5.3102.32 Install Thermostatic Radiator Valves

Topic: 
Hydronic Heating (Hot Water and Steam)
Subtopic: 
Equipment Installation
Desired Outcome: 
Established control of radiator heat output
TitleSpecification(s)Objective(s)
5.3102.32a
Install thermostatic radiator valves (TRVs)

Potential asbestos-containing material will be handled in accordance with SWS 2.0110.2 Potential Asbestos-Containing Materials

Ensure a safe work environment

5.3102.32b
Assessment

Available plans will be reviewed to assess system design and intent

If specified on hot water system, the contractor will check existing distribution piping layout to ensure that installation of these valves will not result in undesired outcomes, such as unintended flows through other branches/circuits

If specified for one-pipe steam system, contractor will make sure valves will not be enclosed inside a radiator cover

If specified for one-pipe steam system, contractor will ensure that the correct valve type is recommended

Contractor will assess whether the specified valve is the correct type so that the temperature sensor will not be enclosed or trapped behind furniture

Ensure specified valve meets design intent and desired outcome

5.3102.32c
Isolate TRV location

TRV location will be isolated.

Nearest valves on either side of TRV location will be closed to isolate from the system

Eliminate water/steam supply to valve location

5.3102.32d
Install TRV

TRV will be installed in accordance with manufacturer specifications

In applicable cases, system will be refilled and air will be eliminated

Allow distribution loop to bypass terminal unit/radiator and eliminate over- and under-heated zones

5.3102.32e
Testing and verification

Contractor will operate the system to verify there are no leaks and valve operations

Ensure there are no leaks in the system and that the valve is operating

5.3102.32f
Education

Completed work will be reviewed with the building/property management team and operations staff

Building/property management team and operations staff will be educated on the safe and efficient operation and maintenance requirements of the installed item

Ensure building/property management team and operations staff is informed of the safe, efficient operation and maintenance requirements of the installed item