Do not use equipment and tools powered by gasoline engines inside buildings or other partially enclosed spaces unless the gasoline engine can be placed outdoors and away from air intakes.
PREFACE
This ALERT is the joint product of a combined effort among the
following agencies:
The National Institute for Occupational Safety and Health
(NIOSH)
The Colorado Department of Public Health and Environment (CDPHE)
The U.S. Consumer Product Safety Commission (CPSC)
The Occupational Safety and Health Administration (OSHA)
The U.S. Environmental Protection Agency (EPA)
Each agency has a unique role in protecting workers, consumers,
or the general public from safety and health hazards. Because
of their common interest in prevention of carbon monoxide (CO)
poisonings resulting from widespread use of small gasoline-powered
engines and tools in enclosed or confined spaces, the agencies
elected to work together to produce a joint document to address
this problem and provide recommendations for prevention. Such
a combined effort avoids duplication and confusion from multiple
documents and promotes efficient use of government resources.
ACKNOWLEDGMENTS
Principal contributors to the development of this joint ALERT
include:
Janet J. Ehlers, Jane B. McCammon, Dennis O'Brien, G. Scott
Earnest, R. Leroy Mickelsen, Mary L. Woebkenberg, and Jerome P.
Flesch (NIOSH)
Allison Hawkes and Lyle McKenzie (CDPHE)
Elizabeth Leland (CPSC)
Edward Stein (OSHA)
Richard Leukroth and John Girman (EPA)
Preventing Carbon Monoxide Poisoning from
Small Gasoline-Powered Engines and Tools
Hundreds of people performing many different tasks have been poisoned
because small gasoline-powered engines and tools produced hazardous
concentrations of carbon monoxide (CO) even in relatively open
buildings:
In December 1992, a farm owner found his 12-year-old son unconscious
near the door of a swine-farrowing building (birthing barn) in
Iowa. The boy had been working alone using an 11-horsepower, gasoline-powered
pressure washer for about half an hour to clean the building.
In January 1993, a 33-year-old farm owner in Iowa died of
carbon monoxide poisoning while using an 11-horsepower, gasoline-powered
pressure washer to clean his swine-farrowing barn. He had worked
about half an hour before being overcome.
In January 1993, a 60-year-old drywall finisher in Colorado
collapsed and fell from the scaffold on which he was standing.
He was using a small gasoline-powered compressor to apply a textured
surface to a cathedral ceiling in a house. Although he landed
on a balcony below, escaping further injury, he was confused and
unable to identify an escape route from the building. He was rescued
by coworkers who saw him beckoning for help at the patio door.
In February 1993, a 30-year-old plumber in Colorado developed
a severe headache and dizziness and began to demonstrate paranoid
behavior that was later diagnosed as CO poisoning. He had worked
for 2 to 3 hours using a gasoline-powered concrete cutter to access
pipes in a basement. He and his supervisor anticipated possible
problems related to the exhaust from this equipment and had set
up what they considered to be adequate ventilation (they opened
doors and windows and placed cooling fans near the cutter and
farther down the hall).
In June 1994, five workers in Washington, D.C., who experienced
dizziness, confusion, headaches, and nervousness were treated
for CO poisoning after using two 8-horsepower, gasoline-powered
pressure washers for 4 hours in an empty, poorly ventilated underground
parking garage. When one of the five workers collapsed at the
worksite, coworkers carried him outside, remained with him for
a short time, and then, unaware of the hazard, re-entered the
hazardous worksite. Only after a second worker collapsed did workers
recognize the hazard, evacuate the environment, and seek help.
In October 1994, a 37-year-old municipal employee at an indoor
water treatment facility in Colorado lost consciousness while
trying to exit from a 59,000-cubic-foot room where he had been
working with an 8-horsepower, gasoline-powered water pump for
4 hours.
In December 1994, a previously healthy 59-year-old owner/operator
of a flooring installation business in Colorado experienced headache
and dizziness after working for 21/2 hours in the stairwell
of a building containing a gasoline-powered generator supplying
power to the construction site. He left the building and rested
in his car. Upon returning to the stairwell, he collapsed in a
grand mal seizure related to CO poisoning.
