5.3104.13 Leak Detection and Repair—Direct Vent Boiler Exhaust

Topic: 
Hydronic Heating (Hot Water and Steam)
Subtopic: 
Equipment Maintenance, Testing, and Repair
Desired Outcome: 
Direct vent boiler exhaust system does not leak
TitleSpecification(s)Objective(s)
5.3104.13a
Check for presence of asbestos-containing materials (ACMs)

Potential ACMs will be handled in accordance with SWS 2.0110.2 Potential Asbestos-Containing Materials

Ensure a safe work environment

5.3104.13b
Identify leak location

Exhaust leaks will be located through visual inspection of exhaust system (signs of leak may include dripping water, misaligned joints, evidence of air movement, discoloration of adjoining surfaces)

If visual inspection does not reveal exhaust leak, leak will be located through instrumented inspection with use of properly calibrated combustion gas detector or smoke test of exhaust system

Determine leak location

5.3104.13c
Turn off combustion system

Combustion system will be turned off to stop exhaust vent system leak

Eliminate exhaust release

5.3104.13d
Repair leak

Piping, fitting, or device will be repaired or replaced

Ensure exhaust system does not leak

5.3104.13e
Restart combustion system

Combustion system will be restarted and integrity of repair assessed with a properly calibrated combustion gas detector

Confirm system is safe for operation

5.3104.13f
Education

Completed work will be reviewed with the building/property management team and operations staff

Building/property management team and operations staff will be educated on the safe and efficient operation and maintenance requirements of the installed item

Ensure building/property management team and operations staff is informed of the safe, efficient operation and maintenance requirements of the installed item