| 5.3088.3a
Very cold | Individual rooms will remain at a pressure differential of no greater than +/-3 pascals with reference to the indoors Combustion inlets and outlets will be terminated above snow line and protected from snow cover Roof exhaust fans will be installed with roof curbs that meet or exceed the mechanical code requirements Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into heating, ventilation, and air conditioning (
HVAC
HVAC
Heating, ventilation, and air conditioning
) systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5
| Avoid moisture-related damage to the building Ensure occupant safety by properly venting combustion gasses Ensure proper exhaust air flow |
| 5.3088.3b
Cold | Combustion inlets and outlets will be terminated above snow line and protected from snow cover Roof exhaust fans will be installed with roof curbs that meet or exceed the mechanical code requirements Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5. Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into
HVAC
HVAC
Heating, ventilation, and air conditioning
systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5
| Ensure occupant safety by properly venting combustion gasses Ensure proper exhaust air flow |
| 5.3088.3c
Mixed humid | Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into
HVAC
HVAC
Heating, ventilation, and air conditioning
systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5
- Heating and cooling refrigerant lines will be insulated
| Ensure proper equipment operation Prevent energy loss and condensation |
| 5.3088.3d
Hot humid | Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into
HVAC
HVAC
Heating, ventilation, and air conditioning
systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5
- Heating and cooling refrigerant lines will be insulated
| Ensure proper equipment operation Prevent energy loss and condensation |
| 5.3088.3e
Marine | Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into
HVAC
HVAC
Heating, ventilation, and air conditioning
systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Air conditioning/heating coils that are to be installed outside will be selected to withstand corrosion
| Ensure equipment durability Ensure system operates efficiently Avoid damage to the system |
| 5.3088.3f
Hot dry | Proper refrigerant charge will be evaluated and documented according to
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 Examples of acceptable procedures that may be performed include: - Refrigerant will be weighed into
HVAC
HVAC
Heating, ventilation, and air conditioning
systems when outdoor temperatures do not facilitate accurate testing of system charge
- Verification of proper charge will be conducted when outdoor temperatures are suitable
- Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5
- Heating and cooling refrigerant lines will be insulated
| Ensure proper equipment operation Prevent energy loss |