[Code of Federal Regulations]

[Title 46, Volume 4]

[Revised as of October 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 46CFR118.410]



[Page 355-358]

 

                            TITLE 46_SHIPPING



                  (This book contains parts 90 to 139)

 

   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)

 

PART 118_FIRE PROTECTION EQUIPMENT--Table of Contents

 

        Subpart D_Fixed Fire Extinguishing and Detecting Systems

 

Sec.  118.410  Fixed gas fire extinguishing systems.



    (a) General. (1) A fixed gas fire extinguishing system aboard a 

vessel must be approved by the Commandant, and be custom engineered to 

meet the requirements of this section unless the system meets the 

requirements of Sec.  118.420 of this part.

    (2) System components must be listed and labeled by an independent 

laboratory. A component from a different system, even if from the same 

manufacturer, must not be used unless included in the approval of the 

installed system.

    (3) System design and installation must be in accordance with the 

Marine Design, Installation, Operation, and Maintenance Manual approved 

for the system by the Commandant.

    (4) A fixed gas fire extinguishing system may protect more than one 

space. The quantity of extinguishing agent must be at least sufficient 

for the space requiring the greatest quantity as determined by the 

requirements of paragraphs (f)(4) or (g)(2) of this section.

    (b) Controls. (1) Controls and valves for operation of a fixed gas 

fire extinguishing system must be:

    (i) Located outside the space protected by the system; and

    (ii) Not located in a space that might be inaccessible in the event 

of fire in the space protected by the system.

    (2) Except for a normally unoccupied space of less than 170 cubic 

meters (6000 cubic feet), release of an extinguishing agent into a space 

must require two distinct operations.

    (3) A system must have local manual controls at the storage 

cylinders capable of releasing the extinguishing agent. In addition, a 

normally manned space must have remote controls for releasing the 

extinguishing agent immediately outside the primary exit from the space.

    (4) Remote controls must be located in a breakglass enclosure to 

preclude accidental discharge.

    (5) Valves and controls must be of a type approved by the Commandant 

and protected from damage or accidental activation. A pull cable used to 

activate the system controls must be enclosed in conduit.

    (6) A system protecting more than one space must have a manifold 

with a normally closed stop valve for each space protected.

    (7) A gas actuated valve or device must be capable of manual 

override at the valve or device.

    (8) A system, which has more than one storage cylinder for the 

extinguishing agent and that relies on pilot cylinders to activate the 

primary storage cylinders, must have at least two pilot cylinders. Local 

manual controls in compliance with paragraph (b)(3) of this section must 

be provided to operate the pilot cylinders but are not required for the 

primary storage cylinders.

    (9) A system protecting a manned space must be fitted with a time 

delay and alarm of a type approved by the Commandant, arranged to 

require the alarm to sound for at least 20 seconds or the time necessary 

to escape from the space, whichever is greater, before the agent is 

released into the space. Alarms must be conspicuously and centrally 

located. The alarm must be powered by the extinguishing agent.

    (10) A device must be provided to automatically shut down power 

ventilation serving the protected space and engines that draw intake air 

from the protected space prior to release of the extinguishing agent 

into the space.

    (11) Controls and storage cylinders must not be in a locked space 

unless the key is in a breakglass type box conspicuously located 

adjacent to the space.

    (c) Storage space. (1) Except as provided in paragraph (c)(2) of 

this section, a storage cylinder for a fixed gas extinguishing system 

must be:

    (i) Located outside the space protected by the system; and

    (ii) Not located in a space that might be inaccessible in the event 

of a fire in the space protected by the system.

    (2) A normally unoccupied space of less than 170 cubic meters (6,000 

cubic feet) may have the storage cylinders located within the space 

protected.



[[Page 356]]



When the storage cylinders are located in the space:

    (i) The system must be capable of automatic operation by a heat 

actuator within the space; and

    (ii) Have manual controls in compliance with paragraph (b) of this 

section except for paragraph (b)(3) of this section.

    (3) A space containing a storage cylinder must be maintained at a 

temperature within the range from -30[deg] C (-20[deg] F) to 55[deg] C 

(130[deg] F) or at another temperature as listed by the independent 

laboratory and stated in the manufacturer's approval manual.

    (4) A storage cylinder must be securely fastened, supported, and 

protected against damage.

    (5) A storage cylinder must be accessible and capable of easy 

removal for recharging and inspection. Provisions must be available for 

weighing each storage cylinder in place.

    (6) Where subject to moisture, a storage cylinder must be installed 

to provide a space of at least 51 millimeters (2 inches) between the 

deck and the bottom of the storage cylinder.

    (7) A Halon 1301 storage cylinder must be stowed in an upright 

position unless otherwise listed by the independent laboratory. A carbon 

dioxide cylinder may be inclined not more than 30[deg] from the 

vertical, unless fitted with flexible or bent siphon tubes, in which 

case they may be inclined not more than 80[deg] from the vertical.

    (8) Where a check valve is not fitted on an independent storage 

cylinder discharge outlet, a plug or cap must be provided for closing 

the outlet resulting from storage cylinder removal.

