Control panel will be mounted at a safe location to prevent damage to the control panel from water and/or excessive heat Location will be easily accessible and in close proximity of the door At minimum, the following sensors will be installed (all sensor wiring will be in metal conduit; all conduits will be secured to wall or metal strut or other acceptable surfaces): - Outside air temperature sensor
- Stack temperature
- Domestic hot water supply water temperature sensor
- Apartment space temperature (minimum 25% of the residential units)
- Boiler water temperature sensor
- New make-up water meter
- Boiler pressure sensor (steam boiler only)
Outside air temperature sensor will be installed on the building exterior, 10 feet above grade, 4" away from the wall, on the north façade, and in shade; the wall penetration made to run the conduit will be sealed airtight with fire-rated material in accordance with applicable codes; sensor will be wired to the control panel Additional sensors and control points will be installed as required by the manufacturer to optimize system operation Control panel will be mounted on the wall, and all connected sensors will be wired to the control panel in accordance with manufacturer specifications Control panel will be energized, and all sensors will be checked for proper accuracy and communication |