CRANES AND DERRICKS - §1926.550

General Requirements

Crane

The employer shall comply with the manufacturer's specifications and limitations applicable to the operation of any and all cranes and derricks. Where manufacturer's specifications are not available, the limitations assigned to the equipment shall be based on the determinations of a qualified engineer competent in this field and such determinations will be appropriately documented and recorded. Attachments used with cranes shall not exceed the capacity, rating, or scope recommended by the manufacturer.

Rated load capacities, and recommended operating speeds, special hazard warnings, or instruction, shall be conspicuously posted on all equipment. Instructions or warnings shall be visible to operators while they are at their control stations.

Hand signals to crane and derrick operators shall be those prescribed by the applicable ANSI standard for the type of crane in use. An illustration of the signals shall be posted at the job site.

The employer shall designate a competent person who shall inspect all machinery and equipment prior to each use, and during use, to make sure it is in safe operating condition. Any deficiencies shall be repaired, or defective parts replaced, before continued use.

A thorough, annual inspection of the hoisting machinery shall be made by a competent person, or by a government or private agency recognized by the U.S. Department of Labor. The employer shall maintain a record of the dates and results of inspections for each hoisting machine and piece of equipment.

Wire rope shall be taken out of service when any of the following conditions exist:

  • In running ropes, six randomly distributed broken wires in one lay or three broken wires in one strand in one lay;
  • Wear of one-third the original diameter of outside individual wires. Kinking, crushing, bird caging, or any other damage resulting in distortion of the rope structure;
  • Evidence of any heat damage from any cause;
  • Reductions from nominal diameter of more than one-sixty-fourth inch for diameters up to and including five-sixteenths inch, one-thirty-second inch for diameters three-eighths inch to and including one-half inch, three-sixty-fourths inch for diameters nine-sixteenths inch to and including three-fourths inch, one-sixteenth inch for diameters seven-eighths inch to 1 inches inclusive, three-thirty-seconds inch for diameters 1¼ to 1½ inches inclusive;
  • In standing ropes, more than two broken wires in one lay in sections beyond end connections or more than one broken wire at an end connection.
  • Wire rope safety factors shall be in accordance with American National Standards Institute B30.5-1968 or SAE J959-1966.

Belts, gears, shafts, pulleys, sprockets, spindles, drums, fly wheels, chains, or other reciprocating, rotating, or other moving parts or equipment shall be guarded if such parts are exposed to contact by employees, or otherwise create a hazard. Guarding shall meet the requirements of the American National Standards Institute B15.1-1958 Rev., Safety Code for Mechanical Power Transmission Apparatus.

Accessible areas within the swing radius of the rear of the rotating superstructure of the crane, either permanently or temporarily mounted, shall be barricaded in such a manner as to prevent an employee from being struck or crushed by the crane.

All exhaust pipes shall be guarded or insulated in areas where contact by employees is possible in the performance of normal duties.

Whenever internal combustion engine powered equipment exhausts in enclosed spaces, tests shall be made and recorded to see that employees are not exposed to unsafe concentrations of toxic gases or oxygen deficient atmospheres.

All windows in cabs shall be of safety glass, or equivalent, that introduces no visible distortion that will interfere with the safe operation of the machine.

Where necessary for rigging or service requirements, a ladder, or steps, shall be provided to give access to a cab roof. Guardrails, handholds, and steps shall be provided on cranes for easy access to the car and cab, conforming to American National Standards Institute B30.5.

Platforms and walkways shall have anti-skid surfaces.

Fuel tank filler pipe shall be located in such a position, or protected in such manner, as to not allow spill or overflow to run onto the engine, exhaust, or electrical equipment of any machine being fueled.

An accessible fire extinguisher of 5BC rating, or higher, shall be available at all operator stations or cabs of equipment.

All fuels shall be transported, stored, and handled to meet the rules of Subpart F, Fire Protection and Prevention. When fuel is transported by vehicles on public highways, Department of Transportation rules contained in 49 CFR Parts 177 and 393 concerning such vehicular transportation are considered applicable.

