&EPA
           United States
           Environmental Protection
           Agency
            Office of Water
            4604
EPA 812-B-94-003
April 1994
Sampling for Lead in
Drinking Water in
Nursery Schools and
Day Care Facilities
  Recycled/Recyclable • Printed with Vegetable Oil Ba.sed Inks on 100% Recycled Paper (50% Postconsumer) • Please recycle as newsprint

-------

-------
                                                            Purpose  of  This  Booklet
       This booklet provides simple, step-by-step
 instructions for sampling drinking water for lead and for
 selecting remedies when contamination problems are found.
 The document is intended to assist owners and operators of
 small nursery schools and day care facilities.  Exposure to
 lead is a significant health concern, especially for young
 children and infants whose growing bodies  tend to absorb
 more lead than the average adult.

 Lead generally gets into drinking water through contact with
 plumbing materials containing lead.  The longer water
 remains in contact with leaded-plumbing, the more the
 opportunity exists for lead to leach or dissolve into water.
 Buildings with on again/off again water use patterns,  such
 as day care centers and nursery schools, may be more
 susceptible to elevated lead concentrations.  Water may sit
 in the pipes of these facilities for significant periods, such as
 overnight and during weekends, and  thus enable more lead
 to leach into  the water.

 Even though  water delivered from your community's public
 water supply must meet Federal and State standards for
 lead, you may still end up with too much lead in your
 drinking water because of the plumbing in your facility and
 because of your facility's water use patterns. The only way
 to be certain that lead is  not a problem in your nursery
 school or day care center is to test various drinking water
 outlets (fountains, faucets, and coolers) for the substance.
 If problems are found, they can then  be corrected.

 This booklet provides  advice on how you might proceed to
test for lead and implement remedies if problems are found.
If you rent your facility,  inform the building owner of your
plans to conduct testing and solicit his cooperation in
correcting any lead problems identified.
        If you own or direct a large nursery school
or day care facility, or if you plan to test all of your
drinking water outlets yourself, you should obtain a
copy of Lead in Drinking Water in Schools and Non-
Residential Buildings.  This U.S.  Environmental
Protection Agency (EPA) publication contains:

•       Information on the causes and effects of lead
        in drinking water.

•       Step-by-step instructions for sampling water
        for lead.

*      Advice on  short- and long-term solutions to
       lead problems.

-------
   Background  Information
  Health Effects of Lead:
  Why You Should Be Concerned

        Lead is a toxic metal that can be harmful to human
  health when ingested or inhaled.  Unlike most other
  contaminants, lead is stored in our bones and is later
  released into our bloodstreams.  As a result, even small
  doses can accumulate and become significant.  The groups
  most vulnerable to lead include fetuses and young children.

  Pregnant Women and Fetuses: Accumulated lead stored in
  mothers may damage a child before it is born, causing a
  lower birth weight and slowing down normal physical and
  mental development. Recently published studies suggest
  that even low levels in a mother may later affect an infant's
  mental performance.

  Young Children: Young children, especially those under
  the age of six, process lead differently than adults.  Their
  growing bodies tend to absorb and withhold more lead,
  putting them at higher risk of lead contamination.  Even at
  low levels of lead exposure, children may experience lower
 IQ levels,  impaired hearing, reduced attention span, and
 poor classroom performance.  At high levels, lead can
 seriously damage the brain.

 Middle-aged Men and Women: Some recent studies have
 found an association between blood-lead levels and slight
 increases in blood pressure among adults. The relationship is
 more marked in middle-aged men but is also significant for
 middle-aged women.  It remains to be determined whether
 lead-related increases in blood pressure are significantly
 connected to more serious cardiovascular diseases.

 The degree of harm from  lead exposure depends on a
 number of factors including the frequency, duration, and
 dose of the exposure and individual susceptibility factors,
 such as age, previous exposure history, and nutrition and'
 health.  In addition, the degree of harm depends on one's
 total exposure to lead from all sources in the
 environment-air, soil, dust, food, and water. Lead in
drinking water can be a significant contributor to  overall
exposure to lead, particularly for infants whose diet consists
of liquids made with water, such as baby food formula
 How Lead Gets into Drinking Water

       Drinking water before treatment, whether it comes
 from underground or from a surface source such as a lake
 or reservoir, contains little if any lead. Lead usually gets
 into drinking water after it leaves the local treatment plant
 or private well and comes into contact  with plumbing
 materials in individual homes and businesses that contain
 lead.  The physical/chemical interaction that occurs between
 the water and plumbing  is known as "corrosion."

 Some interior pipes, soldered piping joints, faucets, valves,
 and fittings are the primary contributors of lead to drinking
 water.  Sediment trapped in some pipes and fixtures may
 also contribute lead to drinking water.  Water coolers
 manufactured before 1988 may contain  lead parts or lead-
 lined water storage tanks and contribute excessive levels of
 lead to drinking water.  Pictures of some common drinking
 water outlets are shown in Exhibit 1.

 The critical issue is that even though your public water supplier
 may send you water that meets all Federal and State public
 health standards for lead, you may still end up with too much
 lead in your drinking water because of the plumbing in your
 nursery school or day care center. That is why testing your
drinking water outlets for lead is so important.

