Texas Department of Licensing and Regulation

Boilers and Boiler Safety

Vacancies on Board of Boiler Rules

The Texas Department of Licensing and Regulation (Department) announces two vacancies on the Board of Boiler Rules (Board) established by Texas Health and Safety Code, Chapter 755.  The pertinent rules may be found in 16 Texas Administrative Code §65.65.  The purpose of the Board of Boiler Rules is to advise the Texas Commission of Licensing and Regulation (Commission) in the adoption of definitions and rules relating to the safe construction, installation, inspection, operating limits, alteration, and repair of boilers and their appurtenances. 

The Board is composed of eleven members appointed by the presiding officer of the Commission, with the Commission’s approval.  The Board consists of three members representing persons who own or use boilers in this state; three members representing companies that insure boilers in this state; one member representing boiler manufacturers or installers; one member representing organizations that repair or alter boilers in this state; one member representing a labor union and two public members. Members serve staggered six-year terms, with the terms of three members expiring January 31 of each odd-numbered year.  This announcement is for the public member positions.

Public Member Frequently Asked Questions

Interested persons should request an application from the Texas Department of Licensing and Regulation by telephone (512) 475‑4765, FAX (512) 475‑2874 or Email advisory.boards@license.state.tx.us. Applicants for public board member should download the Public Member Application; applicants for the other board positions should download the Board of Boiler Rules Application.

Applicants may be asked to appear for an interview; however, any required travel for an interview would be at the applicant's expense.

Amendments to Boiler Administrative Rules effective January 1, 2008

At their meeting held December 11, 2007, the Texas Commission of Licensing and Regulation adopted amendments to the administrative rules regarding the boiler program inspection fees.  Based on the Department’s annual fee review conducted pursuant to Texas Occupations Code, §51.202, the Commission voted at its meeting on September 21, 2007 to increase inspection fees in the boilers program because the inspection fees currently in place were below the amount required by the Department to cover costs.  The increase would not adversely affect the administration and enforcement of the boilers program. 

The adopted amended rule is 16 Texas Administrative Code, Chapter 65, §65.80.  The rule adoption was filed with the Texas Register on December 12, 2007, and will be published in the December 28, 2007, issue of the Texas Register.  The effective date of the rule adoption is January 1, 2008.

TDLR encourages all persons interested in the boilers program to review the rule adoption.

BOILER STACKS AND CHIMNEYS
Reprinted Courtesy of the National Board of Boiler and Pressure Vessel Inspectors

Any boiler using a combustible fuel source requires a stack or chimney. The stack or chimney aids combustion in natural draft boilers by helping to ensure a steady supply of combustion air which mixes with the fuel. The primary purpose of a stack or chimney, though, is to exhaust the products of combustion at some elevation above the boiler which aids the environmental conditions in the immediate area around the boiler. The height of the stack or chimney is determined by several factors including:

  • height of the nearest building or roof line
  • prevailing wind direction
  • height of surrounding manmade structures or natural landforms
  • location of air intake vents
  • type of boiler draft (natural or fan assisted)
  • type of fuel
  • local and/or national requirements

Stacks and chimneys should be designed by a competent engineer who will address all of the necessary factors for the specific application, including any jurisdictional (local, state or provincial, and national) requirements.

Stacks and chimneys should be inspected periodically by a reputable and competent person familiar with stack and chimney design and construction. Jurisdictional requirements may specify who is allowed to make these inspections. Stacks and chimneys deteriorate with age and are very susceptible to seismic or wind damage due to their height.

During a stack or chimney inspection, the following items, as a minimum, should be observed:

  • the stack/chimney base or foundation
  • external supports or guy wires, if used
  • connection to the breeching or boiler
  • condition of bricks and mortar joints in masonry stacks/chimneys
  • condition of metal and joints in metallic stacks/chimneys
  • condition of cap, cone, or spark arrestor, if used, at the top of the stack/chimney
  • the height and diameter of the stack/chimney based upon the original design
  • vertical orientation (is it plumb?)
  • condition of brick or metallic liner in masonry stacks/chimneys
  • condition of interior metal and joints in a double-wall metallic stack/chimney
  • the internal passageway (no obstructions or blockage)

Note: The above list is not intended to be exhaustive, but is provided as a basic guide.