Except where electrical distribution and transmission lines have been deenergized and visibly grounded at point of work or where insulating barriers, not a part of or an attachment to the equipment or machinery, have been erected to prevent physical contact with the lines, equipment or machines shall be operated proximate to power lines only in accordance with the following:

  • For lines rated 50 kV. or below, minimum clearance between the lines and any part of the crane or load shall be 10 feet;
  • For lines rated over 50 kV., minimum clearance between the lines and any part of the crane or load shall be 10 feet plus 0.4 inch for each 1 kV. over 50 kV., or twice the length of the line insulator, but never less than 10 feet;
  • In transit with no load and boom lowered, the equipment clearance shall be a minimum of 4 feet for voltages less than 50 kV., and 10 feet for voltages over 50 kV., up to and including 345 kV., and 16 feet for voltages up to and including 750 kV.
  • A person shall be designated to observe clearance of the equipment and give timely warning for all operations where it is difficult for the operator to maintain the desired clearance by visual means;
  • Cage-type boom guards, insulating links, or proximity warning devices may be used on cranes, but the use of such devices shall not alter the requirements of any other regulation of this part even if such device is required by law or regulation;
  • Any overhead wire shall be considered to be an energized line unless and until the person owning such line or the electrical utility authorities indicate that it is not an energized line and it has been visibly grounded;
  • Prior to work near transmitter towers where an electrical charge can be induced in the equipment or materials being handled, the transmitter shall be de-energized or tests shall be made to determine if electrical charge is induced on the crane. The following precautions shall be taken when necessary to dissipate induced voltages:
    • The equipment shall be provided with an electrical ground directly to the upper rotating structure supporting the boom; and
    • Ground jumper cables shall be attached to materials being handled by boom equipment when electrical charge is induced while working near energized transmitters. Crews shall be provided with nonconductive poles having large alligator clips or other similar protection to attach the ground cable to the load.
    • Combustible and flammable materials shall be removed from the immediate area prior to operations.

No modifications or additions which affect the capacity or safe operation of the equipment shall be made by the employer without the manufacturer's written approval. If such modifications or changes are made, the capacity, operation, and maintenance instruction plates, tags, or decals, shall be changed accordingly. In no case shall the original safety factor of the equipment be reduced.

The employer shall comply with Power Crane and Shovel Association Mobile Hydraulic Crane Standard No. 2.

Sideboom cranes mounted on wheel or crawler tractors shall meet the requirements of SAE J743a-1964.

All employees shall be kept clear of loads about to be lifted and of suspended loads.

Crawler, Locomotive, and Truck Cranes

All jibs shall have positive stops to prevent their movement of more than 5o above the straight line of the jib and boom on conventional type crane booms. The use of cable type belly slings does not constitute compliance with this rule. All crawler, truck, or locomotive cranes in use shall meet the applicable requirements for design, inspection, construction, testing, maintenance and operation as prescribed in the ANSI B30.5-1968, Safety Code for Crawler, Locomotive and Truck Cranes. However, the written, dated, and signed inspection reports and records of the monthly inspection of critical items prescribed in section 5-2.1.5 of the ANSI B30.5-1968 standard are not required. Instead, the employer shall prepare a certification record which includes the date the crane items were inspected; the signature of the person who inspected the crane items; and a serial number, or other identifier, for the crane inspected. The most recent certification record shall be maintained on file until a new one is prepared.

Hammerhead Tower Cranes

Adequate clearance shall be maintained between moving and rotating structures of the crane and fixed objects to allow the passage of employees without harm.

Each employee required to perform duties on the horizontal boom of hammerhead tower cranes shall be protected against falling by guardrails or by a personal fall arrest system in conformance with Subpart M, Fall Protection.

Buffers shall be provided at both ends of travel of the trolley.

Cranes mounted on rail tracks shall be equipped with limit switches limiting the travel of the crane on the track and stops or buffers at each end of the tracks.

All hammerhead tower cranes in use shall meet the applicable requirements for design, construction, installation, testing, maintenance, inspection, and operation as prescribed by the manufacturer.