-------
                                                         Background Information
      Connecting
      Plp«
          Water Cooler
     Connecting np«
SoM*rJota1
      Bubbler
   Sources of Lead in
     Drinking Water

Common sources of lead in
drinking water include;

  • solder

  • fluxes

  • pipes and pipe fittings

  • fixtures (e.g., brass faucets
    containing alloys of lead)

  • sediments
           Faucet (Tap)

                  Exhibit 1.  Common Drinking Water Outlets

-------
  Background  Information
  Factors Contributing to Corrosion

        What causes lead to possibly leach from your
  plumbing into your drinking water? Actually, no single
  situation or activity causes this interaction.  Rather, it is a
  combination of several factors.  The corrosion of lead tends
  to occur more frequently in "soft" water (lathers soap
  easily) and acidic (low pH) water.  Other factors,  however,
  also contribute to the corrosion potential of water and
  include water velocity and temperature, alkalinity, chlorine
  levels, the age and condition of plumbing, and the amount
  of time water is in contact with plumbing. The occurrence
  and rate of corrosion  depends on the complex interaction
  between a number of these and other chemical, physical,
  and biological factors.

 Public water system officials routinely  undertake activities
 aimed at controlling the corrosion characteristics of their
 water supplies.  Their treatment activities  can lead to a
 protective coating of minerals being formed on the inside
 layer of pipes, thereby insulating  the drinking water, in
 effect, from  lead. Given that the health effects of lead
 occur at very low levels, these activities are critical.  The
 activities undertaken by individual homeowners and building
 owners/operators to identify and remove problem plumbing
 are also critical.
How Lead in Drinking Water is Regulated

      Lead is regulated in drinking water under a Federal
body of law known as the Safe Drinking Water Act (SDWA).
This Act was initially passed in 1974 and, in part, requires
EPA to establish regulations for known or potential
contaminants in drinking water for the purpose of protecting
public health. Major amendments were passed to the SDWA
in 1986.  These amendments included, in part, some specific
provisions for controlling lead in drinking water:

•     A  new regulation to
      minimize lead and the
      corrosivity of water
      supplied by public
      water systems (known
      as  the Lead and
      Copper Rule; took
      effect May 1991).
        Your day care center or nursery school is roost
  likely to have a lead problem if:

  •     The facility has lead pipes in the plumbing (the
        pipes will be dull gray in color and will appear
        shiny when scratched with a knife or key; lead
        pipes have not been widely used since the 1930s
        and their  use has been banned since 1986).

  V   The facility has copper pipes joined by lead
        solder (the solder joint will be dull gray in color
        and appear shiny when scratched with a knife or
        key; the newer the solder, the greater the
        likelihood of lead contamination; the use of lead
        solders and flux  has been banned since 1986).

  •      The facility has brass pipes, faucets, fittings
        and valves  (these materials contain alloys of
        lead and may contribute excessive levels of lead
        to drinking water even though they meet the
        lead-free requirements of the Safe Drinking
       Water Act—less than 8 percent lead; these
       plumbing  materials are likely to contribute
       more lead if they are less than 1  year old).

 •     The water supplied to the facility is corrosive
       (contact your public water supplier to determine
       the corrosiveness of the water and what steps it
       is taking to minimize these characteristics).

 •     Sediment  in the screens on faucets contain
       lead.

 •     The service connector to the building
       housing your facility is made of lead (the pipe
       that carries water from the public  water system
       main to the building).

 •     Water coolers in the facility are known to
       contain lead parts or have lead-lined water
       tanks (see EPA's listing of-water coolers  in
      Appendix B).

Note:  If you rent your  facility, ask your landlord to
help identify potential sources of lead in drinking
water in the building.

-------
                                                                                           Background Information
•     A requirement that only lead-free materials be used in
      new plumbing and in plumbing repairs; solders and
      flux are to contain less than 0.2 percent lead and
      pipes and fittings are to contain less than 8 percent
      lead (referred to as the Lead Ban; effective 1986).

In 1988, Congress passed the Lead Contamination Control
Act (LCCA), which further amended the SDWA.  This law
was passed to reduce the dangers of lead exposure to
children by drinking water at schools  and  day care centers.
In part, the LCCA required:
      States to establish a
      program to assist
      schools and day care
      centers in testing for
      and remedying lead
      contamination
      problems.
EPA to publish guidance to assist schools and day care
centers in testing for and remedying lead in drinking
water problems (this booklet and EPA's publication
"Lead in Drinking Water in Schools and Non-Residential
Buildings" represents this guidance).

EPA to publish a list of water coolers that are not lead-
free, including a separate list of coolers that have lead-
lined tanks (see Appendix Bfor a listing); the Consumer
Product Safety Commission (CPSC) was to subsequently
issue an order requiring manufacturers and importers of
water coolers with lead-lined tanks to repair, replace or
recall, and provide a refund for such coolers; civil and
criminal penalties were also established  to prohibit the
further manufacture and sale in interstate commerce of
coolers that are not lead-free.

Schools and day care centers  that conduct lead testing
to inform the school  community  about the testing
effort and make the test results available  for
inspection; guidance  on this topic is provided later in
this booklet  under the section entitled
Outreach—Notify Parents  and Staff.
                                                      Th« SDWA
                                                  ArMndnwntsof
                                                         1986
                                                  • Require lead to be
                                                    further mttrteed
                                                  (Lead & Copper Rule)
                                                    Require materials
                                                    med In the repair
                                                    orconsltucttonof
                                                     pkjrnbkxjtobe
                                                       lead-Tree
                                                       (Lead Ban)
         Some States and local jurisdictions have lead testing programs that are more comprehensive than the LCCA.
   Consult your State/local  education or drinking water program to learn about any such program.  At a minimum,  these
   organizations should be able to provide you with technical assistance as you undertake sampling.

