|Power Reactor |Event Number: 37142 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CLINTON REGION: 3 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [1] [] [] STATE: IL |NOTIFICATION TIME: 13:01[EDT]|
| RXTYPE: [1] GE-6 |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 11:05[CDT]|
| NRC NOTIFIED BY: FUNKHOUSER |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |MICHAEL JORDAN R3 |
|10 CFR SECTION: | |
|AMED 50.72(b)(2)(v) OFFSITE MEDICAL | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| POTENTIALLY CONTAMINATED PERSON TRANSPORTED TO THE HOSPITAL |
| |
| "On 7/5/00 at 1105, a potentially contaminated worker was taken offsite by |
| ambulance to John Warner Hospital in Clinton, Illinois. The worker, an |
| Electrician, was working on the Fuel Building bridge on 755' Fuel Building |
| when he passed out. The Electrician was working in a potentially |
| contaminated area. Radiation Protection personnel accompanied the |
| electrician to the hospital but were not able to verify that he was not |
| contaminated at the time he left site to be taken to the hospital. The |
| electrician regained consciousness while on the Fuel Building bridge. At |
| 1132, Radiation Protection personnel frisked the electrician at the hospital |
| and found no contamination on the individual or his clothing. This |
| notification is being made pursuant to 10CFR50.72(b)(2)(v), Offsite |
| Medical." |
| |
| |
| The NRC Resident Inspector was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37143 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COOK REGION: 3 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [1] [2] [] STATE: MI |NOTIFICATION TIME: 13:06[EDT]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 05:32[EDT]|
| NRC NOTIFIED BY: COBB |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |MICHAEL JORDAN R3 |
|10 CFR SECTION: | |
|HFIT 26.73 FITNESS FOR DUTY | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N N 0 Refueling |0 Refueling |
|2 N Y 98 Power Operation |98 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| POSITIVE FOR-CAUSE ALCOHOL TEST |
| |
| A contractor supervisor tested positive for alcohol during a for-cause test |
| upon entering the site. His access was suspended at 0930. |
| |
| The NRC Resident Inspector was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37144 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND REGION: 4 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [1] [] [] STATE: LA |NOTIFICATION TIME: 13:58[EDT]|
| RXTYPE: [1] GE-6 |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 09:20[CDT]|
| NRC NOTIFIED BY: FELTNER |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |DAVID GRAVES R4 |
|10 CFR SECTION: | |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| REACTOR CORE COOLING SYSTEM ISOLATION DURING A SURVEILLANCE |
| |
| "On 7/5/2000 at 0920 CDT, the Reactor Core Isolation Cooling (RCIC) System |
| isolated due to a sensed high steam supply line differential pressure. |
| Instrument technicians were performing required surveillance test |
| STP-207-4248 on Division 1 pressure transmitter, E51-PDTN084A. This |
| surveillance requires the transmitter to be hydraulically isolated from the |
| system in order to perform a calibration and also generates a Division 1 |
| RCIC Isolation signal. |
| |
| Per the plant design, the Division 1 and 2 pressure transmitters share a |
| common sensing line. While removing the Division 1 transmitter from |
| service, the Division 2 transmitter, E51-PDTN084B, spiked high causing a |
| Division 2 RCIC isolation signal and subsequent closure of E51-MOVF063, RCIC |
| Steam Supply Inboard Isolation Valve. |
| |
| Although the RCIC system was inoperable for scheduled maintenance at the |
| time of the Division 2 isolation, the containment isolation function was |
| still in service and considered operable. High Pressure Core Spray and all |
| other ECCS systems remained operable while the RCIC system was isolated. |
| RCIC will be returned to service following the completion of the scheduled |
| maintenance activities. |
| |
| The RCIC System Isolation Instrumentation is designated as an Engineered |
| Safety Features system and this event is therefore reportable in accordance |
| with 10CFR50.72." |
| |
| The NRC Resident Inspector was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37145 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BEAVER VALLEY REGION: 1 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [1] [] [] STATE: PA |NOTIFICATION TIME: 14:17[EDT]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 13:07[EDT]|
| NRC NOTIFIED BY: MUELLER |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |STEVEN DENNIS R1 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(ii) RPS ACTUATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| REACTOR TRIP FROM 100% POWER DUE TO TURBINE TRIP. |
| |
| The plant had a reactor trip from 100% power due to a turbine trip. Cause |
| of the turbine trip is being investigated. All control rods fully inserted |
| and no relief valves lifted or ECCS actuated. The plant is stable in mode 3 |
| with RCS temperature and pressure at 547þF and 2235 Psig. There were no |
| radiological releases and no RCS or steam generator tube leaks. All safety |
| related equipment functioned as required and remains operable. The aux feed |
| system started as expected and decay heat is being removed via the steam |
| bypass system to the condenser. |
| |
| The NRC Resident Inspector was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37146 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MILLSTONE REGION: 1 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [] [] [3] STATE: CT |NOTIFICATION TIME: 15:16[EDT]|
| RXTYPE: [1] GE-3,[2] CE,[3] W-4-LP |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 15:00[EDT]|
| NRC NOTIFIED BY: LANGAN |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |STEVEN DENNIS R1 |
|10 CFR SECTION: | |
|HFIT 26.73 FITNESS FOR DUTY | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
| | |
|3 N Y 100 Power Operation |100 Power Operation |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| CONTRACT EMPLOYEE FAILS FITNESS FOR DUTY TEST |
| |
| A contractor employee failed a Fitness For Duty test administered on July 5, |
| 2000. Specific details of the event are not for public disclosure. |
| Appropriate action has been taken accordance with the company Fitness For |
| Duty program. |
| |
| |
| The NRC Resident Inspector will be notified. State and Local agencies have |
| been notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37147 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HARRIS REGION: 2 |NOTIFICATION DATE: 07/05/2000|
| UNIT: [1] [] [] STATE: NC |NOTIFICATION TIME: 17:14[EDT]|
| RXTYPE: [1] W-3-LP |EVENT DATE: 07/05/2000|
+------------------------------------------------+EVENT TIME: 10:35[EDT]|
| NRC NOTIFIED BY: JERNIGAN |LAST UPDATE DATE: 07/05/2000|
| HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |GEORGE BELISLE R2 |
|10 CFR SECTION: | |
|HFIT 26.73 FITNESS FOR DUTY | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| USE OF ILLEGAL CONTROLLED SUBSTANCE |
| |
| An employee was tested for cause for illegal controlled substance with the |
| results being negative. However, he admitted during the interview he had |
| used such substance. |
| |
| The NRC Resident Inspector was notified. |
+------------------------------------------------------------------------------+