Overhead and Gantry Cranes

The rated load of the crane shall be plainly marked on each side of the crane, and if the crane has more than one hoisting unit, each hoist shall have its rated load marked on it or its load block, and this marking shall be clearly legible from the ground or floor.

Bridge trucks shall be equipped with sweeps which extend below the top of the rail and project in front of the truck wheels.

Except for floor-operated cranes, a gong or other effective audible warning signal shall be provided for each crane equipped with a power traveling mechanism.

All overhead and gantry cranes in use shall meet the applicable requirements for design, construction, installation, testing, maintenance, inspection, and operation as prescribed in the ANSI B30.2.0-1967, Safety Code for Overhead and Gantry Cranes.

Derricks

All derricks in use shall meet the applicable requirements for design, construction, installation, inspection, testing, maintenance, and operation as prescribed in American National Standards Institute B30.6-1969, Safety Code for Derricks.

Floating Cranes and Derricks

Mobile Cranes Mounted on Barges

When a mobile crane is mounted on a barge, the rated load of the crane shall not exceed the original capacity specified by the manufacturer.

A load rating chart, with clearly legible letters and figures, shall be provided with each crane, and securely fixed at a location easily visible to the operator.

When load ratings are reduced to stay within the limits for list of the barge with a crane mounted on it, a new load rating chart shall be provided.

Mobile cranes on barges shall be positively secured.

Permanently Mounted Floating Cranes and Derricks

When cranes and derricks are permanently installed on a barge, the capacity and limitations of use shall be based on competent design criteria.

A load rating chart with clearly legible letters and figures shall be provided and securely fixed at a location easily visible to the operator.

Floating cranes and floating derricks in use shall meet the applicable requirements for design, construction, installation, testing, maintenance, and operation as prescribed by the manufacturer.

Protection of Employees Working on Barges

The employer shall comply with the applicable requirements for protection of employees working onboard marine vessels specified in §1926.605.

Crane or Derrick Suspended Personnel Platforms

This standard, §1926.550(g), is discussed in a separate document.

HELICOPTERS - §1926.551

Helicopter Regulations

Helicopter

Helicopter cranes shall be expected to comply with any applicable regulations of the Federal Aviation Administration.

Briefing

Prior to each day's operation a briefing shall be conducted. This briefing shall set forth the plan of operation for the pilot and ground personnel.

Slings and Tag Lines

Load shall be properly slung. Tag lines shall be of a length that will not permit their being drawn up into rotors. Pressed sleeve, swedged eyes, or equivalent means shall be used for all freely suspended loads to prevent hand splices from spinning open or cable clamps from loosening.

Cargo Hooks

All electrically operated cargo hooks shall have the electrical activating device so designed and installed as to prevent inadvertent operation. In addition, these cargo hooks shall be equipped with an emergency mechanical control for releasing the load. The hooks shall be tested prior to each day's operation to determine that the

release functions properly, both electrically and mechanically.

Personal Protective Equipment

Personal protective equipment for employees receiving the load shall consist of complete eye protection and hard hats secured by chin straps.

Loose-fitting clothing likely to flap in the downwash, and thus be snagged on hoist line, shall not be worn.

Loose Gear and Objects

Every practical precaution shall be taken to provide for the protection of the employees from flying objects in the rotor downwash. All loose gear within 100 feet of the place of lifting the load, depositing the load, and all other areas susceptible to rotor downwash shall be secured or removed.

Housekeeping

Good housekeeping shall be maintained in all helicopter loading and unloading areas.

Operator Responsibility

The helicopter operator shall be responsible for size, weight, and manner in which loads are connected to the helicopter. If, for any reason, the helicopter operator believes the lift cannot be made safely, the lift shall not be made.

Hooking and Unhooking Loads

When employees are required to perform work under hovering craft, a safe means of access shall be provided for employees to reach the hoist line hook and engage or disengage cargo slings. Employees shall not perform work under hovering craft except when necessary to hook or unhook loads.

Static Charge

Static charge on the suspended load shall be dissipated with a grounding device before ground personnel touch the suspended load, or protective rubber gloves shall be worn by all ground personnel touching the suspended load.