-------
         You cannot see, taste or smell dissolved lead in
  water.  Testing is the only way to determine whether lead is
  a problem in your nursery school or day care center.   This
  section outlines how you can go about sampling and
  interpreting  test results.  If you rent your facility,  notify the
  building owner of your testing plans and provide him with a
  copy of your test results.  You  should encourage your
  landlord to participate in the testing process and to take
  corrective actions if lead  problems are found.

  Who Will Collect and
  Analyze Samples?

        In general, most
  nursery schools and day
  care centers will need to
  contract with  a certified
  drinking water laboratory
  to collect and analyze
  samples.  Contact your
  State drinking water program or EPA's Safe Drinking Water
 Hotline  (see Appendix A) for a list of certified laboratories in
 your area. Once you have  identified possible laboratories,
 consider the following issues prior to making a selection:'

 •    Will the laboratory take samples for you or will they
      provide training and sample containers for collectors
      designated by you?

 •    Will the samples be hand-delivered or shipped to the
      laboratory?  Within  what time frames must samples
      reach the laboratory?

 •    What is the cost of the laboratory's services?  Costs
      should range between $10 and $30, depending upon
      the extent of the services to be provided.

•     What-is the laboratory's time frame for providing
      sample results?

      What documentation  will the laboratory provide to
      note sample results?  If lead contamination problems
      are found, sample records and test results will  assist
      you in pinpointing  the sources of problems.

      Is  the laboratory willing to establish a written agreement
     or contract with you for the services to be provided?
 Where to Sample

       Test all drinking water
 outlets in your nursery school
 or day care center for lead
 where water is normally
 drawn for drinking or food
preparation for children. This is likely to include such
outlets as faucets in kitchens, classrooms, and bathrooms-
bubblers; water coolers; and bottled water dispensers
                                            am.
 When to Sample

       Collect samples in the
 morning before the facility opens
 and before any water is used (this
 includes toilet flushing).  Collect
 water in your sample containers
 immediately after opening the
 faucet or turning on your drinking
 water outlet.  Do not let any water
 run into the basin before collecting
 your  sample.  These samples are
 called morning, first-draw
 samples.  For best results, the
 outlets you are testing should not
 have been used for 8 to 18 hours
prior  to collection of samples.
 Helpful Hints

 *     Do not take samples after a vacation or weekend
       (if the facility is unused during these periods) as
       the water collected would not be representative of
       water the children normally drink.

 •     Do not close the control valve to a water
       cooler or sink to prevent its use before
       sampling.  Small scrapings from the valves
       may get into the sample and produce inaccurate
       results. If necessary, place a sign or box over
       the unit to prevent its use for 8 to 18 hours
       before collecting the sample.

-------
                                                                                   Testing Your Water for Lead
How to Handle Sample Containers
      If you take the samples
yourself, the laboratory will
provide you with sampling
containers and instructions.
Carefully follow the instructions
for handling the containers.  Do
not rinse the containers because
the laboratory  may have added a
small amount of a chemical to
preserve the sample until it
reaches the laboratory.  Avoid
contact with this chemical.  Fill
the container only to the level
indicated (250 milliliters).
Label each container with your name and the specific location
where the sample was collected. You may also wish to
number your samples.  In your own files, keep a separate
record for each sample with the location, sample number, date
and time  the sample was collected, and any other pertinent
information (e.g., manufacturer and model number).
Either mail or deliver your
samples to the laboratory,
depending upon the
arrangements you worked out
in advance.  The "holding"
time on samples is usually
short, so samples should
generally be shipped  the
same day they are collected.
Some laboratories do not
want samples shipped near
the  end of a week because
they are not open on
weekends to receive them.
Interpreting Test Results

      Levels of lead in drinking
water are measured in  parts per
billion (ppb) or parts per million
(ppm).  Parts per billion are also
expressed as micrograms per liter
(/xg/L), and parts per million are also
expressed as milligrams per liter
(mg/L). One ppb is equivalent to  1
/ig/L, and 1 ppm equals 1 mg/L.

In light of recent health studies,
which reveal that even very low
levels of lead in drinking water can
be harmful, especially  to children,
EPA recommends that  you take
action if samples from any of your drinking water outlets
show lead levels  over 20 ppb.  Any drinking water outlet
with test results at or above this level should not be used for
water consumption until the source of contamination is
found and corrective actions are taken to reduce the lead
level below 20 ppb. Consider providing water from a
known lead-free source until the situation is remedied.
>20 ppb

-------
   Testing Your Water for Lead
   Foflow-Up Samples

        Follow-up samples
   should be taken from all
   outlets with lead levels
   over 20 ppb.  A
   comparison of morning,
   first-draw sample results
   and follow-up sample
   results from the same
  outlet will  help you
  determine whether lead is
  coming from the outlet
  itself or from the building's interior plumbing.  The second
  sample (or  follow-up sample) is called a flushed sample
  and is more representative of water being consumed in your
  nursery school or day care center during the day.  This
  sample generally shows a lower lead level.

  Collect a flushed sample in the morning before the facility
  opens and before any water is used. At each outlet being
  tested, allow the water to run for 30 seconds and then
  collect a 250 milliliter sample.

  If the test results from the follow-up samples show lead
  levels above 20 ppb, lead is being contributed  from the
  building's interior plumbing.  You will need to take
 additional samples to pinpoint the specific sources of lead.
 If you plan to conduct such sampling yourself, consult
 EPA's publication Lead in Drinking Water in Schools and
 Non-Residential Buildings for guidance (obtain through your
 State drinking water program-see Appendix A for contact
 information).  If you rent your facility, ask your landlord to
 conduct follow-up testing and to implement any necessary
 corrective measures.
       If test results from any water cooler show lead
 levels above 20 ppb, you may need to take additional
 samples to determine the origin of the lead
 contamination.  There is the possibility that lead is being
 contributed by the building's plumbing and not the
 cooler.  The procedures for conducting follow-up tests
 on water coolers is specified in EPA's publication Lead
 in Drinking Water in Schools and Non-Residential
 Buildings (obtain through your State drinking water
program—see Appendix A for contact information).

