5.3003.5 Refrigerant Line Inspection

Topic: 
Forced Air
Subtopic: 
System Assessment and Maintenance
Desired Outcome: 
Refrigerant lines properly installed
Note: 
The authority having jurisdiction may require that a licensed professional perform certain tasks outlined in this detail.
TitleSpecification(s)Objective(s)
5.3003.5a
Insulation

See redline change(s)

All liquid refrigerant lines will be insulated to a minimum of R-4

Vapor or high side lines will not be insulated unless specified by the equipment's manufacturer

Suction lines will be insulated to a minimum of R-4

Ensure refrigerant lines do not gain excessive heat

5.3003.5b
Ultraviolet ( UV UV Ultraviolet ) protection of insulation

If exposed to sunlight, refrigerant line insulation will be protected from UV UV Ultraviolet degradation in accordance with manufacturer specifications, 2012 IRC IRC International Residential Code N1103.3.1, or local code

Install insulation so it does not degrade

5.3003.5c
Sizing

Refrigerant lines will be sized to meet manufacturer specifications for the installed equipment

Ensure system moves appropriate volume of refrigerant

5.3003.5d
Installation quality

Refrigerant lines will be installed without kinks, crimps, or excessive bends

Ensure system moves appropriate volume of refrigerant

5.3003.5e
Support

Refrigerant lines will be routed, supported, and secured to house in a manner that protects the line from damage by workers or occupants

Ensure refrigerant lines do not move, vibrate, or sag

Protect lines from damage

TitleSpecification(s)Objective(s)
5.3003.5a
Insulation

All liquid refrigerant lines will be insulated to a minimum of R-4

Vapor or high side lines will not be insulated unless specified by the equipment's manufacturer

Suction lines will be insulated to a minimum of R-4

For mixed humid, hot humid, and marine climates, heating and cooling refrigerant lines will be insulated

Ensure refrigerant lines do not gain excessive heat

Prevent energy loss and condensation

5.3003.5b
Ultraviolet ( UV UV Ultraviolet ) protection of insulation

If exposed to sunlight, refrigerant line insulation will be protected from UV UV Ultraviolet degradation in accordance with manufacturer specifications, 2012 IRC IRC International Residential Code N1103.3.1, or local code

Install insulation so it does not degrade

5.3003.5c
Sizing

Refrigerant lines will be sized to meet manufacturer specifications for the installed equipment

Ensure system moves appropriate volume of refrigerant

5.3003.5d
Installation quality

Refrigerant lines will be installed without kinks, crimps, or excessive bends

Ensure system moves appropriate volume of refrigerant

5.3003.5e
Support

Refrigerant lines will be routed, supported, and secured to house in a manner that protects the line from damage by workers or occupants

Ensure refrigerant lines do not move, vibrate, or sag

Protect lines from damage