Total Flooding Carbon Dioxide (CO2) Fire Extinguishing System


Technical Information Bulletin

TIB 01-12-22

This TIB is not a new standard or regulation and it creates no new legal obligations. It is advisory in nature, informational in content, and is intended to assist employers in providing a safe and healthful workplace.

OSHA's Directorate of Technical Support (DTS) issues Technical Information Bulletins (TIBs) to provide information about occupational hazards and /or to provide information about noteworthy, innovative, or specialized procedures, practices and research that relate to occupational safety and health. DTS selects topics for TIBs from recognized scientific, industrial hygiene, labor, industry, engineering, and/or medical sources.

The Occupational Safety and Health Act requires employers to comply with hazard-specific safety and health standards. In addition, employers must provide their employees with a workplace free from recognized hazards likely to cause death or serious physical harm under Section 5(a)(1), the General Duty Clause of the Act. Employers can be cited for violating the General Duty Clause if there is a recognized hazard and they do not take appropriate steps to prevent or abate the hazard. However, the failure to implement TIB recommendations is not, in itself, a violation of the General Duty Clause. Citations can only be based on standards, regulations, and the General Duty Clause.

Further information about this bulletin may be obtained by contacting OSHA's Directorate of Technical Support and Emergency Management (formerly Directorate of Technical Support) at 202-693-2300.

Purpose

This Technical Information Bulletin informs users of total flooding carbon dioxide (CO2) fire-extinguishing systems of a condition that poses a serious hazard to employees.

Background

The New York Regional Office brought to the attention of the Directorate of Technical Support the potential hazards of carbon dioxide intoxication for employees inside a vault protected by a total flooding CO2 fire-extinguishing system. The Manhattan Area Office investigated an accident in which an employee of a securities firm died from CO2 intoxication. The employee was inside the vault with the vault door closed and locked. When the employee pulled a manual fire alarm actuation device that was located inside the vault space, it activated the warning alarm and the total flooding CO2 system.

Description of the Accident

An account administrator at a securities firm was working overtime in a section of a vault. At 7:10 p.m., security personnel closed and locked the vault. The employee was working in a section of the vault accessible only with a swipe card. The security guard did not have a swipe card and did not access that area of the vault, but instead looked through a small window and apparently did not see the employee. The employee discovered that the vault was locked shortly thereafter. There was a phone in the vault, and the employee apparently tried unsuccessfully to call for help. At about 7:35 p.m., the employee pulled a manual fire alarm system actuation device. In addition to sounding an alarm, the device instantly activated a total flooding CO2 fire-extinguishing system. Activation of the CO2 system created an atmosphere immediately dangerous to life and health inside the locked vault. Using self-contained breathing apparatus (SCBA), firefighters recovered the employee's body. The cause of death, as ruled by the medical examiner, was accidental CO2 intoxication.

Accident Investigation

OSHA's accident investigation revealed violations of OSHA's means of egress and fire protection standards, including 29 CFR 1910.36 (b)(1), 1910.160(b)(5), 1910.160(c)(1), and 1910.160(c)(3). The National Fire Protection Association (NFPA) standard on carbon dioxide extinguishing systems (NFPA- 12, 2000) also addresses these conditions.

The investigation found that the extinguishing system was interlocked with the vault door. The system would only discharge if the door was shut. The manual pull station was located inside the vault. Pulling the device with the door open sounds the alarm; however, no CO2 is discharged until the vault door is closed. There were no warning signs at the entrance to the vault indicating the hazard of the total flooding CO2 system. There also was no label on the pull station to indicate that once activated, there would be a discharge of total flooding CO2 into the vault and to describe the resultant hazard to personnel.

The employer explained that the system's configuration was intended to permit employees to pull the manual actuation device, exit the vault, and close the door behind them. The employer further explained that the pull station was installed inside the space to prevent employees from activating the system while others were in the vault. However, if the manual station is pulled when the door is already shut, as was the case in this accident, there is an immediate discharge of the CO2.

The NFPA-12, 2000 standard requires that the normal manual controls for the CO2 system actuation be located for easy accessibility at all times, including the time of fire. It does not specify whether the location should be inside or outside of the protected space. The 18th edition of the NFPA Fire Protection Handbook requires that the manual controls be located to avoid confusion, and they must be clearly labeled with safe operating procedures. However, it also contains schematics for a total flooding CO2 system that depict the manual actuation device outside of the protected space and next to the entrance.

During the rescue operation, a problem arose when the fire department needed quick access to the vault space. Firefighters were unable to execute a rescue until a securities firm employee was able to open the vault door.