If you have not already done so, check to see if the
make and model number of your cooler is listed by
EPA as containing lead parts or a lead-lined tank (see
Appendix B).  If you have a water cooler that has a
lead-lined tank, contact the manufacturer to determine
their requirements for repairing, replacing, or
providing a refund,  or contact the CPSC for follow-up
steps (see Appendix A).
8

-------
                   Correcting  Lead  Contamination   Problems
Routine Control Measures

      To minimize children's exposure to lead, there are
several activities you can conduct on a routine basis. These
activities include:

(1)    Flush all drinking water outlets.  Until you receive
      your test results and implement corrective measures
      for any lead contamination problems, flush all
      drinking water outlets every morning before the
      children arrive. Refrain from consuming water that
      has been in contact with plumbing  for more than
      6 hours, such as overnight or during the weekend.
      Flushing drinking water outlets is important because
      the longer water is exposed to lead pipes or solder,
      the greater the likelihood of lead contamination.
      Before using water for drinking or cooking, flush the
      cold water faucet by allowing  the water to run until
      you feel the water become as cold as it will  get.  You
      must do this for each drinking water faucet.

      Even if all of your morning, first-draw samples show
      low lead levels, there is still a possibility that lead
      may get into any water that sits in  your plumbing for
      long periods (such as during vacations or over long
      weekends).  To be safe, on the first day back, flush
      all drinking  water outlets prior to opening the facility.
Possible Remedies

      In order to determine which remedies will work in
your nursery school or day care center, it is important to
pinpoint the sources of lead in your facility.  This is
accomplished through conducting follow-up testing and then
comparing these results with those of your morning, first-
draw samples.  (See EPA's publication "Lead in Drinking
Water in Schools and Non-Residential Buildings" for further
information on this topic—order document through your
State drinking water program listed in Appendix A).

Before implementing any remedy, all options available should
be considered (see Exhibit 2 for a list of possible remedies).
Decisions should be based on such factors as ease of
implementation, operation and maintenance, and costs.
Following implementation of any remedy, additional follow-up
testing should be conducted to ensure that the remedy
employed is actually successful at reducing lead exposure.
Contact your State drinking water program for advice in this
area (see Appendix A for contact information), or consider
hiring a licensed plumber or water supply professional.  If you
rent your facility, ask the building owner to take follow-up
samples and institute corrective measures.
(2)    Use only cold water to prepare food and drinks.
      Hot water dissolves lead more quickly than cold
      water and is therefore more likely to contain greater
      amounts of lead.  If hot water is needed, water
      should be drawn from the cold water tap and heated.
      Use only thoroughly flushed water from the cold
      water tap for drinking and when making formula,
      juices, or foods.
(3)    Clean all screens of debris on a regular basis.
      Small screens on the end of a faucet can trap
      sediments containing lead.  These sediments can
      cause high lead levels in drinking water.

-------
  Correcting  Lead Contamination Problems

           Possible Remedies for Addressing Both Widespread and Localized Lead Contamination Problems:

           If you have a private well, treat the water for corrosion before it enters the building with calcite filters soda
           ash, or a phosphate solution tank and feeder units.  These devices are commercially available.

           Flush all outlets prior to use (see instructions above for flushing under "Routine Control Measures").

           Remove sources of lead in the plumbing system.  These remedies are probably more appropriate for localized
           contamination problems and are best handled by a licensed plumber:

                Replace solder joints  with  lead-free joints.

                Replace the outlet or fixture/faucet with lead-
                free materials.

                Replace piping with lead-free materials.

          Note:  New brass faucets, fittings, and valves may contribute lead to drinking water even though they meet the
          lead-free requirements of the Safe Drinking Water Act (i.e., they contain less than 8 percent lead)  Before
          purchasing any such materials, request the results of lead testing information from the manufacturer or distributor.

          By-pass the sources of lead contamination.  This
          remedy is also probably most appropriate for
          addressing a localized contamination problem and
          could best be implemented by  a licensed plumber.

          Provide an alternative  and lead-free source of
          drinking water,  such as bottled water.  Make sure
          that you require a written statement from the bottled
          water distributor guaranteeing  that the water quality
          meets Federal and State  bottled water standards.

          Install point-of-use treatment devices (often referred to as home treatment devices).   These devices are installed
          on a faucet or other outlet and are intended to remove specific contaminants.   If you are interested in a home
          treatment device,  investigate  carefully.  Some treatment devices that claim to remove many contaminants often do
          not remove lead.  Unfortunately, some devices, if not maintained properly, may actually increase lead levels
          Before investing in any such device, you may want to contact NSF International,  an independent organization that
         evaluates the effectiveness of home treatment units (see Appendix Afar contact information)
                                           Exhibit 2.   Possible Remedies
10

-------
                           Outreach—Notify  Parents  and  Staff
     The LCCA of 1988 requires you to notify parents,
staff, and other employee organizations that test results are
available.  You might use fliers, letters mailed to the home,
or a parent meeting to disseminate this information. It is a
good idea to include information on the details of your
sampling program, what you are doing and why, so that
those concerned will know how you have identified and
corrected any lead problems.

It is recommended that you communicate with parents and
employees right from the beginning of the testing process.
You can, of course, notify them of your efforts at any time.
Some helpful hints for effective communication include:

•    Take the initiative.

