Openings

NFIP Policy Index

Definition/Description:

In A Zones, all new construction and substantial improvements may have fully enclosed areas below the lowest floor that are usable solely for vehicle parking, building access, or storage, in an area other than a basement, which are subject to flooding These enclosed areas must be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing the entry and exit of floodwaters. Designs to meet this requirement must be certified or meet the following criteria:

  1. A minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding,
  2. The bottom of all openings shall be no higher than one foot above grade. Garage doors do not meet the NFIP minimum requirements for openings.