04/20/1992 - Temporary storage carrier for oxygen and acetylene cylinders. |
Standard Interpretations - Table of Contents |
Standard Number: | 1910.253 |
April 20, 1992 Mr. Joseph Anastasi Safety Manager Dover Elevator Company 333 Meadowland Parkway Secaucus, New Jersey 07094-1801 Dear Mr. Anastasi: Thank you for your inquiry of March 12, requesting an interpretation of the Occupational Safety and Health Administration (OSHA) regulation 29 CFR 1910.253(b)(4)(iii), as it pertains to your special temporary storage carrier for oxygen and acetylene cylinders. The heavy gauge metal partition on your proposed, portable carrier does not provide adequate protection of the oxygen cylinder from fire exposure from the other side where the acetylene cylinder is stored. The partition must be configured to prevent the fire from circumventing it. Also, the barrier must be constructed to withstand, without failure, fire exposure as required for a ½-hour fire resistance rating. The fire resistance rating of a fire barrier, including a noncombustible partition described in 1910.253(b)(4)(iii), is determined by testing in accordance with methods such as those described in the National Fire Protection Association (NFPA) Code, NFPA 251, Standard Methods for Fire Tests of building Construction and Materials. Thank you for your interest in occupational safety and health. If we can be of further assistance, please contact us. Sincerely, Patricia K. Clark, Director [Directorate of Enforcement Programs] [Correction 3/9/2004] |
Standard Interpretations - Table of Contents |
Back to Top | www.osha.gov | www.dol.gov |
Contact Us | Freedom of Information Act | Customer Survey Privacy and Security Statement | Disclaimers |
||
Occupational Safety & Health Administration 200 Constitution Avenue, NW Washington, DC 20210 |