Weight Limitation

The weight of an external load shall not exceed the manufacturer's rating.

Ground Lines

Hoist wires or other gear, except for pulling lines or conductors that are allowed to "pay out" from a container or roll off a reel, shall not be attached to any fixed ground structure, or allowed to foul on any fixed structure.

Visibility

When visibility is reduced by dust or other conditions, ground personnel shall exercise special caution to keep clear of main and stabilizing rotors. Precautions shall also be taken by the employer to eliminate as far as practical reduced visibility.

Signal Systems

Signal systems between aircrew and ground personnel shall be understood and checked in advance of hoisting the load. This applies to either radio or hand signal systems. Hand signals shall be as shown in Figure N-1 in §1926.551(n).

Approach Distance

No unauthorized person shall be allowed to approach within 50 feet of the helicopter when the rotor blades are turning.

Approaching Helicopter

Whenever approaching or leaving a helicopter with blades rotating, all employees shall remain in full view of the pilot and keep in a crouched position. Employees shall avoid the area from the cockpit or cabin rearward unless authorized by the helicopter operator to work there.

Personnel

Sufficient ground personnel shall be provided when required for safe helicopter loading and unloading operations.

Communications

There shall be constant reliable communication between the pilot, and a designated employee of the ground crew who acts as a signalman during the period of loading and unloading. This signalman shall be distinctly recognizable from other ground personnel.

Fires

Open fires shall not be permitted in an area that could result in such fires being spread by the rotor downwash.

MATERIAL HOISTS, PERSONNEL HOISTS, AND ELEVATORS - §1926.552

General Requirements

The employer shall comply with the manufacturer's specifications and limitations applicable to the operation of all hoists and elevators. Where manufacturer's specifications are not available, the limitations assigned to the equipment shall be based on the determinations of a professional engineer competent in the field.

Rated load capacities, recommended operating speeds, and special hazard warnings or instructions shall be posted on cars and platforms.

Wire rope shall be removed from service when any of the following conditions exists:

  • In hoisting ropes, six randomly distributed broken wires in one rope lay or three broken wires in one strand in one rope lay;
  • Abrasion, scrubbing, flattening, or peening, causing loss of more than one-third of the original diameter of the outside wires;
  • Evidence of any heat damage resulting from a torch or any damage caused by contact with electrical wires;
  • Reduction from nominal diameter of more than three sixty-fourths inch for diameters up to and including three-fourths inch; one-sixteenth inch for diameters seven-eights to 1 inches; and three thirty-seconds inch for diameters 1¼ to 1½ inches.

Hoisting ropes shall be installed in accordance with the wire rope manufacturers' recommendations.

The installation of live booms on hoists is prohibited.

The use of endless belt-type manlifts on construction shall be prohibited.

Material Hoists

Operating rules shall be established and posted at the operator's station of the hoist. Such rules shall include signal system and allowable line speed for various loads. Rules and notices shall be posted on the car frame or crosshead in a conspicuous location, including the statement "No Riders Allowed."

No person shall be allowed to ride on material hoists except for the purposes of inspection and maintenance.

All entrances of the hoistways shall be protected by substantial gates or bars which shall guard the full width of the landing entrance. All hoistway entrance bars and gates shall be painted with diagonal contrasting colors, such as black and yellow stripes.

Bars shall be not less than 2- by 4-inch wooden bars or the equivalent, located 2 feet from the hoistway line. Bars shall be located not less than 36 inches nor more than 42 inches above the floor.

Gates or bars protecting the entrances to hoistways shall be equipped with a latching device.

Overhead protective covering of 2-inch planking, ¾-inch plywood, or other solid material of equivalent strength, shall be provided on the top of every material hoist cage or platform.

The operator's station of a hoisting machine shall be provided with overhead protection equivalent to tight planking not less than 2 inches thick. The support for the overhead protection shall be of equal strength.

