United States Nuclear Regulatory Commission - Protecting People and the Environment

D.C. Cook 1

2Q/2012 Performance Indicators

Licensee's General Comments: none



Link to Notes

Unplanned Scrams per 7000 Critical Hrs 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Unplanned scrams 0 0 0 0 1.0 0 0 0
Critical hours 2208.0 2209.0 2031.6 2184.0 1916.6 1617.1 2183.0 2184.0
                 
Indicator value 0 0 0 0 0.8 0.9 0.9 0.9


Licensee Comments:

3Q/11: One unplanned scram: Automatic trip of Unit 1 reactor on September 7 due to a main turbine trip initiated by thrust position circuitry.




Link to Notes

Unplanned Power Changes per 7000 Critical Hrs 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Unplanned power changes 0 0 1.0 0 0 2.0 0 0
Critical hours 2208.0 2209.0 2031.6 2184.0 1916.6 1617.1 2183.0 2184.0
                 
Indicator value 1.2 0.9 1.7 0.8 0.8 2.7 1.8 1.8

Licensee Comments:

4Q/11: Two unplanned power changes: November 25 - power reduced to approximately 54% due to East Main Feedwater Pump high vibrations (turbine shaft failure). December 21 - power reduced to approximately 57% due to EHC fluid leak on West Main Feedwater Pump.

1Q/11: Data reflects unplanned power reduction from 100% to approximately 48% on February 17 for repair of steam leak on bleed steam system check valve






Link to Notes

Unplanned Scrams with Complications 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Scrams with complications 0 0 0 0 0 0 0 0
                 
                 
Indicator value 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Licensee Comments: none






Link to Notes

Safety System Functional Failures (PWR) 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Safety System Functional Failures 0 0 0 0 0 0 0 0
                 
Indicator value 1 1 1 0 0 0 0 0

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Emergency AC Power System 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
UAI (ΔCDF) 6.21E-10 6.21E-10 6.19E-10 5.74E-10 5.80E-10 4.86E-10 4.87E-10 4.00E-10
URI (ΔCDF) 1.35E-07 1.35E-07 1.35E-07 1.35E-07 1.33E-07 1.33E-07 2.85E-07 2.85E-07
PLE NO NO NO NO NO NO NO NO
                 
Indicator value 1.40E-07 1.40E-07 1.40E-07 1.40E-07 1.30E-07 1.30E-07 2.90E-07 2.90E-07

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, High Pressure Injection System 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
UAI (ΔCDF) -2.67E-11 -2.67E-11 -2.67E-11 -3.65E-12 -2.30E-12 -5.56E-12 -8.42E-12 -1.04E-11
URI (ΔCDF) -2.51E-08 -2.51E-08 -2.51E-08 -2.41E-08 -2.58E-08 -2.58E-08 -2.58E-08 -2.58E-08
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -2.50E-08 -2.50E-08 -2.50E-08 -2.40E-08 -2.60E-08 -2.60E-08 -2.60E-08 -2.60E-08

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Heat Removal System 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
UAI (ΔCDF) -2.86E-11 -2.86E-11 -2.86E-11 -2.15E-11 -2.01E-11 -2.37E-11 -2.47E-11 -2.80E-11
URI (ΔCDF) -3.06E-08 -3.06E-08 -3.06E-08 -3.06E-08 -3.15E-08 -3.15E-08 -3.15E-08 -3.15E-08
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -3.10E-08 -3.10E-08 -3.10E-08 -3.10E-08 -3.10E-08 -3.10E-08 -3.10E-08 -3.10E-08

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Residual Heat Removal System 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
UAI (ΔCDF) -3.23E-13 -3.23E-13 -3.23E-13 -3.23E-13 -2.18E-13 -3.05E-13 -3.23E-13 -3.23E-13
URI (ΔCDF) -9.13E-08 -9.13E-08 -9.13E-08 -9.13E-08 -9.76E-08 -9.76E-08 -9.76E-08 -9.76E-08
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -9.10E-08 -9.10E-08 -9.10E-08 -9.10E-08 -9.80E-08 -9.80E-08 -9.80E-08 -9.80E-08

Licensee Comments:

2Q/12: The MSPI Basis document was revised to exclude two Unit 1 RHR heat exchanger CCW outlet valves from monitoring based on their Birnbaum importance.