•    Anticipate questions.

•    Be a good source of information.

•    Keep people up to date on your progress.
PUBLIC NOTICE
                                                                                                  11

-------
  Appendix  A-Listing  of EPA  Regional,  State
  Drinking  Water, and  Other Contacts
  Regional Contacts
  Region I

  Ms. Ellie Kwong
  Groundwater Management and Water Supply Branch
  U.S. Environmental Protection Agency Region I
  JFK Federal Building
  Boston, MA  02203
  (617) 565-3620

  Region II

  Mr. Taj Khan
  Drinking Water/Ground Water Protection Branch
  U.S. Environmental Protection Agency Region II
  26 Federal Plaza, Room 853
  New York, NY  10278
 (212) 264-1358

 Region III

 Mr. George Rizzo
 Drinking Water/Ground Water Protection Branch
 U.S. Environmental Protection Agency Region in
 841 Chestnut Street
 Philadelphia, PA  19107
 (215) 597-0609

 Region IV

 Mr. Tom DeGaetano
 Municipal Facilities Branch
 U.S. Environmental Protection Agency Region IV
 345 Courtland Street, NE
 Atlanta, GA 30365
 (404) 347-.2913

 Region V

 Mr. John Delessandro
 Technical Support Unit
 U.S. Environmental Protection Agency Region V
 77 West Jackson
 Chicago, IL 60604
 (312) 353-4914
  Region VI

  Mr. Len Pardee
  Water Supply Branch
  U.S. Environmental Protection Agency Region VI
  First Interstate Bank Tower at Fountain Place
  1445 Ross Avenue, 12th Floor, Suite 1200
  Dallas, TX  75202
  (214) 655-8086

  Region VII

 Ms. Elizabeth Murtagh-Yaw
 Drinking Water Branch
 U.S. Environmental Protection  Agency Region VII
 726 Minnesota Avenue
 Kansas City, KS 66101
 (913) 551-7440

 Region VIII

 Ms. Marty Swickard,
 PWSP Section - 8WM-DW
 Drinking Water Branch
 U.S. Environmental Protection Agency Region VIE
 999 18th Street, Suite 500
 Denver, CO  80202
 (303) 293-1629

 Region IX

 Ms. Cheryl Gustafson
 Public Water Supply Section
 U.S. Environmental Protection Agency Region IX
 75 Hawthorne Street
 San Francisco, CA 94105
 (415) 744-1828

 Region X

 Ms. Wendy Marshall
 Lead Contact  WD-132
 Ground Water and Drinking Water Branch
 U.S. Environmental Protection Agency Region X
 1200 Sixth Avenue
Seattle, WA 98101
(206) 553-1890
A-l

-------
                   Appendix A-Listing of EPA Regional State Drinking Water, and Other Contacts
 State  LCCA  Contacts

 EPA REGION I

 Connecticut

 Mr. Bob Rivard, Supervising Sanitary Engineer
 Water Supply Section
 Connecticut Department of Health Services
 150 Washington Street
 Hartford, CT06106
 (203) 566-1253

 Maine

 Mr. Peter Moulton, Drinking Water Manager
 Drinking Water Program
 Maine Division of Health
 State Station 10
 Augusta, ME 04333
 (207) 287-2070

 Massachusetts

 Mr. Chuck Larson, Environmental Engineer
 Division of Water Supply
 Massachusetts Department of Environmental Protection
 One Winter Street
 Boston, MA  02108
 (617) 292-5857

 New Hampshire

 Mr. Richard Thayer, Sanitary Engineer
 New Hampshire Department of Environmental Services
 P.O. Box 95
 6 Haven Drive
 Concord, NH 03301
 (603) 271-3139

 Rhode Island

Ms. Donna Pytell,  Sanitary Engineer
Division of Drinking Water Quality
Rhode Island Department of Health
3 Capitol Hill
Providence,  RI 02908
(401) 277-6867
 Vermont

 Ms. Jean Nicolai/Benson Sargent
 Drinking Water Program
 Water Supply Division
 Vermont Department of Health
 Old Pantry Building
 103 South Main Street
 Waterbury, VT 05671-0403
 (802) 241-3400

 EPA REGION II

 New Jersey

 Mr. Sonny Saroya
 Bureau of Safe Drinking Water
 Division of Water Resources
 New Jersey Department of Environmental Protection
 P.O. Box CN-029
 Trenton, NJ  08625
 (609) 292-5550

 New York

 Mr. David Mead
 New York Department of Health
 2 University Plaza/Western Avenue
 Room 406
 Albany, NY 12203-3399
 (518) 458-6706

 Puerto Rico

 Mrs. Olga I. Rivera, Acting Director
 Puerto Rico Department of Health
 Edificio A. Centra Medico
 Call Box 70184
 San Juan, PR  00936
 (809) 763-4307

Virgin Islands (St. Thomas)

Mr. Ira Hobson, Supervisor, PWSS Program
Government of the Virgin IslandsDepartment of Planning and
Natural Resources
Nisky Center,  Suite 231, Nisky 45A
St. Thomas, VI 00802
(809) 774-3320
                                                                                                        A-2

-------
  Appendix A-Listing  of EPA Regional. State Drinking Water, and Other Contacts
  EPA REGION III

  Delaware

  Mr. Ed Hallock
  Environmental Health Specialist IE
  Public Water System Supervision Program
  Division of Public Health
  Delaware Department of Health and Social Services
  P.O. Box 637
  Dover, DE 19901
  (302) 739-5410
  [Both Lead and Drinking Water Contact]

