| 5.3301.1a
Assessment | Existing outlet box will be inspected for manufacturer marking, indicating the outlet box is suitable for fan mounting [
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70, Section 314.27(C)] Work order will be evaluated against site circumstances | Ensure occupant safety Determine feasibility |
| 5.3301.1b
Selection | Fan will match existing switching and wiring configuration, unless modifications are made to allow for automatic control of the fan (e.g., occupancy or daylight sensors, etc.) Fan will be ENERGY STARĀ® qualified or better Existing fan will be replaced with a fan of similar functionality and size Fan and installation will carry a minimum 1-year warranty If the lighting is being controlled by a dimmer, ensure replacement lamps are dimming capable; alternatively, the dimmer control can be removed and replaced with an on/off control | Ensure fan usability Reduce energy use Ensure occupant satisfaction |
| 5.3301.1c
Installation | Work will be performed by licensed electrical professional Outlet will be de-energized before work begins Appropriate lockout procedures will be followed in accordance with
OSHA
OSHA
U.S. Occupational Safety and Health Administration, www.osha.gov
1910 Subpart S and
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70E Fan will be installed in accordance with
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70, IFC Section 903,
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
13R, and manufacturer specifications Worker will verify outlet box is secured and supported Screw base lamps will be ENERGY STAR qualified or exceed Energy Independence and Security Act 2014 standard levels by at least 20% All penetrations will be sealed (
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
/
ICC
ICC
International Code Council
Fire Code) Any penetrations created will be patched and painted | Ensure worker safety Ensure occupant safety Ensure continued energy savings Optimize fixture performance Reduce energy use Ensure integrity of fire barrier Ensure integrity of building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
|
| 5.3301.1d
Commissioning | Worker will ensure fan operates in accordance with manufacturer specifications and test fan accordingly | Ensure occupant satisfaction Ensure occupant safety |
| 5.3301.1e
Decommissioning | Lamps will be disposed of in accordance with local ordinances or manufacturer specifications | Protect the environment Prevent the reuse of inefficient components |
| 5.3301.1f
Safety | Broken lamps containing mercury will be cleaned in accordance with
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
guidelines, unless
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
regulations require qualified personnel to clean broken lamp area | Ensure worker safety Ensure occupant safety |
| 5.3301.1g
Staff education | Building operations staff will be provided with warranty information, product specification, and installer contact information | Educate building operations staff about operation and maintenance of equipment Ensure continued savings |
| 5.3301.1h
Occupant education | Occupants will be provided with a manual and educated of new fan benefits Occupant will be provided with lamp disposal procedure determined by building operations staff If lamps containing mercury are used, occupants will be provided with lamp disposal procedure in accordance with
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
guidelines Building operations staff will provide education and shall make available one copy of the owner's/operator's manual to the operator of the equipment | Educate occupants about new fan and benefits Ensure continued savings Protect the environment Ensure occupant safety |