UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C. 20555 March 8, 1993 NRC INFORMATION NOTICE 93-17: SAFETY SYSTEMS RESPONSE TO LOSS OF COOLANT AND LOSS OF OFFSITE POWER Addressees All holders of operating licenses or construction permits for nuclear power reactors. Purpose The U. S. Nuclear Regulatory Commission (NRC) is issuing this information notice to alert addressees to a condition in which automatic safety systems could have responded inappropriately to certain sequences of loss of coolant and loss of offsite power. It is expected that recipients will review the information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice are not NRC requirements; therefore, no specific action or written response is required. Description of Circumstances In a report of May 1, 1989, the Virginia Electric Power Company, the licensee for the Surry Power Station, reported a deficiency in the emergency diesel generator (EDG) loading logic that could have resulted in overloading the EDGs if a loss of offsite power had occurred after a loss of coolant accident (LOCA) or other design basis event causing the automatic start of the safety system electrical loads. The loading logic was not designed properly to respond to this sequence of events. During recent work on the Improved Standard Technical Specification program and through discussion with nuclear steam supply system owners groups, the NRC has determined that licensees may have similar design logic problems at other plants. The logic at these plants may have been designed to respond properly to a simultaneous LOCA and loss of offsite power but may not have been designed to respond appropriately to other sequences. Discussion General Design Criteria 17 (GDC 17) of Appendix A to Part 50 of Title 10 of the Code of Federal Regulations requires that, following a loss of offsite power, the onsite power system be sufficient to ensure that the core is cooled and containment integrity and other vital functions are maintained in the 9303020536. IN 93-17 March 8, 1993 Page 2 of 3 event of postulated accidents. Licensees typically include an analysis in Chapter 15 of the plant Safety Analysis Report for a simultaneous occurrence of a loss of offsite power and a LOCA. However, licensees may not always analyze for other possible sequences. Thus, the safety systems in some plants may have been designed to respond properly if these events occurred alone or if they occurred simultaneously, but not for other possible sequences. A LOCA with a delayed loss of offsite power may occur in various ways. In one scenario, the LOCA results in a turbine trip and a loss of power generation to the grid causing grid instability and a loss of offsite power seconds later. In another scenario, the loss of power generation causes a degraded voltage at the plant switchyard, which causes the degraded voltage relays to actuate, resulting in a delayed loss of offsite power to the safety buses. In plants where the safety buses are normally fed from the unit auxiliary transformer connected to the output of the main generator, the loss of offsite power could result from a failure of the buses to transfer to the offsite source after the LOCA, or a failure of the offsite transformer to carry the additional load. In such events, offsite power will be lost to the safety buses during the sequencing of the LOCA loads (if LOCA loads are designed to be sequenced on offsite power) or shortly thereafter. The control logic and piping systems (safety injection, service water, etc.) at some plants may not be designed to meet the consequences of such events. Possible adverse results include the failure to reenergize loads required to respond to a LOCA, improper loading and loss of the diesel generators, and water hammer in the piping systems. The opposite sequence is a loss of offsite power followed by a delayed LOCA. One way in which this sequence could occur is if, after the loss of power occurred, a safety relief valve lifted and failed to properly reseat resulting in a loss of reactor coolant inventory and a LOCA initiation signal. Properly designed safety systems will respond appropriately to all credible sequences of a loss of offsite power and LOCA. The design of the control logic, the electrical power and control systems, and the fluid systems all contribute to ensuring that safety systems respond appropriately to these events. . IN 93-17 March 8, 1993 Page 3 of 3 This information notice requires no specific action or written response. If you have any questions about the information in this notice, please contact the technical contact listed below or the appropriate Office of Nuclear Reactor Regulation (NRR) project manager. ORIGINAL SIGNED BY Brian K. Grimes, Director Division of Operating Reactor Support Office of Nuclear Reactor Regulation Technical contact: James Lazevnick, NRR (301) 504-2782 Attachment: List of Recently Issued NRC Information Notices .
Page Last Reviewed/Updated Thursday, March 29, 2012