Conclusions

The employer did not meet the requirements of 29 CFR 1910.160 and NFPA-12 standards that require: a warning be posted at the entrance to the vault space, as well as inside the vault, regarding the function of the total flooding CO2 system and its hazards to personnel; warning signs be posted at the manual actuation station to warn employees about the hazards associated with the total flooding CO2 system; employees who work inside vault spaces be trained with respect to the potential hazard in the protected spaces and the proper safety precautions to be observed before manually actuating the system. Further, the employer did not provide an emergency action plan in accordance with 29 CFR 1910.38, and did not provide a pre-discharge employee alarm in accordance with 29 CFR 1910.160 that complies with 29 CFR 1910.165. Finally, NFPA-12, 2000 requires, in part, that means be provided for the "prompt rescue of any trapped personnel." The employer failed to meet this requirement.

Recommendations

  • Fixed CO2 extinguishing systems should be installed and maintained in accordance with NFPA-12, 2000 standards.
  • Equip the pull station device, installed inside a vault, with a control circuit to ensure that actuating the pull station will initiate activation of the CO2 fire-extinguishing system only if the vault door is open at the time of actuation and that no discharge of CO2 will occur until the vault door is subsequently closed. In addition, the control circuit should disable the manual pull station from activating the extinguishing system if the vault door is already closed.
  • Ensure that employees have safe and readily available means of evacuation. In unique situations, such as those associated with vaults, alternative protective means such as an emergency intercom system, sign-in log, video or manual-surveillance, and a procedure to ensure that all other employees have cleared all vault spaces before actuating the alarm and fire-extinguishing system and before closing the vault doors, should be communicated, implemented, and followed.
  • Post emergency numbers near vault and enclosed space telephones.
  • Install signs at the entrance to and inside the protected space indicating the presence of extinguishing systems which can present CO2 intoxication and suffocation hazards to employees.
  • Properly mark/label pull stations and other actuation devices to indicate their function and the potential hazard to personnel.
  • Insure that total flooding systems have a pre-discharge alarm which provides employees with sufficient time to safely exit the space.
  • Train all employees with respect to: the type of systems installed in the workplace, the hazards involved, proper activation in case of emergency, and the correct response to audible and visual pre-discharge alarms. Provide training for non-English speaking employees in languages understood by the affected employees and other individuals that may be exposed to the hazard.
  • Provide a system or device that can be secured in the closed position to prevent accidental or deliberate discharge when persons not familiar with the system (outside vendors and contractors) and its operation are present in a protected space.
  • 29 CFR 1910.160(b)(6) requires annual inspection to check that the system is maintained in good operating condition. We also recommend inspection of the system for compliance with NFPA and OSHA requirements.

If the total flooding CO2 extinguishing systems are installed by employers to meet a particular OSHA standard, employers must:

  • comply with provisions of 29 CFR 1910.162, Fixed extinguishing systems, gaseous agent;
  • comply with provisions of 29 CFR 1910.160, Fixed extinguishing systems, general. Among the requirements in this standard is the obligation in Paragraph 29 CFR 1910.160 (b)(17) that requires employers to, "provide and assure the use of PPE needed for immediate rescue." Employers will need to designate and train individuals how to properly wear an SCBA and perform rescue.

Additional Information

  • NFPA-12, Section 1-6, Personnel Safety, contains requirements to protect personnel.
  • NFPA-12, Appendix A-1-6, "The steps and safeguards necessary to prevent injury or death to personnel in areas whose atmospheres will be made hazardous by the discharge of carbon dioxide ...." is not a part of the requirements of NFPA-12. It is presented for informational purposes only. However, the appendix includes provisions which can be used to safeguard personnel and prevent injury or death.
  • U.S. Environmental Protection Agency report, "Carbon Dioxide as a Fire Suppressant: Examining the Risks," contains valuable information for raising awareness and promoting the responsible use of CO2 fire suppression systems. See United States Environmental Protection Agency.

*Accessibility Assistance: Contact OSHA's Directorate of Technical Support and Emergency Management at (202) 693-2300 for assistance accessing PDF materials.

All other documents, that are not PDF materials or formatted for the web, are available as Microsoft Office® formats and videos and are noted accordingly. If additional assistance is needed with reading, reviewing or accessing these documents or any figures and illustrations, please also contact OSHA's Directorate of Technical Support and Emergency Management at (202) 693-2300.

**eBooks - EPUB is the most common format for e-Books. If you use a Sony Reader, a Nook, or an iPad you can download the EPUB file format. If you use a Kindle, you can download the MOBI file format.

Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close