[Code of Federal Regulations]
[Title 46, Volume 4]
[Revised as of October 1, 2002]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR105.30-1]

[Page 104]
 
                           TITLE 46--SHIPPING
 
    CHAPTER I--COAST GUARD, DEPARTMENT OF TRANSPORTATION (CONTINUED)
 
PART 105--COMMERCIAL FISHING VESSELS DISPENSING PETROLEUM PRODUCTS--Table of Contents
 
                 Subpart 105.30--Electrical Requirements
 
Sec. 105.30-1  Electrical fittings and fixtures.


    (a) In compartments or areas containing tanks or pumps handling 
other than Grade E petroleum products, no electrical fittings, fixtures, 
nor electrical equipment shall be installed or used unless approved for 
a Class I, Group D hazardous location and so labeled by Underwriter's 
Laboratories, Inc., or other recognized laboratories. (See subpart 
110.10 of subchapter J (Electrical Engineering) of this chapter for 
listings of standards.)
    (b) All electrical equipment, fixtures and fittings within 10 feet 
of a vent outlet or a dispensing outlet shall be explosion proof and 
shall be labeled as explosion proof by Underwriter's Laboratories, Inc., 
or other recognized laboratory, as suitable for Class I, Group D 
atmospheres.