These are examples of the many situations in which people have
been poisoned because they did not recognize the danger of using
small gasoline-powered engines indoors. These poisonings can occur
quickly, even in the presence of what many would consider "adequate
ventilation" and in areas that many would define as relatively
open spaces, such as parking garages.
HEALTH EFFECTS
CO is a lethal poison that is produced when fuels such as gasoline
are burned. It is one of many chemicals found in engine exhaust
and can rapidly accumulate even in areas that might appear to
be well ventilated. Because CO is colorless, tasteless, odorless,
and nonirritating, it can overcome the exposed person without
warning. It produces weakness and confusion, depriving the person
of the ability to seek safety.
CO poisons primarily by tightly binding to hemoglobin in the blood
(forming carboxyhemoglobin), replacing oxygen, and reducing the
oxygen-carrying capacity of the blood. CO may also poison by binding
to tissues and cells of the human body and interfering with their
normal function. Persons with pre-existing heart disease are at
increased risk. Fetuses of pregnant women are also at increased
risk-especially when mothers are exposed to high CO levels. Recognizing
early warning signs of CO poisoning is sometimes difficult because
early symptoms of CO exposure (headache, dizziness, and nausea)
are nonspecific and may be mistaken for symptoms of other illnesses
such as colds, flu, or food poisoning. Confusion and weakness
can inhibit a person's ability to escape the hazardous environment.
The severity of symptoms of CO exposure is influenced by three
main factors: (1) the concentration of CO in the environment;
(2) how long the exposure lasts, and (3) work-load and breathing
rate. In general, assuming that users of gasoline-powered engines
are engaged in at least a moderate level of activity, exposure
to CO concentrations of 80 to100 parts per million (ppm) for 1
to 2 hours can result in decreased exercise tolerance and, in
persons who are at risk, may bring on chest pain and cause irregular
heartbeat [EPA 1991a]. Symptoms associated with CO exposure concentrations
of 100 to 200 ppm include headache, nausea, and mental impairment.
More serious central nervous system effects, coma, and death are
associated with CO exposure concentrations of 700 ppm or greater
for an hour or more [Ilano and Raffin 1990; Forbes et al. 1945].
Symptoms of nervous system effects include staggering, confusion,
changes in personality, and muscle aches. These symptoms may continue
to occur for several days to several weeks after the exposure
stops and the poisoned person has apparently recovered. Victims
of CO poisoning should be immediately removed from the exposure
site and given 100% oxygen. Hyperbaric chambers provide oxygen
under pressure and are sometimes necessary in cases of serious
CO poisoning.
CURRENT STANDARDS AND RECOMMENDED GUIDELINES
Organizations set standards or make recommendations for exposure
to hazardous substances based on assumptions inherent to their
regulatory oversight or authority. Differences in the stated
values reflect variations in the place, duration, characteristics
of the population, or proposed use.
Workplace/Industry
The current Occupational Safety and Health Administration (OSHA)
permissible exposure limit (PEL) for CO is 50 ppm as an 8-hour
time-weighted average (TWA) [29 CFR 1910.1000*]. The NIOSH recommended
exposure limit (REL) for CO is 35 ppm as an 8-hour TWA and a ceiling
limit (CL) of 200 ppm [NIOSH 1992]. The NIOSH recommended immediately
dangerous to life and health concentration (IDLH) for CO is 1,200
ppm. The IDLH is the concentration that could result in death
or irreversible health effects, or prevent escape from the contaminated
environment within 30 minutes. The American Conference of Governmental
Industrial Hygienists (ACGIH) has adopted a threshold limit value
(TLV) for CO of 25 ppm as an 8-hour TWA [ACGIH 1992a].
