GLOSSARY FOR ELECTRICAL EQUIPMENT
NRITL---- Nationally Recognized Independent Testing Laboratory
Portable Fire Extinguisher
Multipurpose dry chemical with a 2A:10B:C rating, listed or approved by a nationally
recognized independent testing laboratory.
"Attended" for Electrical Equipment has the
following meanings:
In a Primary Escapeway (Attended) means:
- The equipment operator will be on the mobile
equipment or immediately adjacent to the equipment and be capable of
activating the fire suppression system in the event of a fire.
When 75.344 applies to electric-operated compressors (75.344(a)(1)) (Attended) means:
- Continuously attended by a person designated by the operator who can see
the compressor at all times during its operation. Any designated person attending
the compressor must be capable of activating the fire suppression system and deenergizing or
shutting off the compressor in the event of a fire.
When 75.1107 applies (75.1107-1(c)) (Attended) means:
- Any machine or device regularly operated by a
miner assigned to operate such machine or device.
- Any machine or device
in the direct line of sight and located within 500 feet of a jobsite regularly
occupied by a miner assigned to perform job duties at the jobsite during each production shift.
Machines and devices described above must be inspected for fire and the
input powerline deenergized when workmen leave the area for more than 30 minutes.
Program Policy states that to be considered as attended, the equipment be
in line of sight of a miner at least once during a 30-minute period.
Noncombustible structure/area
A structure/area that provides protection against flame spread for at least 1
hour when subjected to a fire test incorporating an ASTM E119-88 time/temperature heat
input or equivalent. The following types of installations are considered to be noncombustible
structures as required by 75.340.
1. Installations that are manufactured as packaged units fully enclosed in a metal housing
--
- Power centers;
- Rectifiers and transformer stations that use
dry-type transformers; or
- Transformers filled with nonflammable fluid or inert gas.
2. Underground battery charging stations --
- that are enclosed in substantial metal housings;
- that are used to charge batteries that are also
enclosed in substantial metal housings; and
- where batteries remain on the machine during charging.
Please return to the Previous Page to continue using the Advisor.
|
|
|