[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2002] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR105.30-1] [Page 104] TITLE 46--SHIPPING CHAPTER I--COAST GUARD, DEPARTMENT OF TRANSPORTATION (CONTINUED) PART 105--COMMERCIAL FISHING VESSELS DISPENSING PETROLEUM PRODUCTS--Table of Contents Subpart 105.30--Electrical Requirements Sec. 105.30-1 Electrical fittings and fixtures. (a) In compartments or areas containing tanks or pumps handling other than Grade E petroleum products, no electrical fittings, fixtures, nor electrical equipment shall be installed or used unless approved for a Class I, Group D hazardous location and so labeled by Underwriter's Laboratories, Inc., or other recognized laboratories. (See subpart 110.10 of subchapter J (Electrical Engineering) of this chapter for listings of standards.) (b) All electrical equipment, fixtures and fittings within 10 feet of a vent outlet or a dispensing outlet shall be explosion proof and shall be labeled as explosion proof by Underwriter's Laboratories, Inc., or other recognized laboratory, as suitable for Class I, Group D atmospheres.