps and stages involved in the building process.
On the basis of this study, the Department determined that an appropriate standard
to determine "first occupancy", other than actual occupancy, would be issuance
of the last building permit on or before January 13, 1990. This additional standard
was added to the final Fair Housing Act regulation. The Department believes that,
aside from actual occupancy, issuance of the last building permit remains the
appropriate standard.
Compliance
Determinations by State and Local Jurisdictions
Comment.
A few commenters questioned the role of States and units of local government in
determining compliance with the Act's accessibility requirements. The commenters
noted that
-
§100.205(g) encourages States and units of general local government to include,
in their existing procedures for the review and approval of newly constructed
covered multifamily dwellings, determinations as to whether the design and construction
of such dwellings are consistent with the Act's accessibility requirements; but
- §100.205(h)
provides that determinations of compliance or noncompliance by a State or a unit
of general local government are not conclusive in enforcement proceedings under
the Fair Housing Act. These commenters stated that, unless determinations of compliance
or noncompliance by a State or unit of general local government are deemed to
be conclusive, local jurisdictions will be discouraged from performing compliance
reviews because they will not be able to provide a building permit applicant with
a sense of finality that proposed design plans are in compliance with the Act.