ISSUE DATE: January 25, 2006 PROGRAM INFORMATION BULLETIN NO. P06-01 FROM: RAY McKINNEY Administrator for Coal Mine Safety and Health SUBJECT: Compliance with the testing and maintenance requirements of 30 CFR 75.1911(i), Fire suppression systems for diesel-powered equipment and fuel transportation units. Scope This Program Information Bulletin (PIB) affects underground coal mine operators, miners and miners' representatives, Mine Safety and Health Administration (MSHA) enforcement personnel, and other interested parties should have this information. Purpose The purpose of this bulletin is to clarify the basic requirement for underground coal mine operators to test and maintain each fire suppression system installed on diesel-powered equipment and fuel transportation units in accordance with the manufacturer's recommendations as required in 30 CFR § 75.1911(i). The PIB also is intended to promote consistent enforcement of § 75.1911(i). Information MSHA's Section 30 CFR 75.1911 addresses the requirements for installation of fire suppression systems on diesel-powered equipment and fuel transportation units. Section 75.1911(i) reads:
As stated in the preamble discussion to § 75.1911(i), "a person trained to perform the inspection and maintenance on fire suppression systems as required under § 75.1911(i) is not required to be a person qualified under § 75.1915. However, the person performing tests and inspections of fire suppression systems must have sufficient knowledge to determine whether a fire suppression system is functioning properly." 61 FR 55477. "The weekly visual inspection in § 75.1911(i) is not intended to be an in-depth inspection, but a quick check to determine if defects, such as disconnected hose lines or altered nozzles, are readily apparent." 61 FR 55477. It is the responsibility of underground coal mine operators to ensure that fire suppression systems installed on diesel-powered equipment are in compliance with § 75.1911(i). The decision as to whom will perform the mandated inspection and maintenance on such equipment is within the mine operator's discretion. Background A provision within a fire suppression system manufacturer's recommendations restricts and limits the inspection and maintenance of the system to the manufacturer's personnel, authorized distributor personnel, or persons designated by the manufacturer or authorized distributor. However, it appears that neither the manufacturer nor the authorized distributors provide training or designate mine operator's employees to perform the inspections and maintenance of the system. As a result, questions have been raised concerning the interpretation and enforcement of the inspection and maintenance requirements of § 75.1911(i). This bulletin clarifies the compliance responsibilities of underground coal mine operators with § 75.1911(i). Authority Federal Mine Safety and Health Act of 1977; 30 CFR Part 75 Subpart T - Diesel Powered Equipment Issuing Office and Contact Persons Coal Mine Safety and Health Chief, Division of Safety Terry L. Bentley, (202) 693-9521 Bentley.Terry@dol.gov Robert L. Phillips, (202) 693-9532 Division of Safety, Coal Mine Safety and Health Phillips.Robert@dol.gov Monty Christo, (202) 693-9527 Division of Safety, Coal Mine Safety and Health Christo.Monty@dol.gov Internet Availability This Program Information Bulletin may be viewed on the World Wide Web by accessing the MSHA Home Page www.msha.gov and then choosing "Compliance Info." Distribution Coal and All Volume Program Policy Manual Holders Underground Coal Mine Operators Miners' Representatives Special Interest Groups Equipment Manufacturers br> |
Back to Top | www.msha.gov | www.dol.gov |
| ||
---|---|---|
| ||
Mine Safety and Health Administration (MSHA) 1100 Wilson Boulevard, 21st Floor Arlington, VA 22209-3939 |
Phone:
(202) 693-9400 Fax-on-demand: (202) 693-9401 Technical (web) questions: Webmaster On-line Filing Help: MSHAhelpdesk@dol.gov or call (877) 778-6055 Contact Us |