If repairs to a stack or chimney are required, the owner should be directed to contact the authority having jurisdiction over the stack/chimney to determine if a permit or other documentation is necessary. This jurisdictional authority may be local (city), state or provincial, or national. Two examples of this are:

  • the stack of a small gas-fired boiler may be within the jurisdiction of the city building or mechanical inspection department, or
  • the stack of a large sawdust-fired industrial boiler may be within the jurisdiction of the state or provincial environmental protection department.

Recovering Boiler Systems After a Flood

Floods, whether caused by nature or by structural or mechanical failures, can produce deaths, injuries, and severe property damage. The following information is provided to assist in the recovery of boiler systems affected by flooding to help mitigate further risks to public safety and property damage.

  • Safety of the personnel performing inspections and repairs is the highest priority. Because flood waters contain many hazardous chemicals and bacteria, personnel safety procedures should be developed and enforced.
  • All utilities in the boiler room should be turned off until inspection and necessary repairs of the individual systems allow reactivation.
  • A careful visual inspection of the entire boiler system should be made, both internally and externally, with notations of obvious problems and any special equipment or personnel needed to facilitate repairs.
  • Keep in mind that some equipment may only be repaired by the original manufacturer or its licensed agents in order to maintain warranties and/or certification.
  • The boiler setting or foundation should be examined closely to determine if it has been weakened or undermined. Any movement of the boiler or building will have an adverse effect on piping and other equipment connected to both the boiler and building structure.
  • Waterlogged insulation will hasten external corrosion of boilers and pipes. If removal is deemed necessary, remember that asbestos is still present in many boiler rooms and requires handling by specially licensed personnel. If the insulation is left in place and the boiler is fired before thoroughly drying, steam can be generated within the insulation layers, creating the potential for explosive damage to the external lagging.
  • Refractory and fire brick should be checked for deterioration or loosening.
  • Feedwater and condensate return systems should be thoroughly cleaned of any mud, silt, or debris. After the boiler is put back in operation, the water quality should be checked often for contamination of any kind.
  • Pressure relief devices should be checked for corrosion or any damage that would cause binding and failure to operate. Only qualified personnel should perform disassembly or repair of a pressure relief device. Some jurisdictions require this work to be performed by a company holding the National Board "VR" symbol stamp. The outlet and discharge line of the pressure-relieving device should be inspected for blockage.
  • All drains and blow-off lines should be inspected to ensure there is no blockage by debris.
  • Electric/electronic controls should be evaluated for replacement or repair as needed. Flame safeguard controls, ignition transformers, and safety shutoff valves on the fuel system that have the potential for causing furnace explosions should be replaced. Other fuel system components should be drained and cleaned or replaced as necessary. All work performed on the fuel system and safety devices must comply with jurisdictional requirements.
  • All electric motors and wiring should be inspected closely to determine if repair or replacement is necessary. All electrical work must comply with jurisdictional requirements.
  • Check to make sure air inlets are clear and chimneys or stacks are open.

These items are not intended to be all-inclusive, as boiler systems and equipment vary in design and operation. However, this list could be used as an outline in developing individual inspection and repair guidelines to fit many systems affected by flooding.

(Reprinted courtesy of the National Board of Boiler and Pressure Vessel Inspectors)

The Texas Commission on Licensing and Regulation on April 11 unanimously reappointed three individuals to seats on the Texas Department of Licensing and Regulation’s (TDLR) Board of Boiler Rules. The new terms expire January 31, 2011

  • Luther Bailey of Lubbock was reappointed to a seat designated for organizations that repair or alter boilers.
  • Donald A. Thain of Houston was reappointed to a seat designated for a boiler owner/operator.
  • Richard D. West II of Crosby was reappointed to a seat designated for a representative from the insurance industry.