  District of Columbia

  Preventive Health Services
  Commission of Public Health
  Government of the District of Columbia
  1660 L. Street, NW, Suite 815
  Washington, DC  20036
  (202) 673-6741
  [Childhood Lead Poisoning Prevention Contact]

 Maryland

 Ms. Susan Guyaux
 Center for Special Toxics
 Lead Poisoning Prevention Program
 Maryland Department of the Environment
 2500 Broening Highway
 Baltimore, MD 21224
 (410) 631-3859
 [Lead Contact]

 Pennsylvania

 Mr. Frederick A. Marrocco, Chief
 Division of Water Supplies
 Pennsylvania  Department of Environmental Resources
 P.O.  Box  2357
 Harrisburg, PA 17120
 (717) 787-9037
 [Both Lead and Drinking  Water Contact]
  Virginia

  Mr. Robert B. Stroube, M.D., M.P.H.
  State Health Commissioner
  Virginia Department of Health
  109 Governor Street
  Richmond, VA  23219
  (804) 786-3561
  [Lead Contact]

  West Virginia

  Mr. Donald A. Kuntz,  P.E. Director
  Environmental Engineering Division
  Office of Environmental Health Services
 West Virginia Department of Health and Human Resources
 815 Quarrier Street, Suite 418
 Charleston, WV 25301
 (304) 558-2981
 [Both Lead and Drinking Water Contact]

 EPA REGION IV

 Alabama

 Mr. Joe Alan Power, Director
 Public Water Supply Branch
 Alabama Department of Environmental Management
 1751 Congressman W.L. Dickinson Drive
 Montgomery, AL 36109-2698
 (205) 271-7773

 Florida

 Mr. Van Hoofnagle, Administrator
 Drinking Water Section
 Florida Department of Environmental Regulation
 Twin Towers Office Building
 2600 Blair Stone Road
 Tallahassee, FL 32399-2400
 (904) 487-1762

 Georgia

 Mr.  Fred D.  Lehman, Manager
 Drinking  Water Program
 Georgia Department of Natural Resources
Floyd Towers East, Suite 1362
205 Butler Street, SE
Atlanta, GA  30334
(404) 651-2750
A-3

-------
                    Appendix A-Listing  of EPA  Regional, State Drinking Water, and Other Contacts
 Kentucky

 Mr. John T. Smither, Manager
 Drinking Water Branch
 Kentucky Natural Resources and
   Environmental Protection Cabinet
 14 Reilly Road
 Frankfort, KY  40601
 (502) 564-3410

 Mississippi

 Mr. David Mitchell,  Director
 Division of Water Supply
 Mississippi State Department of Health
 P.O. Box 1700
 Jackson, MS 39205
 (601) 960-7518

 North Carolina

 Mr. Wallace Venrick, Chief
 Public Water Supply  Section
 North Carolina Department of Environmental Health
  and Natural Resources
 Division of Environmental Health
 P.O. Box 29536
 Raleigh, NC 27626-0536
 (919) 733-2321

 South Carolina

 Mr. Robert E. Malpass, Chief
 Bureau of Drinking Water Protection
 South Carolina Department of Health
  and Environmental Control
 2600 Bull Street
 Columbia, SC  29201
 (803) 733-5310

Tennessee

Mr. David Draughon,. Director
Division of Water Supply
Tennessee Department of Environment and Conservation
401 Church Street
Sixth Floor, L & C Tower
Nashville, TN 37219-5404
(615) 532-0191
 EPA REGION V

 Illinois

 Mr. Dean Thady
 State Plumbing Consultant
 Office of Health Protection
 Illinois Department of Public Health
 525 West Jefferson Street
 Springfield, IL 62761
 (217) 524-0799
 [For questions on plumbing]

 Mr. G. Michael Brant
 Office of Health Protection
 Division of Environmental Health
 Illinois  Department of Public Health
 525 West Jefferson Street
 Springfield, IL 62761
 (217) 524-5830
 [For questions on fountains in schools]

 Indiana

 Mr. Wayne Brattain
 Drinking Water Branch
 Indiana Department of Environmental Management
 P.O. Box 6015
 Indianapolis, IN  46206-6015
 (317) 233-4179

 Michigan

 Division of Water Supply
 Michigan Department of Public Health
 3423 North Logan/Martin L. King Jr. Boulevard
 P.O. Box 30195
 Lansing, MI 48909
 (517) 335-9215

 Minnesota

 Ms. Lih-In Rezania
 Drinking Water Protection Section
 Division of Environmental Health
 Minnesota Department of Health
925 Delaware Street, SE
P.O. Box 59040
Minneapolis, MN  55459-0040
(612) 627-5488
                                                                                                             A-4

-------
 Appendix A-Listing of EPA Regional, State Drinking Water, and Other Contacts
 Ohio

 Mr. Dan Chatfield
 Ohio Department of Health
 246 North High Street
 P.O. Box 118
 Columbus, OH  43266-0118
 (614) 466-1450

 Wisconsin

 Ms. Cindy Diedrich
 Public Water Supply Section
 Bureau of Water Supply
 Wisconsin Department of Natural Resources
 101 South  Webster Street
 P.O. Box 7921
 Madison, WI 53707
 (608) 267-2451

 EPA REGION VI

 Arkansas

 Engineering Division
 Arkansas Department of Health
 4815 West Markham
 Little Rock, AR 72203-3867
 (501) 661-2623

 Louisiana

 Louisiana Department of Health and Hospitals
 Office of Public Health
 P.O. Box 60630, Room 403
 New Orleans, LA 70160
 (504) 568-5100

