| 5.3102.5a
Determine location of outdoor sensor | Optimal outdoor sensor location will be determined by visual inspection of building exterior (e.g., north facing, shaded, away from heat sources and exhaust outlets, exposed to typical wind conditions, and in a secure location) | Determine optimal location for outdoor sensor |
| 5.3102.5b
Determine location of distribution piping sensor | Presence of integral outdoor reset control in boiler control panel will be determined. Indoor sensor will be located on distribution supply header | Determine optimal location for indoor sensor |
| 5.3102.5c
Check for presence of asbestos-containing materials (ACMs) | Potential ACMs will be handled in accordance with SWS 2.0110.2 Potential Asbestos-Containing Materials | Ensure a safe work environment |
| 5.3102.5d
Install sensors | Outdoor sensor will be installed in optimal location in accordance with manufacturer specifications As necessary, indoor sensor will be installed on distribution supply header in accordance with manufacturer specifications Presence and function of thermometers on supply and return headers will be verified; thermometers will be installed or replaced as necessary Strap-on indoor sensors will be connected tightly to piping; piping and sensor will be reinsulated with new insulation to
IECC
IECC
International Energy Conservation Code
2012 and
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1-2010, at a minimum Immersion-type sensors will be provided with heat transfer grease between sensor and thermowell in accordance with manufacturer's instructions | Properly install sensors in optimal locations |
| 5.3102.5e
Mount control panel | Control panels that are not part of the boiler will be mounted and wired in accordance with manufacturer specifications and protected from tampering by unauthorized personnel | Ensure proper code-compliant installation of control panel |
| 5.3102.5f
Connect sensors | Sensors will be connected with wiring in accordance with manufacturer specifications and protected from friction and abrasion as they pass through building components | Properly connect sensors |
| 5.3102.5g
Set up control panel | Control optimization will be followed in accordance with SWS 5.3104.4 Optimize Outdoor Reset Boiler Controller (Hot Water) | Optimize control |