[Code of Federal Regulations]
[Title 40, Volume 8]
[Revised as of July 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 40CFR61.343]

[Page 197-199]
 
                   TITLE 40--PROTECTION OF ENVIRONMENT
 
         CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)
 
PART 61_NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR POLLUTANTS
--Table of Contents
 
   Subpart FF_National Emission Standard for Benzene Waste Operations
 
Sec. 61.343  Standards: Tanks.

    (a) Except as provided in paragraph (b) of this section and in Sec. 
61.351, the owner or operator must meet the standards in paragraph 
(a)(1) or (2) of this section for each tank in which the waste stream is 
placed in accordance with Sec. 61.342 (c)(1)(ii). The standards in this 
section apply to the treatment and storage of the waste stream in a 
tank, including dewatering.
    (1) The owner or operator shall install, operate, and maintain a 
fixed-roof and closed-vent system that routes all organic vapors vented 
from the tank to a control device.
    (i) The fixed-roof shall meet the following requirements:
    (A) The cover and all openings (e.g., access hatches, sampling 
ports, and gauge wells) shall be designed to operate with no detectable 
emissions as indicated by an instrument reading of less than 500 ppmv 
above background, as determined initially and thereafter at least once 
per year by the methods specified in Sec. 61.355(h) of this subpart.
    (B) Each opening shall be maintained in a closed, sealed position 
(e.g., covered by a lid that is gasketed and latched) at all times that 
waste is in the tank except when it is necessary to use the opening for 
waste sampling or removal, or for equipment inspection, maintenance, or 
repair.
    (C) If the cover and closed-vent system operate such that the tank 
is maintained at a pressure less than atmospheric pressure, then 
paragraph (a)(1)(i)(B) of this section does not apply to any opening 
that meets all of thefollowing conditions:
    (1) The purpose of the opening is to provide dilution air to reduce 
the explosion hazard;
    (2) The opening is designed to operate with no detectable emissions 
as indicated by an instrument reading of less than 500 ppmv above 
background, as determined initially and thereafter at least once per 
year by the methods specified in Sec. 61.355(h); and
    (3) The pressure is monitored continuously to ensure that the 
pressure in the tank remains below atmospheric pressure.
    (ii) The closed-vent system and control device shall be designed and 
operated in accordance with the requirements of Sec. 61.349 of this 
subpart.
    (2) The owner or operator must install, operate, and maintain an 
enclosure and closed-vent system that routes all organic vapors vented 
from the tank, located inside the enclosure, to a control device in 
accordance with

[[Page 198]]

the requirements specified in paragraph (e) of this section.
    (b) For a tank that meets all the conditions specified in paragraph 
(b)(1) of this section, the owner or operator may elect to comply with 
paragraph (b)(2) of this section as an alternative to the requirements 
specified in paragraph (a)(1) of this section.
    (1) The waste managed in the tank complying with paragraph (b)(2) of 
this section shall meet all of the following conditions:
    (i) Each waste stream managed in the tank must have a flow-weighted 
annual average water content less than or equal to 10 percent water, on 
a volume basis as total water.
    (ii) The waste managed in the tank either:
    (A) Has a maximum organic vapor pressure less than 5.2 kilopascals 
(kPa) (0.75 pounds per square inch (psi));
    (B) Has a maximum organic vapor pressure less than 27.6 kPa (4.0 
psi) and is managed in a tank having design capacity less than 151 m\3\ 
(40,000 gal); or
    (C) Has a maximum organic vapor pressure less than 76.6 kPa (11.1 
psi) and is managed in a tank having a design capacity less than 75 m\3\ 
(20,000 gal).
    (2) The owner or operator shall install, operate, and maintain a 
fixed roof as specified in paragraph (a)(1)(i).
    (3) For each tank complying with paragraph (b) of this section, one 
or more devices which vent directly to the atmosphere may be used on the 
tank provided each device remains in a closed, sealed position during 
normal operations except when the device needs to open to prevent 
physical damage or permanent deformation of the tank or cover resulting 
from filling or emptying the tank, diurnal temperature changes, 
atmospheric pressure changes or malfunction of the unit in accordance 
with good engineering and safety practices for handling flammable, 
explosive, or other hazardous materials.
    (c) Each fixed-roof, seal, access door, and all other openings shall 
be checked by visual inspection initially and quarterly thereafter to 
ensure that no cracks or gaps occur and that access doors and other 
openings are closed and gasketed properly.
    (d) Except as provided in Sec. 61.350 of this subpart, when a 
broken seal or gasket or other problem is identified, or when detectable 
emissions are measured, first efforts at repair shall be made as soon as 
practicable, but not later than 45 calendar days after identification.
    (e) Each owner or operator who controls air pollutant emissions by 
using an enclosure vented through a closed-vent system to a control 
device must meet the requirements specified in paragraphs (e)(1) through 
(4) of this section.
    (1) The tank must be located inside a total enclosure. The enclosure 
must be designed and operated in accordance with the criteria for a 
permanent total enclosure as specified in ``Procedure T--Criteria for 
and Verification of a Permanent or Temporary Total Enclosure'' in 40 CFR 
52.741, appendix B. The enclosure may have permanent or temporary 
openings to allow worker access; passage of material into or out of the 
enclosure by conveyor, vehicles, or other mechanical means; entry of 
permanent mechanical or electrical equipment; or direct airflow into the 
enclosure. The owner or operator must perform the verification procedure 
for the enclosure as specified in section 5.0 of Procedure T initially 
when the enclosure is first installed and, thereafter, annually. A 
facility that has conducted an initial compliance demonstration and that 
performs annual compliance demonstrations in accordance with the 
requirements for Tank Level 2 control requirements 40 CFR 264.1084(i) or 
40 CFR 265(i) is not required to make repeat demonstrations of initial 
and continuous compliance for the purposes of this subpart.
    (2) The enclosure must be vented through a closed-vent system to a 
control device that is designed and operated in accordance with the 
standards for control devices specified in Sec. 61.349.
    (3) Safety devices, as defined in this subpart, may be installed and 
operated as necessary on any enclosure, closed-vent system, or control 
device used to comply with the requirements of paragraphs (e)(1) and (2) 
of this section.

[[Page 199]]

    (4) The closed-vent system must be designed and operated in 
accordance with the requirements of Sec. 61.349.

[55 FR 8346, Mar. 7, 1990, as amended at 55 FR 18331, May 2, 1990; 58 FR 
3096, Jan. 7, 1993; 67 FR 68532, Nov. 12, 2002; 68 FR 6082, Feb. 6, 
2003; 68 FR 67935, Dec. 4, 2003]