EQ Hazardous Waste Plant Explosions and Fire

Location: Apex, NC
October 05, 2006

EQ Hazardous Waste Plant Explosions and Fire

EQ Hazardous Waste Plant Explosions and Fire

Accident Description

Explosions and fire at a hazardous waste facility forced the evacuation of approximately 16,000 residents from Apex, North Carolina, on October 5, 2006. The incident likely began in the oxidizer section of the EQ North Carolina waste facility, where chemicals such as pool chlorination tablets were stored. The fire was allowed to burn out and the facility was destroyed.

View Investigation Information

Recommendations

Environmental Protection Agency (EPA)

2007-1-I-NC-1

Ensure that the emergency response planning required for permitted hazardous waste treatment, storage, and disposal facilities (40 CFR 264.37) includes providing written information to state and local emergency response officials on the type, approximate quantities, and locations of materials within the facility (similar to reporting requirements of the Emergency Planning and Community Right-to-Know Act). Additionally, ensure that permit holders periodically update this information throughout the ten-year permit period.
Status: C-AA

Mobile Aerospace Engineering, Inc.

2007-1-I-NC-1URGENT!

Revise and or develop company procedures and policies to require and ensure that unspent chemical oxygen generators that have exceeded their service life be actuated so that the chemical core is expended before shipping by any transport mode.
Status: C-AA
Download Document

2007-1-I-NC-2URGENT!

Review and revise as necessary company procedures and policies for transporting hazardous waste to ensure that hazardous waste is correctly characterized on the shipping manifest.
Status: C-AA

2007-1-I-NC-3URGENT!

Communicate to all of your waste brokers and treatment, storage, and disposal facilities to which unspent oxygen generators were shipped: - the hazards associated with unspent chemical oxygen generators and - that the incorrect shipping name and UN code was, or might have been used, for unspent chemical oxygen generators shipped from your facility.
Status: C-AA

Environmental Technology Council

2007-1-I-NC-2

Superseded by 2009-10-I-OH-R6
Petition the National Fire Protection Association, following the guidelines of their "Codes and Standards Development Process" (http://www.nfpa.org/index.asp), to develop a fire protection standard (occupancy standard) specific to hazardous waste treatment, storage, and disposal facilities. This standard should address fire prevention, detection, control, and suppression requirements.

Status: C-R/S

2007-1-I-NC-3

Superseded by 2009-10-I-OH-R7
Develop standardized guidance for the handling and storage of hazardous waste to reduce the likelihood of releases and fires at hazardous waste treatment, storage, and disposal facilities.

Status: C-R/S