Hoist towers may be used with or without an enclosure on all sides. However, whichever alternative is chosen, the following applicable conditions shall be met:

When a hoist tower is enclosed, it shall be enclosed on all sides for its entire height with a screen enclosure of ½-inch mesh, No. 18 U.S. gauge wire or equivalent, except for landing access.

When a hoist tower is not enclosed, the hoist platform or car shall be totally enclosed (caged) on all sides for the full height between the floor and the overhead protective covering with ½-inch mesh of No. 14 U.S. gauge wire or equivalent. The hoist platform enclosure shall include the required gates for loading and unloading. A 6-foot high enclosure shall be provided on the unused sides of the hoist tower at ground level.

Car arresting devices shall be installed to function in case of rope failure.

All material hoist towers shall be designed by a licensed professional engineer.

All material hoists shall conform to the requirements of ANSI A10.5-1969, Safety Requirements for Material Hoists.

Personnel Hoists

Hoist towers outside the structure shall be enclosed for the full height on the side or sides used for entrance and exit to the structure. At the lowest landing, the enclosure on the sides not used for exit or entrance to the structure shall be enclosed to a height of at least 10 feet. Other sides of the tower adjacent to floors or scaffold platforms shall be enclosed to a height of 10 feet above the level of such floors or scaffolds.

Towers inside of structures shall be enclosed on all four sides throughout the full height.

Towers shall be anchored to the structure at intervals not exceeding 25 feet. In addition to tie-ins, a series of guys shall be installed. Where tie-ins are not practical the tower shall be anchored by means of guys made of wire rope at least one-half inch in diameter, securely fastened to anchorage to ensure stability.

Hoistway doors or gates shall be not less than 6 feet 6 inches high and shall be provided with mechanical locks which cannot be operated from the landing side, and shall be accessible only to persons on the car.

Cars shall be permanently enclosed on all sides and the top, except sides used for entrance and exit which have car gates or doors.

A door or gate shall be provided at each entrance to the car which shall protect the full width and height of the car entrance opening.

Overhead protective covering of 2-inch planking, ¾-inch plywood or other solid material or equivalent strength shall be provided on the top of every personnel hoist.

Doors or gates shall be provided with electric contacts which do not allow movement of the hoist when door or gate is open.

Safeties shall be capable of stopping and holding the car and rated load when traveling at governor tripping speed.

Cars shall be provided with a capacity and data plate secured in a conspicuous place on the car or crosshead.

Internal combustion engines shall not be permitted for direct drive.

Normal and final terminal stopping devices shall be provided.

An emergency stop switch shall be provided in the car and marked "Stop."

The minimum number of hoisting ropes used shall be three for traction hoists and two for drum-type hoists. The minimum diameter of hoisting and counterweight wire ropes shall be ½-inch. Minimum factors of safety for suspension wire ropes are shown in §1926.552(c)(14)(iii).

Following assembly and erection of hoists, and before being put in service, an inspection and test of all functions and safety devices shall be made under the supervision of a competent person. A similar inspection and test is required following major alteration of an existing installation. All hoists shall be inspected and tested at not more than 3-month intervals. The employer shall prepare a certification record which includes the date the inspection and test of all functions and safety devices was performed; the signature of the person who performed the inspection and test; and a serial number, or other identifier, for the hoist that was inspected and tested. The most recent certification record shall be maintained on file.

All personnel hoists used by employees shall be constructed of materials and components which meet the specifications for materials, construction, safety devices, assembly, and structural integrity as stated in the American National Standard A10.4-1963, Safety Requirements for Workmen's Hoists. The requirements of this paragraph §1926.552(c)(16) do not apply to cantilever type personnel hoists.

Personnel hoists used in bridge tower construction shall be approved by a registered professional engineer and erected under the supervision of a qualified engineer competent in this field.

When a hoist tower is not enclosed, the hoist platform or car shall be totally enclosed (caged) on all sides for the full height between the floor and the overhead protective covering with ¾-inch mesh of No. 14 U.S. gauge wire or equivalent. The hoist platform enclosure shall include the required gates for loading and unloading.

These hoists shall be inspected and maintained on a weekly basis. Whenever the hoisting equipment is exposed to winds exceeding 35 miles per hour it shall be inspected and put in operable condition before reuse.