-------------------
**Code of Federal Regulations. See CFR in references.
Ambient Air/Residential Settings
The U.S. Environmental Protection Agency (EPA) has established
an ambient (outdoor) CO air quality Federal standard of 9 ppm
for an 8-hour exposure and 25 ppm for a short-term (1-hr) exposure
[EPA 1991a]. The Consumer Product Safety Commission (CPSC) staff
recommends that long-term exposures to CO in indoor environments
be limited to less than 15 ppm as an 8-hour TWA and 25 ppm for
1 hour, but product-specific recommendations for CO may vary depending
on expected usage patterns and exposure.
DATA SUMMARIZING CO POISONINGS
Illness related to CO exposure is probably underestimated because
workers with mild symptoms may go untreated or medical providers
may not recognize their symptoms as CO poisoning. In addition,
persons may not recognize the cause of their symptoms unless coworkers
and other persons become ill at the same time.
Two surveys assessing individuals' beliefs, knowledge, and risk
perceptions regarding CO suggest that many people are unaware
of the hazards associated with CO. In 1993, NIOSH assessed flood
victims' risk perceptions associated with CO poisoning from using
equipment powered by small engines (e.g., gasoline-powered pressure
washers indoors to clean up flood-related debris) [Greife et al.
1995]. Many of the 416 respondents (26%) incorrectly believed
that with only a window open, the use of a gasoline-powered engine
indoors would be safe. A majority of respondents (54%) and 92%
of respondents between the ages of 12 and 20, incorrectly believed
that it was safe to operate a gasoline-powered engine indoors
with windows and doors open and an exhaust fan running. In a second
survey, during follow-up investigations of nonfatal, unintentional
CO poisoning in residential settings in Connecticut between November
1993 and March 1994, investigators interviewed 36 victims or their
adult representatives [CDC 1995b]. Many of the victims of CO poisoning
(poisoning that was related to heating systems, gas appliances,
and fireplaces) still demonstrated a lack of knowledge about prevention
strategies. When asked to list prevention methods, 14% were unable
to list any method, 44% listed appropriate maintenance of appliances,
39% listed the use of a CO detector, and 14% listed proper ventilation.
Reports from a number of sources show that CO poisoning from the
use of gasoline-powered tools indoors happens frequently:
Occupational Health Nurses in Agricultural Communities
(OHNAC): The NIOSH-sponsored (OHNAC) Surveillance Program
identified 18 cases of CO poisoning related to the use of small
engines; 17 cases occurred in less than 3 years [CDC 1993; Ehlers
1994]. Although only one case resulted in a fatality, at least
three cases could have been fatal had the victims not been found
by coworkers or family members, removed from the hazardous environment,
and taken for medical care. At least four were overcome in about
half an hour. Persons working in open environments (e.g., doors
and windows open and exhaust fans operating) began developing
symptoms in as little as 1 hour of constant work or as many as
7 hours of intermittent exposure. All interviewed persons reported
being unaware that they could be poisoned in a short time and
that CO can attain hazardous levels inside buildings with windows
and doors open. Several victims, although appearing obviously
confused and ill to family members at the worksite, were unaware
of their impaired condition and sought medical help only at the
insistence of family members. Seven of the 18 incidents occurred
among Iowa farmers using pressure washers to clean animal housing
between January 1992 and March 1994. Of the other 11 cases, 7
occurred while using pressure washers to clean animal housing
elsewhere or in other years, and 4 occurred while using gasoline-powered
pressure washers or concrete saws to clean up after floods.
Colorado Department of Public Health and Environment (CDPHE):
In Colorado, 40% (135) of all work-related CO poisonings reported
to CDPHE since 1985 have been related to the use of gasoline-powered
equipment [CDPHE 1996]. Other sources of exposure associated with
reported occupational poisonings in Colorado include automobile
exhaust (25% of poisonings) and furnaces (12%). Seventeen of the
135 workers poisoned by gasoline-powered equipment lost consciousness
during their exposures to emissions, and 2 workers died. The 135
poisonings were primarily caused by concrete-cutting saws (28
workers), power trowels (15 workers), high-pressure washers (14
workers), compressors (10 workers), welding equipment (9 workers),
and floor buffers (9 workers). Other equipment causing poisonings
included jackhammers, pumps, carpet cleaners, and paint sprayers.
