7.8003.3 Emergency Lighting

Topic: 
Plug Load
Subtopic: 
Lighting
Desired Outcome: 
Energy used for lighting reduced
For supporting material, see Referenced Standards.
TitleSpecification(s)Objective(s)
7.8003.3a
Assessment

Lighting strategy will be provided by lighting professional

Work order will be evaluated against site circumstances

Determine and ensure appropriate device and location

7.8003.3b
Selection

Emergency light fixtures will meet the appropriate nationally recognized product standard ( UL UL Underwriters Laboratories 542, UL UL Underwriters Laboratories 1570)

Emergency lighting will include battery backup capable of operating for 90 minutes and will comply with NFPA NFPA National Fire Protection Association, www.nfpa.org 70 section 700.12

Outdoor lamps will be suitable for local climate conditions and in accordance with ANSI ANSI American National Standards Institute, www.ansi.org / UL UL Underwriters Laboratories product standards

Linear fluorescent lamps will not be replaced with T12 lamps, and T8 lamps will be installed as minimum standard

Lamps in luminaires with emergency ballasts shall be replaced with a appropriate type of lamp

Vandal-proof fixtures will be used, if appropriate

Reduce energy use

Ensure device functions properly

Ensure product safety

Ensure occupant satisfaction

Ensure adequate lighting during emergency situations

7.8003.3c
Installation

Fixture will be de-energized before work begins

Worker will follow appropriate lockout procedures in accordance with OSHA OSHA U.S. Occupational Safety and Health Administration, www.osha.gov 1910 Subpart S and ANSI ANSI American National Standards Institute, www.ansi.org / NFPA NFPA National Fire Protection Association, www.nfpa.org 70E

Lamps will be installed in accordance with manufacturer specifications

If fixture is broken, worker will refer to SWS 7.8003.14 Fixture Replacement

Lens and reflector will be cleaned

Ensure worker safety

Ensure occupant safety

Ensure continued savings

Optimize fixture performance

7.8003.3d
Commissioning

Emergency lighting will not inhibit required egress lighting, as required by ANSI ANSI American National Standards Institute, www.ansi.org / NFPA NFPA National Fire Protection Association, www.nfpa.org 101

Battery backup will be tested to meet NEC NEC National Electrical Code 70 Section 700.12(F)

Battery backup emergency lighting will be tested to simulate loss of power

Emergency lighting will be tested in accordance with local ordinances and manufacturer specifications

Exit sign placement will be in accordance with NFPA NFPA National Fire Protection Association, www.nfpa.org 110

Meet target light levels

Ensure occupant satisfaction

Ensure occupant safety

7.8003.3e
Decommissioning

Lamps will be disposed of in accordance with EPA EPA U.S. Environmental Protection Agency, www.epa.gov guidelines, local ordinances, or manufacturer specifications

Protect the environment

Prevent the reuse of inefficient components

7.8003.3f
Safety

Broken lamps containing mercury will be cleaned in accordance with EPA EPA U.S. Environmental Protection Agency, www.epa.gov guidelines

Ensure worker safety

Ensure occupant safety

7.8003.3g
Staff education

Building operations staff will be provided with warranty information, product specification, and installer contact information

Educate building operations staff about operation and maintenance of equipment

7.8003.3h
Occupant education

Education regarding emergency lighting will be provided by building operations staff

Ensure occupant safety