The board advises the Commission in the adoption of definitions and rules relating to the safe construction, installation, inspection, operating limits, alteration, and repair of boilers and their appurtenances. Appointments to the board are made by Commission Chairman Leo Vasquez of Houston with the approval of the Commission.

HISTORY

The Texas Boiler Law, Chapter 755 of the Health and Safety Code, was enacted on June 3, 1937, after a fatal boiler accident.

For many years the program was a part of the agency then known as The Bureau of Labor Statistics. Later, the agency name was changed to the Texas Department of Labor and Standards. In 1989, the name was changed to and is currently named The Texas Department of Licensing and Regulation, where the Boiler Program continues to function and work with an ever changing commercial and industrial environment.

PURPOSE STATEMENT

The Boiler Program’s mission is to provide technical analysis, expertise in all areas of the program for the safety and well being of the citizens, properties and industries in the State of Texas.

WHAT IS A BOILER?

Equipment that falls within the scope of the Texas Boiler Law and Rules, that must be registered and inspected, is defined in both the law and rules. This means all types of boilers that are used in commercial and public facilities that produce steam (either low or high pressure), hot water heating for use in comfort air heating systems, and hot water supply for use in domestic water systems (such as showers, sinks, pools, or for miscellaneous use) which includes potable hot water heater type boilers. Boilers used for hot water supply or potable hot water supply can be further defined in the following two (2) categories:

  • A hot water supply boiler means a boiler designed for operation at a pressure not exceeding 160 psig or temperatures not exceeding 250 degrees Fahrenheit at or near the boiler outlet if the boiler’s: heat input exceeds 200,000 BTUs per hour; water temperature exceeds 210 degrees Fahrenheit; or nominal water-containing capacity exceeds 120 gallons.
  • A potable water heater means a boiler designed for operation at pressures not exceeding 160 psig and water temperatures not exceeding 210 degrees Fahrenheit if the boiler’s: heat input exceeds 200,000 BTUs per hour or nominal water-containing capacity exceeds 120 gallons.

Further classification and definitions can be obtained by accessing the Texas Boiler Law and Rules and referring to the definitions in both the law and rules or by calling (800) 722-7843 and a technical representative can assist you with any questions.

CAUSES OF BOILER ACCIDENTS

Boiler systems are designed for safety and efficiency. The boiler operator is the key to safe boiler operations. Having knowledge about boiler systems and maintenance can ensure years of safe, reliable service.

History has shown that without proper operation and maintenance, boiler conditions and safety deteriorate causing potential hazards due to neglect and misunderstanding. Routine maintenance is well within the ability of most boiler operators. Boiler tune up and repairs, however, are best left to trained professionals. Understanding when to turn to qualified professionals for assistance is one of the operator’s responsibilities and can save time and money. Some of the areas where trained professionals are needed are:

  • Leaking safety and or safety relief valves
  • Feed water to boiler
  • Steam leaks (steam systems)
  • High stack temperatures (excess of 350ºF)
  • Insufficient heat for building
  • Condensate dripping down stack or out the front of the boiler
  • Constantly resetting of controllers and safety devices

Boiler accidents can occur when the boiler is allowed to operate without adequate water in the boiler. Proper functioning low water cutoffs are essential to prevent these types of accidents. Boiler damage can run from severe buckling and deforming of the boiler to complete meltdown or potential boiler explosions.

Another type of boiler accident and the most lethal is excessive pressure. These accidents occur when the boiler can no longer contain the excessive pressure allowed to build in the boiler. Excessive pressure accidents, even in small boilers, have been known to completely destroy a building.

Fuel related accidents usually occur when there is a failure to purge combustible gases from the firebox before ignition is attempted. Leaking fuel valves can also be the cause of these accidents. If the operator notices any gas odor, the boiler should be shut down and the fuel supplier notified immediately.

“Never bypass safety devices with jumper wires to restart your boiler. Unintended ignition of unburned combustion gases in the fire box is possible.”