Information about where the 135 poisoned workers were using gasoline-powered
equipment was available in 115 cases; 110 (96%) of these 115 poisonings
occurred indoors.
George Washington University (GWU): Seven worker poisonings
related to the emissions from gasoline-powered tools used indoors
have also been identified by the GWU Emergency Department Surveillance
Project. Five of these poisonings occurred in June 1994 and were
discussed above (workers using a pressure washer in an empty underground
parking garage) [CDC 1995a]. Two additional workers were poisoned
while using gasoline-powered saws.
California: A study of all death certificates in the
State of California during the 10-year period from 1979 to 1988
showed 444 deaths due to unintentional carbon monoxide poisoning
[CDHS 1993]. Of these deaths, 23 (5%) were caused by small engine
exhaust.
National Estimates: There is no complete U.S. database
for this problem. According to the U.S. Bureau of Labor Statistics
(BLS), there were nearly 900 work-related CO poisonings resulting
in death or illness in private industry in the United States in
1992 (32 deaths and 867 nonfatal poisonings) [BLS 1992a,b]. CPSC
estimates that in 1992 (the latest year for which mortality data
are available), there were 212 deaths from CO associated with
the use of household fuel-burning appliances. Thirteen of these
deaths were reported to have involved the use of gasoline-powered
appliances [NCHS/CPSC 1992]. In 1994 (the latest year for which
injury data are available), CPSC estimates that 3,900 CO injury
incidents occurred in which an average of two to three persons
per incident were treated in hospital emergency rooms. Of these
3,900 incidents, approximately 400 incidents were associated with
the use of gasoline-powered appliances [CPSC 1994].
ENVIRONMENTAL MEASUREMENTS AND MODELING DOCUMENT RAPID CO
BUILDUP
Three of the above groups measured CO concentrations after the
CO poisoning incidents in the same or similar exposure situations
to estimate how quickly dangerous CO concentrations developed.
A fourth group modeled the time to reach dangerous CO concentrations.
OHNAC: NIOSH measured the generation of CO by a gasoline-powered
pressure washer using a 5.5-horsepower engine under environmental
conditions comparable with those experienced by the farmers using
pressure washers described in this report [Venable et al.
1995]. A 5.5-horsepower, gasoline-powered pressure washer was
operated inside an 8,360-cubic-foot, double-car garage using two
ventilation scenarios. In the first or "worst-case"
scenario, all doors, windows, and vents were closed. Breathing-zone
concentrations of CO reached 200 ppm within 5 minutes, 1,200 ppm
(IDLH value) within 15 minutes, and 1,500 ppm within 19 minutes;
they continued to increase thereafter. In the second or "best-case"
scenario, the two double-car garage doors and one window were
left open and the vent was unsealed; breathing-zone concentrations
of CO reached 200 ppm within 3 minutes and peaked at 658 ppm within
12 minutes. The results from the simulations indicate that acutely
toxic concentrations of CO greater than 200 ppm (NIOSH ceiling)
can be quickly generated within 3 to 5 minutes near a pressure
washer operated indoors (even when passive ventilation is provided),
and IDLH concentrations of 1,200 ppm can be generated rapidly
in enclosed spaces.
CDPHE: The CDPHE measured or recreated exposures in
four poisonings related to the use of gasoline-powered tools indoors
[CDPHE 1996].
First, CDPHE attempted to estimate the CO exposure of the
drywall texturizer discussed earlier by sampling the air at another
construction site where he was doing similar work. On the day
of the air sampling, the gasoline-powered compressor was placed
just outside the garage door. Because of the way the equipment
was designed and oriented, exhaust from the engine on the compressor
went directly into the house when the garage door was open. As
is usual for this operation, all windows and external doors in
the home had been closed and sealed with tape and paper to protect
the surfaces from the texturing material and to maintain the proper
conditions for drying. The concentration of CO at the tailpipe
of the compressor engine was substantially greater than 1,000
ppm (this was the upper limit of the testing equipment). Within
the first 20 minutes of the operation, CO concentrations as high
as 410 ppm were measured in the basement of the home, and concentrations
as high as 322 ppm were measured where the worker was standing.