Wire rope shall be taken out of service when any of the following conditions exist:

  • In running ropes, six randomly distributed broken wires in one lay or three broken wires in one strand in one lay;
  • Wear of one-third the original diameter of outside individual wires. Kinking, crushing, bird caging, or any other damage resulting in distortion of the rope structure;
  • Evidence of any heat damage from any cause;
  • Reductions from nominal diameter of more than three-sixty-fourths inch for diameters to and including three-fourths inch, one-sixteenth inch for diameters seven-eights inch to 1 inches inclusive, three-thirty-seconds inch for diameters 1¼ to 1½ inches inclusive;

In standing ropes, more than two broken wires in one lay in sections beyond end connections or more than one broken wire at an end connection.

Permanent elevators under the care and custody of the employer and used by employees for work covered by this Act shall comply with the requirements of American National Standards Institute A17.1-1965 with addenda A17.1a-1967, A17.1b-1968, A17.1c-1969, A17.1d-1970, and inspected in accordance with A17.2-1960 with addenda A17.2a-1965, A17.2b-1967.

BASE-MOUNTED DRUM HOISTS - §1926.553

Exposed moving parts such as gears, projecting screws, setscrews, chain, cables, chain sprockets, and reciprocating or rotating parts, which constitute a hazard, shall be guarded.

All controls used during the normal operation cycle shall be located within easy reach of the operator's station.

Electric motor operated hoists shall be provided with:

  • A device to disconnect all motors from the line upon power failure and not permit any motor to be restarted until the controller handle is brought to the "off" position;
  • Where applicable, an overspeed preventive device;
  • A means whereby remotely operated hoists stop when any control is ineffective.

All base-mounted drum hoists in use shall meet the applicable requirements for design, construction, installation, testing, inspection, maintenance, and operations, as prescribed by the manufacturer.

OVERHEAD HOISTS - §1926.554

  • The safe working load of the overhead hoist, as determined by the manufacturer, shall be indicated on the hoist, and this safe working load shall not be exceeded.
  • The supporting structure to which the hoist is attached shall have a safe working load equal to that of the hoist.
  • The support shall be arranged so as to provide for free movement of the hoist and shall not restrict the hoist from lining itself up with the load.
  • The hoist shall be installed only in locations that will permit the operator to stand clear of the load at all times.
  • Air hoists shall be connected to an air supply of sufficient capacity and pressure to safely operate the hoist. All air hoses supplying air shall be positively connected to prevent their becoming disconnected during use.
  • All overhead hoists in use shall meet the applicable requirements for construction, design, installation, testing, inspection, maintenance, and operation, as prescribed by the manufacturer.

CONVEYORS - §1926.555

  • Means for stopping the motor or engine shall be provided at the operator's station. Conveyor systems shall be equipped with an audible warning signal to be sounded immediately before starting up the conveyor.
  • If the operator's station is at a remote point, similar provisions for stopping the motor or engine shall be provided at the motor or engine location.
  • Emergency stop switches shall be arranged so that the conveyor cannot be started again until the actuating stop switch has been reset to running or "on" position.
  • Screw conveyors shall be guarded to prevent employee contact with turning flights.
  • Where a conveyor passes over work areas, aisles, or thoroughfares, suitable guards shall be provided to protect employees required to work below the conveyors.
  • All crossovers, aisles, and passageways shall be conspicuously marked by suitable signs, as required by Subpart G, Signs, Signals, and Barricades.
  • Conveyors shall be locked out or otherwise rendered inoperable, and tagged out with a "Do Not Operate" tag during repairs and when operation is hazardous to employees performing maintenance work.
  • All conveyors in use shall meet the applicable requirements for design, construction, inspection, testing, maintenance, and operation, as prescribed in the ANSI B20.1-1957, Safety Code for Conveyors, Cableways, and Related Equipment.