    (9) Each storage cylinder must meet the requirements of Sec.  147.60 

in subchapter N of this chapter, or other standard specified by the 

Commandant.

    (10) A storage cylinder space must have doors that open outwards or 

be fitted with kickout panels installed in each door.

    (d) Piping. (1) A pipe, valve, or fitting of ferrous material must 

be protected inside and outside against corrosion unless otherwise 

approved by the Commandant. Aluminum or other low melting material must 

not be used for a component of a fixed gas fire extinguishing system 

except as specifically approved by the Commandant.

    (2) A distribution line must extend at least 51 millimeters (2 

inches) beyond the last orifice and be closed with a cap or plug.

    (3) Piping, valves, and fittings must be securely supported, and 

where necessary, protected against damage.

    (4) Drains and dirt traps must be fitted where necessary to prevent 

the accumulation of dirt or moisture and located in accessible 

locations.

    (5) Piping must be used for no other purpose except that it may be 

incorporated with the fire detecting system.

    (6) Piping passing through accommodation spaces must not be fitted 

with drains or other openings within such spaces.

    (7) The distribution piping of a carbon dioxide fixed gas 

extinguishing system must be tested as required by this paragraph, upon 

completion of the piping installation, using only carbon dioxide, 

compressed air, or nitrogen gas.

    (i) Piping between a storage cylinder and a stop valve in the 

manifold must be subjected to a pressure of 6,894 kPa (1,000 psi), 

except as permitted in paragraph (d)(7)(iii) of this section. Without 

additional gas being introduced to the system, the pressure drop must 

not exceed 2,068 kPa (300 psi) after two minutes.

    (ii) A distribution line to a space protected by the system must be 

subjected to a test similar to that described in paragraph (d)(7)(i) of 

this section, except that the pressure used must be 4,136 kPa (600 psi). 

For the purpose of this test, the distribution piping must be capped 

within the space protected at the first joint between the nozzles and 

the storage cylinders.

    (iii) A small independent system protecting a space such as a paint 

locker may be tested by blowing out the piping with air at a pressure of 

not less than 689 kPa (100 psi).

    (8) The distribution piping of a Halon 1301 fixed gas extinguishing 

system must be tested, as required by this paragraph, upon completion of 

the piping installation, using only carbon dioxide, compressed air, or 

nitrogen.

    (i) When pressurizing the piping, pressure must be increased in 

small increments. Each joint must be subjected



[[Page 357]]



to a soap bubble leak test, and all joints must be leak free.

    (ii) Piping between the storage cylinders and the manifold stop 

valve must be subjected to a leak test conducted as a pressure of 4,136 

kPa (600 psi). Without additional gas being added to the system, there 

must be no loss of pressure over a two minute period after thermal 

equilibrium is reached.

    (iii) Distribution piping between the manifold stop valve and the 

first nozzle in the system must be capped and pneumatically tested for a 

period of 10 minutes at 1,034 kPa (150 psi). At the end of 10 minutes, 

the pressure drop must not exceed 10% of the test pressure.

    (e) Pressure relief. When required by the cognizant OCMI, spaces 

that are protected by a fixed gas fire extinguishing system and that are 

relatively airtight, such as refrigeration spaces, paint lockers, etc., 

must be provided with suitable means for relieving excessive pressure 

within the space when the agent is released.

    (f) Specific requirements for carbon dioxide systems. A custom 

engineered fixed gas fire extinguishing system, which uses carbon 

dioxide as the extinguishing agent, must meet the requirements of this 

paragraph.

    (1) Piping, valves, and fittings must have a bursting pressure of 

not less than 41,360 kPa (6,000 psi). Piping, in nominal sizes of not 

more than 19 millimeters (0.75 inches), must be at least Schedule 40 

(standard weight), and in nominal sizes of over 19 millimeter (0.75 

inches), must be at least Schedule 80 (extra heavy).

    (2) A pressure relief valve or equivalent set to relieve at between 

16,550 and 19,300 kPa (2,400 and 2,800 psi) must be installed in the 

distribution manifold to protect the piping from overpressurization.

    (3) Nozzles must be approved by the Commandant.

    (4) When installed in a machinery space, paint locker, a space 

containing flammable liquid stores, or a space with a fuel tank, a fixed 

carbon dioxide system must meet the following requirements.

    (i) The quantity of carbon dioxide in kilograms (pounds) that the 

system must be capable of providing to a space must not be less than the 

gross volume of the space divided by the appropriate factor given in 

Table 118.410(f)(4)(i). If fuel can drain from a space being protected 

to an adjacent space or if the spaces are not entirely separate, the 

volume of both spaces must be used to determine the quantity of carbon 

dioxide required. The carbon dioxide must be arranged to discharge into 

both such spaces simultaneously.



                         Table 118.410(f)(4)(i)

------------------------------------------------------------------------

                        Gross volume of space in cubic meters (feet)

      Factor       -----------------------------------------------------

                               over                     Not Over

------------------------------------------------------------------------

     0.94 (15)      .........................               14 (500)

      1.0 (16)                   14 (500)                 45 (1,600)

      1.1 (18)                 45 (1,600)                125 (4,500)

      1.2 (20)                125 (4,500)             1,400 (50,000)

      1.4 (22)             1,400 (50,000)      .........................