CDPHE asked the worker to open the windows and external doors
on the upper floor of the duplex because of concerns about this
concentration of exposure. CO concentrations within the house
dropped to approximately 30 ppm when that was done, but this is
not the way the process is usually carried out.
In response to the second incident (another CO poisoning related
to the use of an 8-horsepower pressure washer in a 30,000-cubic-foot
room of a municipal construction project), CDPHE asked to run
the same pressure washer in the same room a few days later. There
was no mechanical ventilation in this room because the facility
was not yet operational. The pressure washer was placed approximately
15 feet from one corner of the room (the same place the worker
had placed it on the day of the poisoning). The power unit was
an integral part of the washer. Again, the CO concentration at
the engine exhaust pipe was greater than 1,000 ppm, the highest
concentration CDPHE could measure at the time. CDPHE measured
CO concentrations as high as 450 ppm at several locations in the
room within 20 minutes of activation of the washer engine, and
concentrations as high as 546 ppm approximately 50 minutes after
the washer engine was activated. The test was then terminated.
In a third incident, CDPHE asked the managers of the enclosed
municipal water treatment plant to recreate the exposure situation
encountered by the worker mentioned before who was using the 8-horsepower
pump in the 59,000-cubic-foot room (48 × 88 × 14 feet).
This room was only partially enclosed so that employees could
observe operations in the room from the level above. Outside air
was introduced into the area through a forced-air heating system
that was running on the day of the poisoning and on the day of
air sampling. External doors to the treatment plant were opened
on both days as well. Ten minutes after the pump engine was started,
CO concentrations as high as 395 ppm were measured within 7 feet
of the pump, near the location where the employee was standing
for much of the time on the day of the poisoning. CO concentrations
25 feet from the water pump rose to as high as 193 ppm during
the 20-minute test. CDPHE returned to the room 1 hour after the
water pump was stopped and measured 40 ppm of CO.
Finally, in January 1996, two Colorado workers were poisoned
as a result of operating a gasoline-powered, 5-horsepower, walk-behind
concrete saw during a remodeling project. The machine was 3 years
old and was used two to three times per year. The workers operated
the saw for about an hour and a half inside what had previously
been two bathrooms (the dividing wall had been removed and the
volume of the room was 2,332 cubic feet). The workers were cutting
a hole in the floor to allow access to pipes below the floor.
The two doors to the room were open and the bathroom ventilation
system was operating when these poisonings occurred. The day after
the poisonings occurred, the work in this bathroom was continued
with two differences: A cooling fan was used this time in an effort
to better move CO from the room, and the saw was operated for
shorter periods (the periods of operation were not clearly defined
but were thought to be 15 to 30 minutes). CDPHE recreated the
second day's operating conditions to measure CO concentrations
in the room. The NIOSH ceiling limit of 200 ppm was exceeded within
the first minute of operation. Within 5 minutes of operation,
the CO concentration within the room reached 842 ppm, at which
point the demonstration was discontinued (see Figure 1).
Figure 1. Actual CO concentrations measured inside a 2,332-cubic-foot
bathroom with a gasoline-powered, 5-horsepower concrete saw operating
(doors open, cooling fan and ventilation running).
GWU: In the poisoning incident in which five workers
were using pressure washers in an underground garage, the fire
department measured 648 ppm CO 1 hour after the washers had been
turned off (washers had been running for 3 hours).
NIOSH: NIOSH engineers modeled the time required for
a gasoline-powered, 5-horsepower, 4-cycle engine to reach the
200-ppm (ceiling) and 1,200-ppm IDLH CO concentration for room
sizes of 1,000 to 100,000 cubic feet and general ventilation rates
of 1 to 20 air changes per hour [ACGIH 1992b]. The CO generation
rate used in the model was 670 grams/horsepower-hour based on
data from a 1991 EPA study [EPA 1991b]. Ideal mixing was assumed.
