November 12, 1999 The Honorable Richard A. Meserve Dear Chairman Meserve: SUBJECT: PROPOSED FINAL DESIGN CERTIFICATION RULE AND CHANGES TO THE DESIGN CONTROL DOCUMENT ASSOCIATED WITH AP600 DESIGN During the 467th meeting of the Advisory Committee on Reactor Safeguards, November 4-6, 1999, we reviewed the changes to the AP600 Design Control Document and the associated Supplement 1 to NUREG-1512, "Final Safety Evaluation Report Related to Certification of the AP600 Standard Design." We also considered the proposed final AP600 Design Certification Rule. During our review, we had the benefit of discussions with representatives of the NRC staff and Westinghouse Electric Company, and of the documents referenced. Conclusion
Background and Discussion We reviewed the AP600 standard design in accordance with 10 CFR Part 52, which requires the ACRS to report on those portions of the application that concern safety. In our present review, we considered changes to the AP600 Design Control Document, including changes to the design of the plate above a containment sump screen and an increase in the calculated concentrations of hydrogen in the containment following a loss-of-coolant accident (LOCA). The area of the plate was reduced to avoid mechanical interference with a steam generator. The redesigned plate was also lowered closer to the top of the containment sump screen in order to reduce debris accumulation on the screen. The design change was judged to increase safety. Results of the calculations using the final version of the WGOTHIC code demonstrated that the long-term containment temperatures following a LOCA are higher than originally predicted. The higher temperatures lead to a predicted increase in the hydrogen concentrations. However, the post-LOCA hydrogen concentrations remain well below flammability limits throughout the accident. Sincerely, /s/ Dana A. Powers References
|