[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2006] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR118.420] [Page 358-359] TITLE 46_SHIPPING (This book contains parts 90 to 139) CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 118_FIRE PROTECTION EQUIPMENT--Table of Contents Subpart D_Fixed Fire Extinguishing and Detecting Systems Sec. 118.420 Pre-engineered fixed gas fire extinguishing systems. (a) A pre-engineered fixed gas fire extinguishing system must: (1) Be approved by the Commandant; (2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector; [[Page 359]] (3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protection space; and (4) Be installed in accordance with manufacturer's instructions. (b) A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station: (1) A light to indicate discharge; (2) An audible alarm that sounds upon discharge; and (3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section. (c) Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.