 New Mexico

 New Mexico Environmental Department
 1190 St. Francis Drive
 P.O. Box 26110
 Santa Fe, NM  87502
 (505) 827-7536
 Oklahoma

 Oklahoma Department of Environmental Quality
 Water Quality Service-0207
 1000 NE 10th Street
 P.O. Box 53551
 Oklahoma City, OK 73117-1212
 (405)271-5205 x!48

 Texas

 Texas National Resource Conservation Commission
 P.O. Box 13087
 Austin, TX  78711-3087
 (512) 908-6020

 EPA REGION VII

 Iowa

 Ms. Rita Gergely
 Bureau of Health Engineering and Consumer Safety
 Division of Disease Prevention
 Iowa Department of Public Health
 Lucas State Office Building
 321  East 12th Street'
 Des Moines, IA 50319-0075
 (512) 242-6340

 Kansas

 Contact school system for information

 Missouri

 Mr.  Mike Carter
 Bureau of Environmental Epidemiology
 Missouri Department of Health
 P.O. Box 570
Jefferson City, MO 65102
 (314) 751-6102 or  1-800-392-7245

 Nebraska

Mr. Jack Daniel, Director
Division of Drinking Water and Environmental Sanitation
Nebraska Department of Health
301 Centennial Mall South
P.O. Box 95007
Lincoln, NE  68509
(402) 471-2541
A-5

-------
                   Appendix A-Listing of EPA Regional, State Drinking Water, and Other Contacts
 EPA REGION VIII

 Colorado

 Ms. Michelle Bolyard
 Drinking Water Section
 Water Quality Control  Division
 Colorado Department of Health
 4300 Cherry Creek Dr. South
 Denver, CO  80222
 (303) 692-3539

 Montana

 Mr. Terry Campbell
 Drinking Water Section, Water Quality Bureau
 Montana Department of Health and Environmental Sciences
 Cogswell Building
 Helena, MT  59620
 (406) 444-5256

 North Dakota

 Mr. Sherwin Wanner
 North Dakota State Department of Health
  and Consolidated Laboratories
 Municipal Facilities Division
 1200 Missouri Avenue, Box 5520
 Bismarck, ND 58502-5520
 (701) 221-5210

 South Dakota

 Mr. Michael Getty
 South Dakota Department of Environmental
  and Natural  Resources
 Office of Drinking Water
Joe Foss Building
 Pierre, SD  57501-3181
 (605) 773-3754

Utah

Ms. Patti Fauver
Utah Department of Environmental Quality
Division of  Drinking Water
P.O. Box 144830
Salt Lake City, UT  84114-4830
(801) 538-6159
 Wyoming

 Ms. Maureen Doughtie
 United States Environmental Protection Agency Region 8
 PWSIE Section
 999 18th Street, Suite 500
 Denver, CO  80202 '
 (303) 293-1629

 EPA REGION IX

 Arizona

 Mr. Michael Kleminski
 Compliance Officer
 Drinking Water Compliance Unit
 Arizona Office of Water Quality
 3033 North Central Avenue
 Phoenix, AZ  85012
 (602) 207-4641

 California

 Technical Programs Branch
 California Department of Health Services
 Division of Drinking Water
 2151 Berkeley Way, Room 113
 Berkeley, CA 94704
 (510) 540-2154

 Hawaii

 Hawaii Department of Health
 Five Waterfront Plaza, Suite 250
 500 Ala Moana Boulevard
 Honolulu, ffl  96813
 (808) 586-4258

 Nevada

Nevada Department of Human Resources
Bureau of Health Protection Services
505 East King Street
Carson City, NV  89710
(702) 687-4750
                                                                                                           A-6

-------
  Appendix A-Listing of EPA Regional. State Drinking Water, and Other Contacts

  EPA REGION X                                          ^A.      ^
                                                         Other  Contacts
  Alaska
  A1  ,  _         rr,  .                                  Consumer Product Safety Commission (CPSC)
  Alaska Department of Environmental Conservation               Washington, DC 20207
  Drinking Water Program Manager                            (800) 638-8772
  410 Willoughby, Suite 105

  (^46^300 801                                        EPA/S Nati°nal Safe Drinkln9 Water Hotline
  (yU/; ^ 530°                                           (800) 426-4791
  Idaho                                                   Hotline operates Monday through Friday,  9:00 a.m. to
                                                         5:30 p.m. (EST), except Federal holidays
  Mr. Eldon Nelson, Support Services Supervisor
  Idaho Department of Education                               NSF international
  650 West State                                            3475 Plymouth Road
  Boise, ID  83720                                          P-O- Box 1468
  (208) 334-2203                                           Ann Arbor, MI  48106

  Oregon

 Mr. Dave Leland,  Supervisor
 Drinking Water Section
 Oregon Health Division
 P.O. Box 14450
 Portland, OR 97214-0450
 (503) 731-4010

 Washington

 Washington Department of Health
 Division of Drinking Water
 P.O. Box 47822
 Olympia, WA 98504-7822
 (206) 753-9674
A-7

-------
                            Appendix  B—Water  Cooler  Summary
       The Lead Contamination Control Act (LCCA), which
 amended the Safe Drinking Water Act, was signed into law on
 October 31, 1988 (P.L. 100-572).  The potential of water
 coolers to supply lead to drinking water in schools and day care
 centers was a principle focus of this legislation. Specifically, the
 LCCA mandated that the Consumer Product Safety Commission
 (CPSC) order the repair, replacement, or recall and refund of
 drinking water coolers with  lead-lined water tanks.  In addition,
 the LCCA called for a ban on the manufacture or sale in
 interstate commerce of drinking water coolers that are not lead-
 free.  Civil  and criminal penalties were established under the
 law for violations of this ban.  With respect  to a water cooler
 that may come in contact with drinking water,  the LCCA
 defined the term "lead-free"  to mean:

       "not more than 8 percent lead, except  that no drinking
       water cooler which contains any solder, flux, or
       storage tank interior  surface which may come in
       contact with drinking water shall be considered lead
       free if the solder, flux, or storage tank interior surface
       contains more than 0.2 percent lead."