AERIAL LIFTS - §1926.556

General Requirements

Unless otherwise provided in this section, aerial lifts acquired for use on or after the effective date of this section shall be designed and constructed in conformance with the applicable requirements of the American National Standards for Vehicle Mounted Elevating and Rotating Work Platforms, ANSI A92.2-1969, including appendix. Aerial lifts acquired before the effective date of this section, which do not meet the requirements of ANSI A92.2-1969, may not be used unless they have been modified so as to conform with the applicable design and construction requirements of ANSI A92.2-1969. Aerial lifts include the following types of vehicle-mounted aerial devices used to elevate personnel to job-sites above ground: (i) Extensible boom platforms; (ii) aerial ladders; (iii) articulating boom platforms; (iv) vertical towers; and (v) a combination of any of the above. Aerial equipment may be made of metal, wood, fiberglass reinforced plastic (FRP), or other material; may be powered or manually operated; and are deemed to be aerial lifts whether or not they are capable of rotating about a substantially vertical axis.

Aerial lifts may be "field modified" for uses other than those intended by the manufacturer provided the modification has been certified in writing by the manufacturer or by any other equivalent entity, such as a nationally recognized testing laboratory, to be in conformity with all applicable provisions of ANSI A92.2-1969 and this section and to be at least as safe as the equipment was before modification.

Specific Requirements

Ladder Trucks and Tower Trucks

Aerial ladders shall be secured in the lower traveling position by the locking device on top of the truck cab, and the manually operated device at the base of the ladder before the truck is moved for highway travel.

Extensible and Articulating Boom Platforms

Lift controls shall be tested each day prior to use to determine that such controls are in safe working condition.

Only authorized persons shall operate an aerial lift.

Belting off to an adjacent pole, structure, or equipment while working from an aerial lift shall not be permitted.

Employees shall always stand firmly on the floor of the basket, and shall not sit or climb on the edge of the basket or use planks, ladders, or other devices for a work position.

A body belt shall be worn and a lanyard attached to the boom or basket when working from an aerial lift.

Boom and basket load limits specified by the manufacturer shall not be exceeded.

The brakes shall be set and when outriggers are used, they shall be positioned on pads or a solid surface. Wheel chocks shall be installed before using an aerial lift on an incline, provided they can be safely installed.

An aerial lift truck shall not be moved when the boom is elevated in a working position with men in the basket, except for equipment which is specifically designed for this type of operation in accordance with the provisions of paragraph "General Requirements" of this section.

Articulating boom and extensible boom platforms, primarily designed as personnel carriers, shall have both platform (upper) and lower controls. Upper controls shall be in or beside the platform within easy reach of the operator. Lower controls shall provide for overriding the upper controls. Controls shall be plainly marked as to their function. Lower level controls shall not be operated unless permission has been obtained from the employee in the lift, except in case of emergency.

Climbers shall not be worn while performing work from an aerial lift.

The insulated portion of an aerial lift shall not be altered in any manner that might reduce its insulating value.

Before moving an aerial lift for travel, the boom(s) shall be inspected to see that it is properly cradled and outriggers are in stowed position except as provided in paragraph (b)(2)(viii) of this section.

Electrical Tests

All electrical tests shall conform to the requirements of ANSI A92.2-1969 section 5. However, equivalent d.c. voltage tests may be used in lieu of the a.c. voltage specified in A92.2-1969; d.c. voltage tests which are approved by the equipment manufacturer or equivalent entity shall be considered an equivalent test for the purpose of this paragraph.

Bursting Safety Factor

The provisions of the American National Standards Institute standard ANSI A92.2-1969, section 4.9 Bursting Safety Factor shall apply to all critical hydraulic and pneumatic components. Critical components are those in which a failure would result in a free fall or free rotation of the boom. All noncritical components shall have a bursting safety factor of at least 2 to 1.

Welding Standards

All welding shall conform to the following standards as applicable:

  • Standard Qualification Procedure, AWS B3.0-41.
  • Recommended Practices for Automotive Welding Design, AWS D8.4-61.
  • Standard Qualification of Welding Procedures and Welders for Piping and Tubing, AWS D10.9-69.
  • Specifications for Welding Highway and Railway Bridges, AWS D2.0-69.