[Code of Federal Regulations]
[Title 46, Volume 7]
[Revised as of October 1, 2002]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR176.810]

[Page 221-222]
 
                           TITLE 46--SHIPPING
 
    CHAPTER I--COAST GUARD, DEPARTMENT OF TRANSPORTATION (CONTINUED)
 
PART 176--INSPECTION AND CERTIFICATION--Table of Contents
 
                     Subpart H--Material Inspections
 
Sec. 176.810  Fire protection.

    (a) At each initial and subsequent inspection for certification, the 
owner or managing operator shall be prepared to conduct tests and have 
the vessel ready for inspection of its fire protection equipment, 
including the following:
    (1) Inspection of each hand portable fire extinguisher, semiportable 
fire extinguisher, and fixed gas fire extinguishing system to check for 
excessive corrosion and general condition;
    (2) Inspection of piping, controls, and valves, and the inspection 
and testing of alarms and ventilation shutdowns, for each fixed gas fire 
extinguishing system and detecting system to determine that the system 
is in operating condition;
    (3) Operation of the fire main system and checking of the pressure 
at the most remote and highest outlets;
    (4) Testing of each fire hose to a test pressure equivalent to its 
maximum service pressure;
    (5) Checking of each cylinder containing compressed gas to ensure it 
has been tested and marked in accordance with Sec. 147.60 in subchapter 
N of this chapter;
    (6) Testing or renewal of flexible connections and discharge hoses 
on semiportable extinguishers and fixed gas extinguishing systems in 
accordance with Sec. 147.65 in subchapter N of this chapter; and
    (7) Inspection and testing of all smoke and fire detection systems, 
including sensors and alarms.
    (b) The owner, managing operator, or a qualified servicing facility 
as applicable shall conduct the following inspections and tests:
    (1) For portable fire extinguishers, the inspections, maintenance 
procedures, and hydrostatic pressure tests required by Chapter 4 of NFPA 
10, ``Portable Fire Extinguishers,'' with the frequency specified by 
NFPA 10. In addition, carbon dioxide and Halon portable fire 
extinguishers must be refilled when the net content weight loss exceeds 
that specified for fixed systems

[[Page 222]]

by Table 176.810(b). The owner or managing operator shall provide 
satisfactory evidence of the required servicing to the marine inspector. 
If any of the equipment or records have not been properly maintained, a 
qualified servicing facility must be required to perform the required 
inspections, maintenance procedures, and hydrostatic pressure tests. A 
tag issued by a qualified servicing organization, and attached to each 
extinguisher, may be accepted as evidence that the necessary maintenance 
procedures have been conducted.
    (2) For semiportable and fixed gas fire extinguishing systems, the 
inspections and tests required by Table 176.810(b), in addition to the 
tests required by Secs. 147.60 and 147.65 in subchapter N of this 
chapter. The owner or managing operator shall provide satisfactory 
evidence of the required servicing to the marine inspector. If any of 
the equipment or records have not been properly maintained, a qualified 
servicing facility may be required to perform the required inspections, 
maintenance procedures, and hydrostatic pressure tests.

   Table 176.810(b)--Semiportable and Fixed Fire Extinguishing Systems
------------------------------------------------------------------------
            Type System                             Test
------------------------------------------------------------------------
Carbon dioxide....................  Weigh cylinders. Recharge if weight
                                     loss exceeds 10% of weight of
                                     charge. Test time delays, alarms,
                                     and ventilation shutdowns with
                                     carbon dioxide, nitrogen, or other
                                     nonflammable gas as stated in the
                                     system manufacturer's instruction
                                     manual. Inspect hoses and nozzles
                                     to be sure they are clean.
Halon.............................  Weigh cylinders. Recharge if weight
                                     loss exceeds 5% of weight of
                                     charge. If the system has a
                                     pressure gauge, also recharge if
                                     pressure loss (adjusted for
                                     temperature) exceeds 10%. Test time
                                     delays, alarms and ventilation
                                     shutdowns with carbon dioxide,
                                     nitrogen, or other nonflammable gas
                                     as stated in the system
                                     manufacturer's instruction manual.
                                     Inspect hoses and nozzles to be
                                     sure they are clean.
Dry Chemical (cartridge operated).  Examine pressure cartridge and
                                     replace if end is punctured or if
                                     determined to have leaked or to be
                                     in unsuitable condition. Inspect
                                     hose and nozzle to see if they are
                                     clear. Insert charged cartridge.
                                     Ensure dry chemical is free flowing
                                     (not caked) and extinguisher
                                     contains full charge.
Dry chemical (stored pressure)....  See that pressure gauge is in
                                     operating range. If not, or if the
                                     seal is broken, weigh or otherwise
                                     determined that extinguisher is
                                     fully charged with dry chemical.
                                     Recharge if pressure is low or if
                                     dry chemical is needed.
Foam (stored pressure)............  See that pressure gauge, if so
                                     equipped, is in the operating
                                     range. If not, or if the seal is
                                     broken, weigh or otherwise
                                     determine that extinguisher is
                                     fully charged with foam. Recharge
                                     if pressure is low or if foam is
                                     needed. Replace premixed agent
                                     every 3 years.
Clean Agents (Halon replacements).  (To be developed)
------------------------------------------------------------------------

    (c) The owner, managing operator, or master shall destroy, in the 
presence of the marine inspector, each fire hose found to be defective 
and incapable of repair.
    (d) At each initial and subsequent inspection for certification, the 
marine inspector may require that a fire drill be held under simulated 
emergency conditions to be specified by the inspector.

[CGD 85-080, 61 FR 953, Jan. 10, 1996; 61 FR 20557, May 7, 1996, as 
amended at 62 FR 51356, Sept. 30, 1997]