BOILER WATER TREATMENT

Boiler system (steam/water) loses water through steam and water leaks. Additional water called “make-up water” is added to the boiler to replace these losses. The amount of make-up water and the level of naturally occurring impurities in water will determine the type of water treatment required. Boiler heating systems that have very few leaks will require a simple water treatment program. Your boiler water treatment professional can assist you in developing an effective water treatment program.

All water contains dissolved minerals and these minerals, if allowed to reach high enough levels in the boiler water, will come out of solutions and form as a hard shell on the hot surfaces of the boiler. This hard shell is called “scale” and is often found on the outside of the fire tubes or the inside of water tubes. Scale insulates the heating surfaces reducing the ability of the fire tubes to transfer heat from the hot combustion to the boiler water. High stack temperatures or ruptured tubes are common problems related to scale build up. Boiler water also contains dissolved gases such as oxygen or carbon dioxide. These gases, in the presence of water and metal, can cause corrosion. Corrosion eats away the metal affecting the durability of the boiler.

WHY BOILER INSPECTIONS?

Much like your automobile, furnace, or air conditioner, a boiler requires an ongoing, routine maintenance and inspection program. Well trained maintenance personnel, boiler operators and boiler inspectors are important components to the safe operation of a boiler.

Routine boiler inspections are required by the Texas Boiler Law and Rules. The State and Authorized Inspection Agencies provide trained personnel throughout the state to perform the required inspections to be in compliance with the Texas Boiler Law and Rules.

A boiler should be examined internally and externally to determine the operating condition of the boiler and to ascertain the true condition of the boiler.

Boiler inspectors examine the structural integrity of the boiler along with the associated safety devices attached to the boiler. These devices must remain in good operating condition for the continued safe operation of the boiler.

The loss of water (low water), furnace explosion, over pressure and excessive temperature are the principal causes for boiler accidents and are primarily the direct result of the missing or inoperative controls and safety devices, lack of maintenance, untrained operators, and complacency. These are some reasons why boiler inspections are so important and what could result if boilers are left uninspected.

PROGRAM RESPONSIBILITIES

The Texas Boiler Law requires that all boilers operating in the State of Texas be registered with the department and, depending on the use, be inspected annually, biennially, or triennially. Additionally, department representatives review quality control systems for issuance of Certificates of Authorization to boiler and pressure vessel manufacturers, repair organizations, and state owner/user organizations.

AREA OF RESPONSIBILITY

Throughout the State of Texas there are approximately 60,000 registered boilers. Our records indicate that approximately 60 percent of these registered boilers are under inspection agreements and are inspected by Authorized Inspection Agency inspectors; and the remaining 40 percent of boilers are inspected by state deputy inspectors.

The following are the five (5) regional areas of responsibility for state deputy inspectors, and two (2) of the major regions (91 & 94) are further subdivided between state deputy inspectors by zip codes and counties. To find out which state deputy inspector is for your area you can contact either a regional office or the Department for further assistance at (800) 722-7843.

Region 91- Ft. Worth Office
Telephone (817) 321-8350 or (800) 687-4102

  • Don Jones
  • Jim Jake Templin
  • Jon Seibel
  • (Vacant)

Region 91 – Flint
Telephone (817) 321-8362

  • Clayton Poole

Region 92 – Lubbock
Telephone (817) 321-8359

  • Toby Wetzel

Region 95 – El Paso
Telephone (817) 321-8360

  • Adam Reyes

Region 94 – Houston Office
Telephone (713) 924-6300

  • Lyle Shotts
  • Mike Spurling
  • Salvador Guzman

Region 93 – San Antonio Office
Telephone (210) 281-0333

  • Manuel Del Bosque

Region 93 – Austin Office
Telephone (512) 936-4394

  • Tim Larrew

For Further Assistance  

For more information about boilers contact:

Texas Department of Licensing and Regulation
Boiler Program
P.O. Box 12157
Austin, Texas 78711

(800) 722-7843 (In Texas Only)
(512) 539-5707
(512) 539-5687 (fax)

For more information about the Boiler Safety program, e-mail TDLR at boilers@license.state.tx.us.