[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2002] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR111.05-23] [Page 217] TITLE 46--SHIPPING CHAPTER I--COAST GUARD, DEPARTMENT OF TRANSPORTATION (CONTINUED) PART 111--ELECTRIC SYSTEMS--GENERAL REQUIREMENTS--Table of Contents Subpart 111.05--Equipment Ground, Ground Detection, and Grounded Systems Sec. 111.05-23 Location of ground indicators. Ground indicators must: (a) Be at the vessel's ship's service generator distribution switchboard for the normal power, normal lighting, and emergency lighting systems; (b) Be at the propulsion switchboard for propulsion systems; and (c) Be readily accessible. (d) Be provided (at the distribution switchboard or at another location, such as a centralized monitoring position for the circuit affected) for each feeder circuit that is isolated from the main source by a transformer or other device. Note to paragraph (d): An alarm contact or indicating device returned to the main switchboard via a control cable, that allows the detecting equipment to remain near the transformer or other isolating device for local troubleshooting, is allowed. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28276, June 4, 1996; 62 FR 23907, May 1, 1997] [[Page 218]]