5.3088.3 Regional Climatic Considerations—Mid and High Rise

Topic: 
Forced Air
Subtopic: 
Special Considerations
Desired Outcome: 
Regional climatic variables are taken into consideration
For supporting material, see Referenced Standards.
TitleSpecification(s)Objective(s)
5.3088.3a
Very cold

Individual rooms will remain at a pressure differential of no greater than +/-3 pascals with reference to the indoors

Combustion inlets and outlets will be terminated above snow line and protected from snow cover

Roof exhaust fans will be installed with roof curbs that meet or exceed the mechanical code requirements

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into heating, ventilation, and air conditioning ( HVAC HVAC Heating, ventilation, and air conditioning ) systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Avoid moisture-related damage to the building

Ensure occupant safety by properly venting combustion gasses

Ensure proper exhaust air flow

5.3088.3b
Cold

Combustion inlets and outlets will be terminated above snow line and protected from snow cover

Roof exhaust fans will be installed with roof curbs that meet or exceed the mechanical code requirements

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5.

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into HVAC HVAC Heating, ventilation, and air conditioning systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Ensure occupant safety by properly venting combustion gasses

Ensure proper exhaust air flow

5.3088.3c
Mixed humid

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into HVAC HVAC Heating, ventilation, and air conditioning systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5
  • Heating and cooling refrigerant lines will be insulated

Ensure proper equipment operation

Prevent energy loss and condensation

5.3088.3d
Hot humid

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into HVAC HVAC Heating, ventilation, and air conditioning systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5
  • Heating and cooling refrigerant lines will be insulated

Ensure proper equipment operation

Prevent energy loss and condensation

5.3088.3e
Marine

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into HVAC HVAC Heating, ventilation, and air conditioning systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Air conditioning/heating coils that are to be installed outside will be selected to withstand corrosion

Ensure equipment durability

Ensure system operates efficiently

Avoid damage to the system

5.3088.3f
Hot dry

Proper refrigerant charge will be evaluated and documented according to ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5

Examples of acceptable procedures that may be performed include:

  • Refrigerant will be weighed into HVAC HVAC Heating, ventilation, and air conditioning systems when outdoor temperatures do not facilitate accurate testing of system charge
  • Verification of proper charge will be conducted when outdoor temperatures are suitable
  • Refrigerant charge evaluation must be done using proper evaluation techniques (subcooling/superheat) depending on metering device in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / ACCA ACCA Air Conditioning Contractors of America, www.acca.org Standard 5
  • Heating and cooling refrigerant lines will be insulated

Ensure proper equipment operation

Prevent energy loss