Nine Mile Point 1
2Q/2012 Performance Indicators
Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Unplanned scrams | 0 | 1.0 | 0 | 1.0 | 0 | 0 | 0 | 0 |
Critical hours | 2208.0 | 2138.5 | 1898.0 | 1390.7 | 2208.0 | 2209.0 | 2065.3 | 2184.0 |
Indicator value | 0.8 | 0.8 | 0.8 | 1.8 | 1.8 | 0.9 | 0.9 | 0 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Unplanned power changes | 0 | 0 | 1.0 | 0 | 0 | 0 | 1.0 | 0 |
Critical hours | 2208.0 | 2138.5 | 1898.0 | 1390.7 | 2208.0 | 2209.0 | 2065.3 | 2184.0 |
Indicator value | 0 | 0 | 0.8 | 0.9 | 0.9 | 0.9 | 0.9 | 0.8 |
Licensee Comments: none
Unplanned Scrams with Complications | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Scrams with complications | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (BWR) | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Safety System Functional Failures | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
UAI (ΔCDF) | -4.26E-09 | -4.25E-09 | -4.24E-09 | -4.18E-09 | -3.27E-09 | -3.28E-09 | -2.95E-09 | -2.84E-09 |
URI (ΔCDF) | 1.57E-08 | 1.72E-08 | 1.59E-08 | 1.62E-08 | 1.25E-08 | 1.19E-08 | 1.35E-08 | 1.39E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 1.10E-08 | 1.30E-08 | 1.20E-08 | 1.20E-08 | 9.20E-09 | 8.60E-09 | 1.10E-08 | 1.10E-08 |
Licensee Comments:
1Q/11: MSPI Planned Unavailability Coefficients were updated to align with changes in maintenance strategies including newly identified work, offline work being performed online, and unavailability activities no longer being performed in parallel
Mitigating Systems Performance Index, High Pressure Injection System | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
UAI (ΔCDF) | -1.13E-08 | -1.13E-08 | -1.13E-08 | -1.09E-08 | -1.09E-08 | -1.09E-08 | -1.09E-08 | -1.09E-08 |
URI (ΔCDF) | -1.90E-09 | -1.98E-09 | -2.06E-09 | 9.18E-09 | 9.15E-09 | 9.51E-09 | 9.69E-09 | 9.99E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.30E-08 | -1.30E-08 | -1.30E-08 | -1.70E-09 | -1.70E-09 | -1.40E-09 | -1.20E-09 | -8.90E-10 |
Licensee Comments:
1Q/11: MSPI Planned Unavailability Coefficients were updated to align with changes in maintenance strategies including newly identified work, offline work being performed online, and unavailability activities no longer being performed in parallel
Mitigating Systems Performance Index, Heat Removal System | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
UAI (ΔCDF) | -1.11E-09 | -1.11E-09 | -1.24E-09 | -1.24E-09 | -1.24E-09 | -1.24E-09 | -1.24E-09 | -1.24E-09 |
URI (ΔCDF) | -5.06E-10 | -4.98E-10 | -5.14E-10 | -5.25E-10 | -5.14E-10 | -5.06E-10 | -4.69E-10 | -4.42E-10 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.60E-09 | -1.60E-09 | -1.80E-09 | -1.80E-09 | -1.80E-09 | -1.70E-09 | -1.70E-09 | -1.70E-09 |
Licensee Comments:
1Q/11: MSPI Planned Unavailability Coefficients were updated to align with changes in maintenance strategies including newly identified work, offline work being performed online, and unavailability activities no longer being performed in parallel
Mitigating Systems Performance Index, Residual Heat Removal System | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
UAI (ΔCDF) | -1.47E-10 | -1.47E-10 | -1.46E-10 | -1.46E-10 | -1.46E-10 | -1.46E-10 | -1.46E-10 | -1.46E-10 |
URI (ΔCDF) | -1.43E-09 | -1.44E-09 | -1.44E-09 | -1.54E-09 | -1.53E-09 | -1.54E-09 | -1.55E-09 | -1.46E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.60E-09 | -1.60E-09 | -1.60E-09 | -1.70E-09 | -1.70E-09 | -1.70E-09 | -1.70E-09 | -1.60E-09 |
Licensee Comments:
1Q/11: MSPI Planned Unavailability Coefficients were updated to align with changes in maintenance strategies including newly identified work, offline work being performed online, and unavailability activities no longer being performed in parallel
Mitigating Systems Performance Index, Cooling Water Systems | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
UAI (ΔCDF) | -1.57E-08 | -1.57E-08 | -1.57E-08 | -1.57E-08 | -1.57E-08 | -1.57E-08 | -1.57E-08 | -1.57E-08 |
URI (ΔCDF) | 1.33E-08 | 1.33E-08 | 1.33E-08 | 1.33E-08 | 1.33E-08 | 1.33E-08 | 1.33E-08 | 1.34E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -2.40E-09 | -2.40E-09 | -2.40E-09 | -2.40E-09 | -2.40E-09 | -2.40E-09 | -2.40E-09 | -2.30E-09 |
Licensee Comments:
1Q/11: MSPI Planned Unavailability Coefficients were updated to align with changes in maintenance strategies including newly identified work, offline work being performed online, and unavailability activities no longer being performed in parallel
Reactor Coolant System Activity | 7/10 | 8/10 | 9/10 | 10/10 | 11/10 | 12/10 | 1/11 | 2/11 | 3/11 | 4/11 | 5/11 | 6/11 |
Maximum activity | 0.000006 | 0.000005 | 0.000008 | 0.000007 | 0.000007 | 0.000005 | 0.000004 | 0.000005 | 0.000005 | N/A | N/A | 0.000009 |
Technical specification limit | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | N/A | N/A | 0 |