Under actual conditions, if mixing were poor, hazardous concentrations
could develop more quickly. In the small 1,000-cubic-foot room,
the ceiling concentration of 200 ppm was reached in approximately
0.1 minute, and the IDLH was reached in less than 1 minute at
all air flow rates. In the medium 10,000-cubic-foot room, the
IDLH was reached in approximately 7 minutes for 1 air change per
hour and approximately 10 minutes for 5 air changes per hour.
These models demonstrate that for rooms up to 10,000 cubic feet,
the NIOSH ceiling limit of 200 ppm was exceeded in less than 2
minutes--even with general ventilation rates as high as 20 air
changes per hour. In no case would it be possible to operate an
engine for 8 hours without exceeding the NIOSH REL of 35 ppm.
(see Figures 2 through 4).
Figure 2. Calculated CO concentrations generated by a 5-horsepower,
4-cycle gasoline-powered engine in a 1,000-cubic-foot room with
various air changes per hour.
Figure 3. Calculated CO concentrations generated by a 5-horsepower,
4-cycle gasoline-powered engine in a 10,000-cubic-foot room with
various air changes per hour.
Figure 4. Calculated CO concentrations generated by a 5-horsepower,
4-cycle gasoline-powered engine in a 100,000-cubic-foot room with
various air changes per hour.
RECOMMENDATIONS
It is not widely known that small gasoline-powered engines and
tools present a serious health hazard. They produce high concentrations
of carbon monoxide, a poisonous gas that can cause illness, permanent
neurological damage, and death. Because it is colorless, odorless,
and nonirritating, CO can overcome exposed persons without warning.
Often there is little time before they experience symptoms that
inhibit their ability to seek safety. Prior use of equipment without
incident has sometimes given users a false sense of safety; such
users have been poisoned on subsequent occasions. Recommendations
for preventing CO poisoning are provided below for employers,
equipment users, tool rental agencies, and tool manufacturers.
All Employers and Equipment Users Should:
NOT allow the use or operation of gasoline-powered
engines or tools inside buildings or in partially enclosed areas
unless gasoline engines can be located outside and away from air
intakes. Use of gasoline-powered tools indoors where CO from the
engine can accumulate can be fatal.
An exception to this rule might be an emergency rescue situation
in which other options are not available; such an exception should
be made only when equipment operators, assisting personnel, and
the victim are provided with supplied-air respirators.
Learn to recognize the signs and symptoms of CO overexposure:
headache, nausea, weakness, dizziness, visual disturbances, changes
in personality, and loss of consciousness. Any of these signs
and symptoms can occur within minutes after the equipment is turned
on.
Always place the pump and power unit of high-pressure washers
outdoors and away from air intakes so that engine exhaust is not
drawn indoors where the work is being done. Run only the high-pressure
wash line inside.
Consider the use of tools powered by electricity or compressed
air if they are available and can be used safely. For example,
electric-powered tools present an electrocution hazard and require
specific precautions for safety.
If compressed air is used, place the gasoline-powered compressor
outdoors away from air intakes so that engine exhaust is not drawn
indoors where the work is being done.
Use personal CO monitors where potential sources of CO exist.
These monitors should be equipped with audible alarms to warn
workers when CO concentrations are too high. More information
on CO monitors is contained in the appendix.
Employers Should Also:
Conduct a workplace survey to identify all potential sources
of CO exposure.
Educate workers about the sources and conditions that may
result in CO poisoning as well as the symptoms and control of
CO exposure.
Always substitute less hazardous equipment if possible. Use
equipment that allows for the placement of gasoline-powered engines
outdoors at a safe distance from air entering the building.
Monitor employee CO exposure to determine the extent of the
hazard.
Equipment Users Should Also:
Substitute less hazardous equipment whenever possible. Use
electric tools or tools with engines that are separate from the
tools and can be located outside and away from air intakes.
