Electricity
‹ See entire Electric Power Annual
Electric Power Annual 2010 Data Tables
With Data for 2010 | Release Date: November 09, 2011 | Next Release Date: November 2012
FRCC | MRO | NPCC | RFC | SERC | SPP | TRE | WECC | Contigious U.S. |
FRCC | MRO | NPCC | RFC | SERC | SPP | TRE | WECC | Contigious U.S. |
|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AC & DC Circuit Outage Hours | Percent | |||||||||||||||||
Sustained Outage Causes | ||||||||||||||||||
Weather, excluding lightning | - | 2,050 | 21 | 568 | 849 | 668 | 0.05 | 4,626 | 8,782 | - | 22.3 | 0.1 | 4.1 | 18.3 | 59.8 | 0.0 | 19.5 | 11.7 |
Lightning | 8 | 2 | 1 | 82 | 130 | 38 | 26 | 101 | 388 | 0.1 | 0.0 | 0.0 | 0.6 | 2.8 | 3.4 | 2.4 | 0.4 | 0.5 |
Environmental | - | 2 | - | 8 | 202 | - | - | 11 | 222 | - | 0.0 | - | 0.1 | 4.3 | - | - | 0.0 | 0.3 |
Contamination | 9 | 17 | 0.02 | - | 446 | 2 | 0.02 | 37 | 512 | 0.1 | 0.2 | 0.0 | - | 9.6 | 0.2 | 0.0 | 0.2 | 0.7 |
Foreign Interference | 74 | 0.03 | 835 | 92 | 150 | - | 23 | 57 | 1,232 | 1.1 | 0.0 | 5.7 | 0.7 | 3.2 | - | 2.1 | 0.2 | 1.6 |
Fire | 0.08 | - | 766 | 12 | 4 | 27 | - | 373 | 1,181 | 0.0 | - | 5.3 | 0.1 | 0.1 | 2.4 | - | 1.6 | 1.6 |
Vandalism, Terrorism, or Malicious Acts | - | - | - | - | - | - | - | 18 | 18 | - | - | - | - | - | - | - | 0.1 | 0.0 |
Failed AC Substation Equipment | 6,091 | 614 | 11,329 | 8,863 | 715 | 27 | 625 | 3,496 | 31,761 | 88.7 | 6.7 | 78.0 | 64.4 | 15.4 | 2.4 | 57.4 | 14.8 | 42.4 |
Failed AC/DC Terminal Equipment | - | 812 | - | 429 | - | - | - | 9 | 1,250 | - | 8.8 | - | 3.1 | - | - | - | 0.0 | 1.7 |
Failed Protection System Equipment | 36 | 38 | 223 | 396 | 223 | 5 | 50 | 116 | 1,086 | 0.5 | 0.4 | 1.5 | 2.9 | 4.8 | 0.5 | 4.6 | 0.5 | 1.5 |
Failed AC Circuit Equipment | 521 | 4,742 | 1,235 | 2,489 | 1,380 | 90 | 342 | 3,353 | 14,152 | 7.6 | 51.5 | 8.5 | 18.1 | 29.7 | 8.1 | 31.4 | 14.2 | 18.9 |
Failed DC Circuit Equipment | - | 56 | - | - | - | - | - | 47 | 102 | - | 0.6 | - | - | - | - | - | 0.2 | 0.1 |
Vegetation | - | - | 27 | 4 | 115 | 4 | - | 78 | 228 | - | - | 0.2 | 0.0 | 2.5 | 0.4 | - | 0.3 | 0.3 |
Power System Condition | 1 | 228 | 54 | 12 | - | 138 | 4 | 131 | 569 | 0.0 | 2.5 | 0.4 | 0.1 | - | 12.3 | 0.4 | 0.6 | 0.8 |
Human Error | 9 | 457 | 12 | 48 | 244 | 0.20 | 6 | 318 | 1,095 | 0.1 | 5.0 | 0.1 | 0.3 | 5.3 | 0.0 | 0.6 | 1.3 | 1.5 |
Unknown | 83 | 12 | 1 | 513 | 66 | 79 | 13 | 1,998 | 2,765 | 1.2 | 0.1 | 0.0 | 3.7 | 1.4 | 7.1 | 1.2 | 8.4 | 3.7 |
Other | 32 | 174 | 26 | 253 | 118 | 39 | 0.15 | 8,899 | 9,542 | 0.5 | 1.9 | 0.2 | 1.8 | 2.5 | 3.5 | 0.0 | 37.6 | 12.7 |
TOTAL | 6,864 | 9,204 | 14,530 | 13,770 | 4,642 | 1,117 | 1,089 | 23,669 | 74,884 | 100.0 | 100.0 | 100.0 | 100.0 | 100.0 | 100.0 | 100.0 | 100.0 | 100.0 |
Notes: • Detailed information on the Transmission Availability Data System outage causes is available at: http://www.nerc.com/docs/pc/tadswg/Appendix%207%2020101202a%20clean.pdf Source: U.S. Energy Information Administration, Form EIA-411, "Coordinated Bulk Power Supply Program Report." |