FavoritePlease sign in to add this to your favorites. Topic: Hydronic Heating (Hot Water and Steam) Subtopic: Equipment Installation Desired Outcome: Increased efficiency of domestic hot water production Multifamily HomesPrintCopy to ExcelEmail TitleSpecification(s)Objective(s) 5.3102.22a Assessment Assessment will be conducted to determine whether alternative options for providing domestic hot water exist, such as:Separate direct-fired unit (SWS 7.8102.4 Storage Tank-Type Water Heater) Boiler with indirect water heater (SWS 5.3102.10 Installation of Combined Heat and Domestic Hot Water System (Hot Water)) Ensure optimal system is applied 5.3102.22b Replacement Selected heat exchanger will be of a higher efficiency/effectivenessInternal leaks will be checked by a contractor before new unit is put into serviceIsolation valves will be installed for proper servicingGauges and insulation will be installed and functioning Increase efficiency Ensure supply of safe domestic hot water by eliminating cross contaminationEnsure ease of access, operation and maintenance 5.3102.22c Testing Domestic hot water production, distribution system, and delivery temperature will be tested for proper and safe operation Ensure system operates safely and efficiently 5.3102.22d Control recalibration If alternative, stand-alone domestic hot water production system is selected, burner controls will be adjusted to address remaining heating load Ensure heating system is optimized 5.3102.22e Education Property manager will be educated on proper operation and maintenance of heat exchanger Maintain optimal performance Previous Detail Next Detail Back to 5.3102 Equipment Installation Back to Top