 Another component of the LCCA was the requirement that
 EPA publish and make available to the states a list of
 drinking water coolers, by brand and model, that are not
 lead-free.  In addition, EPA was to publish and make
 available to the states a separate list of the  brand and model
 of water coolers with a lead-lined tank.   EPA is required to
 revise and republish these lists as new information  or
 analyses become available.

 Based on responses to a Congressional survey in the winter
 of 1988, three major manufacturers, the Halsey Taylor
 Company,  EBCO Manufacturing Corporation, and  Sunroc
 Corporation, indicated that  lead solder had been used in at
 least some models of their drinking water coolers.  On April
 10, 1988, EPA proposed in the Federal Register (at 54 FR
 14320) lists of drinking water coolers with lead-lined tanks
 and coolers that  are not lead-free. Public comments were
 received on the notice, and  the list was revised and published
 on January 18,  1990 (Part IE, 55  FR 1772).  See Table B-l
for a list of water coolers with lead components.


 'Based on an analysis of 22 water  coolers  at a U.S. Navy facility and
 subsequent data obtained by EPA, EPA believes the most serious cooler
 contamination problems are associated with water coolers that have lead-
 lined tanks.
 Prior to publication of the January 1990 list,  EPA determined
 that Halsey Taylor was the only manufacturer of water
 coolers with lead-lined tanks.1  Table B-2 presents a listing of
 model numbers of the Halsey Taylor drinking water coolers
 with lead-lined tanks that had been identified  by EPA  as of
 January 18,  1990.

 Since the LCCA required the CPSC to order manufacturers
 of coolers with lead-lined tanks to repair,  replace  or recall
 and provide  a refund of such coolers, the CPSC negotiated
 such an agreement with Halsey Taylor through a consent
 order published on June  1, 1990 (at 55 FR 22387).  The
 consent agreement calls on Halsey Taylor  to provide a
 replacement  or refund program that addresses all the water
 coolers listed in Table B-2 as well as "all tank-type models of
 drinking water coolers manufactured  by Halsey  Taylor,
 whether or not those models  are included on the present or
 on a future EPA list." Under the consent order, Halsey
 Taylor agreed to notify the public of the replacement and
 refund program for all tank type models.

 If you  have one of the Halsey Taylor water coolers noted  in
 Table B-2, contact Halsey Taylor (address and phone noted
 below) to learn more about the requirements surrounding
 their replacement and refund  program.

 Halsey Taylor
2222 Camden Court
Oak Brook, IL  60520
(708) 574-3500
   SPECIAL NOTE:

         Experience indicates that newly installed brass
   plumbing components containing 8 percent or less lead,
   as allowed by the LCCA and the Lead Ban, can
   contribute high lead levels to drinking water for a
   considerable period after installation.  U.S.  water
   cooler manufacturers have notified EPA that since
   September 1993, the components of water coolers that
   come in contact with drinking water have been made
   with non-lead alloy materials.  These materials include
   stainless steel  for fittings and water control devices,
   brass made of 60 percent copper and 40 percent zinc,
   terillium copper, and food grade plastic.
                                                                                                                  B-l

-------
Appendix B-Water Cooler Summary
                                               Table B-1
                               Water Coolers With Other Lead Components
  EBCO Manufacturing
  •    AH pressure bubbler water coolers with
       lead.  The units contain a single, 50-50 tin-
       category are not available.
       CP3
       DP16M
       WTC10
       DP20-50
       CP3-50
       CP10
           DP15W    DPM8
           DP5S      C10E
           DP13M-60  DP14M
           DP7SM    DP10X
           DP13M    DP3RH
           DP20      DP12N
7P
PX-10
CP10-50
DP13A
DP5F
DP7WM
                                                     19?8
                   13P.       DPM8H
                   DP7S     DP13SM
                   CP5       CP5M
                   DP13A-50  EP10F
                   CP3M     EP5F
                   DP14A-50/60
                                                                      1981
                                                                                «e 50-50 tin-lead
DP15M    DP3R
DP7M     DP7MH
DP15MW  DP3R
DP5M     DP10F
13PL      DP8AH
DP8A
DP7WD
DP14S
CP3H
DP13S
 Halsey Taylor
WMA-1
S3/5/10D
           solder was used in these models of water coolers manufactured between 1978 and the last week of 1987:

                                                                            DC/DHC-1
SCWT/SCWT-A
BFC-4F/7F/4FS/7FS
                  SWA-1
                  S300/500/100D
                                                                             HC2F     HC14WT
                                                                             HC14WL  HCBF7D
                                                                             HWC7
                                            Table B-2
                          Halsey Taylor Water Coolers With Lead-Lined'Tanks''

      The following six model numbers have one or more units in the mode! series with lead-lined tanks;

      WM8A     WT8A     GC10ACR GC10A     GC5A      RWM13A

      The following models and serial numbers contain lead-lined tanks:
      WM14A Serial No. 843034
      WT21A Serial No. 64309550
                            WM14A Serial No. 843006
                            WT21A Serial No. 64309542
                                       WT11A Serial No. 222650
                                       LL14A Serial No. 64346908

-------