Learn to recognize the warning symptoms of CO poisoning.
If you have any symptoms, immediately turn off equipment and
go outdoors or to a place with uncontaminated air.
Call 911 or another local emergency number for medical attention
or assistance if symptoms occur. Do NOT drive a motor vehicle--get
someone else to drive you to a health care facility.
Stay away from the work area until the tool has been deactivated
and measured CO concentrations are below accepted guidelines and
standards.
Watch coworkers for the signs of CO toxicity.
Tool Rental Agencies Should:
Place warning labels on gasoline-powered tools. For example:
WARNING--CARBON MONOXIDE PRODUCED DURING USE CAN KILL--DO NOT
USE INDOORS OR IN OTHER SHELTERED AREAS.
Tell renters that the tool should NOT be used indoors and
explain why.
Recommend safer tools for the intended use if available.
Have portable, audible CO monitors for rent and encourage
their use.
Provide renters with educational materials like this information
sheet.
Tool Manufacturers Should:
Design tools that can be used safely indoors.
Provide warning labels for existing and new gasoline-powered
equipment. For example:
WARNING--CARBON MONOXIDE PRODUCED DURING USE CAN KILL--DO NOT
USE INDOORS OR IN OTHER SHELTERED AREAS.
Provide recommendations for equipment maintenance to reduce
CO emissions.
Recommend the use of portable, audible CO monitors with small
gasoline- powered engines.
DISTRIBUTION
NIOSH, CDPHE, CPSC, OSHA, and EPA request that the information
in this ALERT be brought to the attention of (1) all employers
and workers who use small gasoline-powered engines and tools in
their jobs and trades (e.g., building, construction, agriculture,
and maintenance and cleaning operations), (2) tool rental agencies
and equipment sellers and users, (3) tool manufacturers, and (4)
editors of appropriate trade journals.
REFERENCES
ACGIH [1992a]. 1992-1993 threshold limit values for chemical substances
and physical agents and biological exposure indices. Cincinnati,
OH: American Conference of Governmental Industrial Hygienists.
ACGIH [1992b]. Industrial ventilation--a manual of recommended
practice. 21st ed. Cincinnati, OH: American Conference of Governmental
Industrial Hygienists, Committee on Industrial Ventilation, pp.
2-1 to 2-16.
BLS [1992a]. Census of fatal occupational injuries. Washington,
DC: U.S. Department of Labor, Bureau of Labor Statistics. Unpublished
data.
BLS [1992b]. Survey of occupational injuries and illnesses. Washington,
DC: U.S. Department of Labor, Bureau of Labor Statistics. Unpublished
data.
CDC (Centers for Disease Control and Prevention) [1993]. Unintentional
carbon monoxide poisoning from indoor use of pressure washers--Iowa,
January 1992-January 1993. MMWR 42(40):777-779, 785.
CDC (Centers for Disease Control and Prevention) [1995a]. Carbon
monoxide poisoning from use of gasoline-fueled powered washers
in an underground parking garage--District of Columbia, 1994.
MMWR 44(18):356-357, 363-364.
CDC (Centers for Disease Control and Prevention) [1995b]. Unintentional
carbon monoxide poisonings in residential settings--Connecticut,
November 1993-March 1994. MMWR 44(41):765-767.
CDHS [1993]. Causes of unintentional deaths from carbon monoxide
poisonings in California. Sacramento, CA: California Health Services
Department.
CDPHE [1996]. Occupational carbon monoxide poisonings in Colorado.
Denver, CO: Colorado Department of Public Health and Environment.
Unpublished data.
CFR. Code of Federal regulations. Washington, DC: U.S. Government
Printing Office, Office of the Federal Register.
Ehlers J [1994]. Carbon monoxide poisoning among Iowa farmers
while using gasoline-powered washers--a case series. Cincinnati,
OH: U.S. Department of Health and Human Services, Public Health
Service, Centers for Disease Control and Prevention, National
Institute for Occupational Safety and Health. Unpublished report.
