[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2002] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR112.50-5] [Page 263] TITLE 46--SHIPPING CHAPTER I--COAST GUARD, DEPARTMENT OF TRANSPORTATION (CONTINUED) PART 112--EMERGENCY LIGHTING AND POWER SYSTEMS--Table of Contents Subpart 112.50--Emergency Diesel and Gas Turbine Engine Driven Generator Sets Sec. 112.50-5 Electric starting. An electric starting system must have a starting battery with sufficient capacity for at least six consecutive starts. A second, separate source of starting energy may provide three of the required six starts. If a second source is provided, the electrical starting system need only provide three consecutive starts. [CGD 94-108, 61 FR 28288, June 4, 1996]