Sec. 111.05-27  Grounded neutral alternating current systems.

    Grounded neutral and high-impedance grounded neutral alternating 
current systems must have a suitably sensitive ground detection system 
which indicates current in the ground connection, is able to withstand 
the maximum available fault current without damage, and provides 
continuous indication of circuit status to ground. A provision must be 
included to compare indications under fault conditions with those under 
normal conditions.