EPA [1991a]. Air quality criteria for carbon monoxide. Washington,
DC: U.S. Environmental Protection Agency, Office of Research and
Development, Publication No. EPA-600/8-90/045F.
EPA [1991b]. Nonroad engine and vehicle emission study-report.
Washington, DC: U.S. Environmental Protection Agency, Office of
Air and Radiation, Publication No. EPA 21A-2001.
Forbes WH, Sargent F, Foughton FJW [1945]. The rate of CO uptake
by normal man. Am J Physiol 143:594-608.
Greife A, Goldenhar LM, Freund E, Stock A, Hornung R, Connon C,
et al [1995]. Risk perception of carbon monoxide poisoning from
gasoline-powered engines among midwest flood victims. Cincinnati,
OH: U.S. Department of Health and Human Services, Public Health
Service, Centers for Disease Control and Prevention, National
Institute for Occupational Safety and Health. Unpublished report.
Ilano A, Raffin T [1990]. Management of carbon monoxide poisoning.
Chest 97:165-169.
NCHS/CPSC [1992]. Death certificate file. Atlanta, GA: U.S. Department
of Health and Human Services, Public Health Service, Centers for
Disease Control and Prevention, National Center for Health Statistics;
and U.S. Consumer Product Safety Commission.
NIOSH [1992]. NIOSH recommendations for occupational safety and
health: compendium of policy documents and statements. Cincinnati,
OH: U.S. Department of Health and Human Services, Public Health
Service, Centers for Disease Control and Prevention, National
Institute for Occupational Safety and Health, DHHS (NIOSH) Publication
No. 92-100.
Venable H, Wallingford K, Roberts D, Booher D [1995]. Simulated
carbon monoxide exposure in an enclosed structure from a gasoline-powered
pressure washer. Appl Occup Environ Hyg 10(7):581-584.
APPENDIX
Carbon Monoxide Monitors and Detectors
Detectors for carbon monoxide (CO) are manufactured and marketed
for use in either the home or occupational industrial settings.
The detectors for home use are devices that will sound an alarm
before CO concentrations in the home become hazardous. There is
an Underwriters Laboratories, Inc., performance standard (UL 2034)
for residential CO detectors. Detectors currently available on
the market are battery-powered, plug-in, or hard-wired. Some models
incorporate a visual display of the parts per million (ppm ) concentration
of CO present in the home. For more information on CO detectors
for home use, call the Consumer Product Safety Commission Hotline
at 1-800-638-2772.
CO detectors for use in residential settings are not designed
for use in typical workplace settings. Monitoring requirements
in an occupational setting are different from monitoring requirements
in the home. In the workplace, it is frequently necessary to monitor
a worker's exposure to carbon monoxide over an entire work shift
and determine the time-weighted average (TWA) concentration of
the exposure. It may also be necessary to have carbon monoxide
monitors with alarm capabilities in the workplace. CO in the workplace
can be detected using detector tubes, direct-reading passive badges,
dosimeter tubes and direct-reading instruments. These badges,
tubes, and instruments operate on a variety of principles including
colorimetric reaction, potentiometry, coulometry, infrared spectrometry,
fluorescence, thermal conductivity, and heat of combustion. The
direct-reading instruments are frequently equipped with audio
and/or visual alarms and may be used for area and/or personal
exposure monitoring. Some have microprocessors and memory for
storing CO concentration readings taken during the day. It is
significant to note that some of the devices mentioned for workplace
CO monitoring are not capable of monitoring TWAs, and not all
are equipped with alarms. The appropriate monitor must be chosen
on an application-by-application basis. For more information on
the availability of workplace CO monitors or their application,
call the National Institute for Occupational Safety and Health
at 1-800-35-NIOSH (1-800-356-4674).
Mention of any company or product does not constitute endorsement
by the National Institute for Occupational Safety and Health,
the Colorado Department of Public Health and Environment, the
U.S. Consumer Product Safety Commission, the Occupational Safety
and Health Administration, or the U.S. Environmental Protection
Agency.