------------------------------------------------------------------------



    (ii) The minimum size of a branch line to a space must be as noted 

in Table 118.410(f)(4)(ii).



                                             Table 118.410(f)(4)(ii)

----------------------------------------------------------------------------------------------------------------

   Maximum quantity of

 carbon dioxide required  Minimum nominal pipe size mm   Maximum quantity of carbon   Minimum nominal pipe size

        kg (lbs)                    (inches)             dioxide required kg (lbs)           mm (inches)

----------------------------------------------------------------------------------------------------------------

         45.4 (100)                    12.7 (0.5)                 1,134 (2,500)                     65 (2.5)

          102 (225)                     19 (0.75)                 2,018 (4,450)                     75 (3.0)

          136 (300)                      25 (1.0)                 3,220 (7,100)                     90 (3.5)

          272 (600)                     30 (1.25)                4,739 (10,450)                    100 (4.0)

        454 (1,000)                      40 (1.5)                6,802 (15,000)                    113 (4.5)

      1,111 (2,450)                      50 (2.0)       ...........................

----------------------------------------------------------------------------------------------------------------



    (iii) Distribution piping within a space must be proportioned from 

the distribution line to give proper supply to the outlets without 

throttling.

    (iv) The number, type, and location of discharge outlets must 

provide uniform distribution of carbon dioxide throughout a space.



[[Page 358]]



    (v) The total area of all discharge outlets must not exceed 85 

percent nor be less than 35 percent of the nominal cylinder outlet area 

or the area of the supply pipe, whichever is smaller. The nominal 

cylinder outlet area in square millimeters (inches) is determined by 

multiplying the factor 0.015 (0.0022 if using square inches) by the 

total capacity in kilograms (pounds) of all carbon dioxide cylinders in 

the system, except in no case must the outlet area be of less than 71 

square millimeters (0.110 square inches).

    (vi) The discharge of at least 85 percent of the required amount of 

carbon dioxide must be completed within two minutes.

    (5) When installed in an enclosed ventilation system for rotating 

electrical propulsion equipment a fixed carbon dioxide system must meet 

the following requirements.

    (i) The quantity of carbon dioxide in kilograms (pounds) must be 

sufficient for initial and delayed discharges as required by this 

paragraph. The initial discharge must be equal to the gross volume of 

the system divided by 160 (10 if using pounds) for ventilation systems 

having a volume of less than 57 cubic meters (2,000 cubic feet), or 

divided by 192 (12 if using pounds) for ventilation systems having a 

volume of at least 57 cubic meters (2,000 cubic feet). In addition, 

there must be sufficient carbon dioxide available to permit delayed 

discharges to maintain at least a 25 percent concentration until the 

equipment can be stopped. If the initial discharge achieves this 

concentration, a delayed discharge is not required.

    (ii) The piping sizes for the initial discharge must be in 

accordance with Table 118.410(f)(4)(ii) and the discharge of the 

required amount must be completed within two minutes.

    (iii) Piping for the delayed discharge must not be less than 12.7 

millimeters (0.5 inches) nominal pipe size, and need not meet specific 

requirement for discharge rate.

    (iv) Piping for the delayed discharge may be incorporated with the 

initial discharge piping.

    (6) When installed in a cargo space a fixed carbon dioxide system 

must meet the following requirements.

    (i) The number of kilograms (pounds) of carbon dioxide required for 

each space in cubic meters (feet) must be equal to the gross volume of 

the space in cubic meters (feet) divided by 480 (30 if using pounds).

    (ii) System piping must be of at least 19 millimeters (0.75 inches).

    (iii) No specific discharge rate is required.

    (g) Specific requirements for Halon 1301 systems. (1) A custom 

engineered fixed gas fire extinguishing system that uses Halon 1301, 

must comply with the applicable sections of UL 1058 ``Halogenated Agent 

Extinguishing System Units,'' and the requirements of this paragraph.

    (2) The Halon 1301 quantity and discharge requirements of UL 1058 

apply, with the exception that the Halon 1301 design concentration must 

be 6 percent at the lowest ambient temperature expected in the space. If 

the lowest temperature is not known, a temperature of -18[deg] C (0[deg] 

F) must be assumed.

    (3) Each storage cylinder in a system must have the same pressure 

and volume.

    (4) Computer programs used in designing systems must be approved by 

an independent laboratory recognized by the Commandant.



    Note to Sec.  118.410(g): As of Jan. 1, 1994, the United States 

banned the production of Halon. The Environmental Protection Agency 

placed significant restrictions on the servicing and maintenance of 

systems containing Halon. Vessels operating on an international voyage, 

subject to SOLAS requirements, are prohibited from installing fixed gas 

fire extinguishing systems containing Halon.



[CGD 85-080, 61 FR 917, Jan. 10, 1996; 61 FR 20556, May 7, 1996, as 

amended at 62 FR 51351, Sept. 30, 1997; USCG-2000-7790, 65 FR 58462, 

Sept. 29, 2000]