2.0203.4 Combustion Air for Natural Draft Appliances

Topic: 
Combustion Safety
Subtopic: 
Vented Gas Appliances
Desired Outcome: 
Sufficient air provided in the Combustion Appliance Zone ( CAZ CAZ Combustion appliance zone )
TitleSpecification(s)Objective(s)
2.0203.4a
Required combustion air

The required volume of indoor air will be determined in accordance with Section G2407.5.1 or G2407.5.2 and authority having jurisdiction, except where the air infiltration Infiltration The uncontrolled passage of outside air into a building through unintended leaks in the building envelope rate is known to be less than 0.40 air changes per hour (ACH), at which time Section G2407.5.2 will be used

Determine if existing conditions meet the combustion air calculation

2.0203.4b
Additional combustion air (if action is required)

Additional combustion air will be provided in accordance with 2012 IRC IRC International Residential Code G2407 and authority having jurisdiction

Ensure adequate combustion air for operation of the appliance

2.0203.4c
Spillage testing

If a combustion appliance spillage exceeds 2 minutes during pressure testing, specify measures to mitigate

Ensure appliance is not spilling longer than 2 minutes

2.0203.4d
Occupant health and safety

All homes will have a functioning CO CO Carbon monoxide alarm

If CO CO Carbon monoxide levels in interior living spaces exceed outdoor levels, investigate potential sources and take appropriate action to reduce them (e.g., have a qualified professional tune, repair, or replace improperly operating combustion appliances; apply weatherstripping; or conduct air sealing between the garage or crawl space and the home)

Ensure occupant health and safety

Ensure indoor CO CO Carbon monoxide levels do not exceed outdoor CO CO Carbon monoxide levels

2.0203.4e
Occupant education

Occupants will be educated on the operation and maintenance of the CO CO Carbon monoxide alarm

Completed work on combustion appliances and recommended maintenance will be reviewed with occupant

Occupant will be provided information regarding the health effects and risks of high CO CO Carbon monoxide concentrations

Ensure occupant can operate and maintain installations

Inform occupant regarding possible CO CO Carbon monoxide hazards