Reactor Coolant System Activity | 7/11 | 8/11 | 9/11 | 10/11 | 11/11 | 12/11 | 1/12 | 2/12 | 3/12 | 4/12 | 5/12 | 6/12 |
Maximum activity | 0.000008 | 0.000007 | 0.000006 | 0.000007 | 0.000007 | 0.000009 | 0.000007 | 0.000007 | 0.000007 | 0.000016 | 0.000007 | 0.000008 |
Technical specification limit | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Reactor Coolant System Leakage | 7/10 | 8/10 | 9/10 | 10/10 | 11/10 | 12/10 | 1/11 | 2/11 | 3/11 | 4/11 | 5/11 | 6/11 |
Maximum leakage | 5.135 | 5.347 | 4.660 | 4.511 | 5.339 | 5.382 | 5.753 | 5.947 | 6.214 | 4.657 | 4.480 | 5.562 |
Technical specification limit | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 |
Indicator value | 20.5 | 21.4 | 18.6 | 18.0 | 21.4 | 21.5 | 23.0 | 23.8 | 24.9 | 18.6 | 17.9 | 22.2 |
Reactor Coolant System Leakage | 7/11 | 8/11 | 9/11 | 10/11 | 11/11 | 12/11 | 1/12 | 2/12 | 3/12 | 4/12 | 5/12 | 6/12 |
Maximum leakage | 5.664 | 4.717 | 4.583 | 5.057 | 5.452 | 5.834 | 5.469 | 5.174 | 6.457 | 6.434 | 6.881 | 6.480 |
Technical specification limit | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 | 25.0 |
Indicator value | 22.7 | 18.9 | 18.3 | 20.2 | 21.8 | 23.3 | 21.9 | 20.7 | 25.8 | 25.7 | 27.5 | 25.9 |
Licensee Comments:
6/11: Change reflects Maximum RCS Identified leakage value since 1Q2010. Unit 1 does not have a technical specification limit on identified leakage. Per NEI 99-02, the total leakage must be entered instead of the identified leakage. However, identified leakage was entered since 1Q2010. This was corrected in 3Q2011. This change has no impact on the color of the indicator.
3/11: Change reflects Maximum RCS Identified leakage value since 1Q2010. Unit 1 does not have a technical specification limit on identified leakage. Per NEI 99-02, the total leakage must be entered instead of the identified leakage. However, identified leakage was entered since 1Q2010. This was corrected in 3Q2011. This change has no impact on the color of the indicator.
12/10: Change reflects Maximum RCS Identified leakage value since 1Q2010. Unit 1 does not have a technical specification limit on identified leakage. Per NEI 99-02, the total leakage must be entered instead of the identified leakage. However, identified leakage was entered since 1Q2010. This was corrected in 3Q2011. This change has no impact on the color of the indicator.
9/10: Change reflects Maximum RCS Identified leakage value since 1Q2010. Unit 1 does not have a technical specification limit on identified leakage. Per NEI 99-02, the total leakage must be entered instead of the identified leakage. However, identified leakage was entered since 1Q2010. This was corrected in 3Q2011. This change has no impact on the color of the indicator.
Drill/Exercise Performance | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Successful opportunities | 21.0 | 50.0 | 33.0 | 11.0 | 26.0 | 60.0 | 37.0 | 3.0 |
Total opportunities | 21.0 | 51.0 | 33.0 | 11.0 | 26.0 | 61.0 | 38.0 | 3.0 |
Indicator value | 97.8% | 98.3% | 98.5% | 98.5% | 99.0% | 98.9% | 98.8% | 98.8% |
Licensee Comments: none
ERO Drill Participation | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Participating Key personnel | 101.0 | 96.0 | 100.0 | 102.0 | 97.0 | 90.0 | 88.0 | 83.0 |
Total Key personnel | 101.0 | 96.0 | 100.0 | 102.0 | 97.0 | 90.0 | 88.0 | 83.0 |
Indicator value | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% |
Licensee Comments: none
Alert & Notification System | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
Successful siren-tests | 256 | 296 | 222 | 258 | 258 | 295 | 222 | 296 |
Total sirens-tests | 259 | 296 | 222 | 259 | 259 | 296 | 222 | 296 |
Indicator value | 99.7% | 99.7% | 99.7% | 99.6% | 99.8% | 99.7% | 99.7% | 99.8% |
Licensee Comments:
3Q/10: Change reflect correction to Successful siren-test and Total siren-test for August 2010. They were reported as 74 each. The actual numbers should have been 111 each. This change has no impact on the color of the indicator which continues to be in GREEN
Occupational Exposure Control Effectiveness | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
High radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 3Q/10 | 4Q/10 | 1Q/11 | 2Q/11 | 3Q/11 | 4Q/11 | 1Q/12 | 2Q/12 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Although the Security Cornerstone is included in the Reactor Oversight Process assessment program, the Commission has decided that specific information related to findings and performance indicators pertaining to the Security Cornerstone will not be publicly available to ensure that security information is not provided to a possible adversary. Other than the fact that a finding or performance indicator is Green or Greater-Than-Green, security related information will not be displayed on the public web page.