[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2006] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR132.310] [Page 469-470] TITLE 46_SHIPPING (This book contains parts 90 to 139) CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 132_FIRE-PROTECTION EQUIPMENT--Table of Contents Subpart C_Miscellaneous Sec. 132.310 Fixed fire-extinguishing systems for paint lockers. (a) Except as provided by paragraph (b) of this section, a fixed gaseous fire-extinguishing system or another approved fixed fire- extinguishing system must be installed in each paint locker. (b) No fixed fire-extinguishing system need be installed in a paint locker that is-- (1) Less than 1.7 cubic meters (60 cubic feet) in volume; (2) Accessible only from the weather deck; and (3) Not adjacent to a tank for flammable or combustible liquid. (c) Each fixed fire-extinguishing system installed must comply with part 95 [[Page 470]] of this chapter or be approved by the Commanding Officer, Marine Safety Center.