Link to Notes

Mitigating Systems Performance Index, Cooling Water Systems 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
UAI (ΔCDF) -3.23E-12 -3.23E-12 3.95E-11 6.25E-11 6.36E-11 4.62E-11 4.25E-11 2.77E-11
URI (ΔCDF) -1.42E-07 -1.42E-07 -4.58E-08 -4.58E-08 -4.69E-08 -4.69E-08 -4.69E-08 -4.69E-08
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -1.40E-07 -1.40E-07 -4.60E-08 -4.60E-08 -4.70E-08 -4.70E-08 -4.70E-08 -4.70E-08

Licensee Comments: none






Link to Notes

Reactor Coolant System Activity 7/10 8/10 9/10 10/10 11/10 12/10 1/11 2/11 3/11 4/11 5/11 6/11
Maximum activity 0.001330 0.001360 0.001420 0.001580 0.001560 0.001610 0.001680 0.001750 0.001760 0.002300 0.003800 0.002470
Technical specification limit 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
                         
Indicator value 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.4 0.2
Reactor Coolant System Activity 7/11 8/11 9/11 10/11 11/11 12/11 1/12 2/12 3/12 4/12 5/12 6/12
Maximum activity 0.002560 0.002610 0.003030 N/A 0.000843 0.000793 0.000850 0.000885 0.000932 0.000939 0.000977 0.001050
Technical specification limit 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
                         
Indicator value 0.3 0.3 0.3 N/A 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Licensee Comments:

12/11: Due to a refueling outage followed by power escalation, RCS Activity data is not available for the month of October.






Link to Notes

Reactor Coolant System Leakage 7/10 8/10 9/10 10/10 11/10 12/10 1/11 2/11 3/11 4/11 5/11 6/11
Maximum leakage 0.047 0.006 0.009 0.013 0.057 0.028 0.011 0.015 0.150 0.026 0.015 0.024
Technical specification limit 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
                         
Indicator value 0.4 0.1 0.1 0.1 0.5 0.3 0.1 0.1 1.4 0.2 0.1 0.2
Reactor Coolant System Leakage 7/11 8/11 9/11 10/11 11/11 12/11 1/12 2/12 3/12 4/12 5/12 6/12
Maximum leakage 0.012 0.009 0.094 0.036 0.020 0.075 0.009 0.017 0.012 0.005 0.012 0.012
Technical specification limit 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
                         
Indicator value 0.1 0.1 0.9 0.3 0.2 0.7 0.1 0.2 0.1 0 0.1 0.1

Licensee Comments: none






Link to Notes

Drill/Exercise Performance 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Successful opportunities 29.0 19.0 43.0 16.0 41.0 0 34.0 24.0
Total opportunities 29.0 19.0 50.0 16.0 41.0 0 35.0 25.0
                 
Indicator value 96.9% 97.9% 95.1% 95.3% 95.7% 95.4% 95.4% 95.8%

Licensee Comments:

1Q/11: Previously submitted data for February 2011 was revised to correct an error in grading drill results. Data was changed from "19 of 21 successful" to "18 of 21 successful". This changes the first quarter 2011 total from "44 of 50 successful" to "43 of 50 successful". This change has no impact on performance indicator color.






Link to Notes

ERO Drill Participation 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Participating Key personnel 103.0 94.0 92.0 92.0 91.0 91.0 91.0 89.0
Total Key personnel 106.0 95.0 92.0 92.0 91.0 91.0 91.0 89.0
                 
Indicator value 97.2% 98.9% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%

Licensee Comments: none






Link to Notes

Alert & Notification System 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
Successful siren-tests 1118 1118 1119 1117 1120 1120 1118 1118
Total sirens-tests 1119 1120 1120 1119 1120 1120 1120 1119
                 
Indicator value 100.0% 99.9% 99.9% 99.9% 99.9% 99.9% 99.9% 99.9%

Licensee Comments: none






Link to Notes

Occupational Exposure Control Effectiveness 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
High radiation area occurrences 0 0 0 0 0 0 0 0
Very high radiation area occurrences 0 0 0 0 0 0 0 0
Unintended exposure occurrences 0 0 0 0 0 0 0 0
Indicator value 0 0 0 0 0 0 0 0

Licensee Comments: none






Link to Notes

RETS/ODCM Radiological Effluent 3Q/10 4Q/10 1Q/11 2Q/11 3Q/11 4Q/11 1Q/12 2Q/12
RETS/ODCM occurrences 0 0 0 0 0 0 0 0
                 
Indicator value 0 0 0 0 0 0 0 0

Licensee Comments: none






Although the Security Cornerstone is included in the Reactor Oversight Process assessment program, the Commission has decided that specific information related to findings and performance indicators pertaining to the Security Cornerstone will not be publicly available to ensure that security information is not provided to a possible adversary. Other than the fact that a finding or performance indicator is Green or Greater-Than-Green, security related information will not be displayed on the public web page.





 
 
 
 