Introduction
Plumbing may be defined as the practice, materials,
and fixtures used in installing, maintaining, and altering piping, fixtures, appliances,
and appurtenances in connection with sanitary or storm drainage facilities, a venting
system, and public or private water supply systems. Plumbing does not include drilling
water wells; installing water softening equipment; or manufacturing or selling plumbing
fixtures, appliances, equipment, or hardware. A plumbing system consists of three
parts: an adequate potable water supply system; a safe, adequate drainage system;
and ample fixtures and equipment.
The housing inspector’s prime concern while inspecting plumbing is to ensure the
provision of a safe water supply system, an adequate drainage system, and ample
and proper fixtures and equipment that do not contaminate water. The inspector must
make sure that the system moves waste safely from the home and protects the occupants
from backup of waste and dangerous gases. This chapter covers the major features
of a residential plumbing system and the basic plumbing terms and principles the
inspector must know and understand to identify housing code violations that involve
plumbing. It will also assist in identifying the more complicated defects that the
inspector should refer to the appropriate agencies. This chapter is not a plumbing
code, but should provide a base of knowledge sufficient to evaluate household systems.
Elements of a Plumbing System
The primary purposes of a plumbing system are
- To bring an adequate and potable supply of
hot and cold water to the inhabitants of a house, and
- To drain all wastewater and sewage discharge
from fixtures into the public sewer or a private disposal system.
It is, therefore, very important that the housing
inspector be completely familiar with all elements of these systems so that inadequacies
of the structure’s plumbing and other code violations will be recognized. To aid
the inspector in understanding the plumbing system, a schematic of a home plumbing
system is shown in
Figure 9.1.
Water Service
The piping of a house service line should be as short as possible. Elbows and bends
should be kept to a minimum because they reduce water pressure and, therefore, the
supply of water to fixtures in the house. The house service line also should be
protected from freezing. Four feet of soil is a commonly accepted depth to bury
the line to prevent freezing. This depth varies, however, across the country from
north to south. The local or state plumbing code should be consulted for recommended
depths. The minimum service line size should be ¾ inch. The minimum water supply
pressure should be 40 pounds per square inch (psi), no cement or concrete joints
should be allowed, no glue joints between different types of plastic should be allowed,
and no female threaded PVC fittings should be used.
The materials used for a house service may be approved plastic, copper, cast iron,
steel, or wrought iron. The connections used should be compatible with the type
of pipe used. A typical house service installation is pictured in
Figure 9.2. The elements of the service installation are described below.
Corporation stop—The
corporation stop is connected to the water main. This connection is usually made
of brass and can be connected to the main with a special tool without shutting off
the municipal supply. The valve incorporated in the corporation stop permits the
pressure to be maintained in the main while the service to the building is completed.
Curb stop—The curb stop is a similar valve used to isolate the building from
the main for repairs, nonpayment, of water bills or flooded basements. Because the
corporation stop is usually under the street and it is necessary to break the pavement
to reach the valve, the curb stop is used as the isolation valve.
Curb stop box—The curb stop box is an access box to the curb stop for opening
and closing the valve. A long-handled wrench is used to reach the valve.
Meter stop—The meter stop is a valve placed on the street side of the water
meter to isolate it for installation or maintenance. Many codes require a gate valve
on the house side of the meter to shut off water for plumbing repairs. The curb
and meter stops can be ruined in a short time if used very frequently.
The water meter is a device used to measure the amount
of water used in the house. It is usually the property of the water provider and
is a very delicate instrument that should not be abused. In cold climates, the water
meter is often inside the home to keep it from freezing. When the meter is located
inside the home, the company providing the water must make appointments to read
the meter, which often results in higher water costs unless the meter is equipped
with a signal that can be observed from the outside. The water meter is not shown
in
Figure 9.2 because of regional differences in location of the unit.
Because the electric system is sometimes grounded to an older home’s water line,
a grounding loop device should be installed around the meter. Many meters come with
a yoke that maintains electrical continuity even though the meter is removed.
Click here for definitions of terms related to home water systems.
Hot and Cold Water Main Lines
The hot and cold water main lines are usually hung from the basement ceiling or
in the crawl space of the home and are attached to the water meter and hot water
tank on one side and the fixture supply risers on the other. These pipes should
be installed neatly and should be supported by pipe hangers or straps of sufficient
strength and number to prevent sagging. Older homes that have copper pipe with soldered
pipes can pose a lead poisoning risk, particularly to children. In 1986, Congress
banned lead solder containing greater than 0.2% lead and restricted the lead content
of faucets, pipes, and other plumbing materials to no more than 8%. The water should
be tested to determine the presence or level of lead in the water. Until such tests
can be conducted, the water should be run for about 2 minutes in the morning to
flush any such material from the line. Hot and cold water lines should be approximately
6 inches apart unless the hot water line is insulated. This is to ensure that the
cold water line does not pick up heat from the hot water line [2].
The supply mains should have a drain valve stop and waste valve to remove water
from the system for repairs. These valves should be on the low end of the line or
on the end of each fixture riser.
The fixture risers start at the basement main and rise vertically to the fixtures
on the upper floors. In a one-family dwelling, riser branches will usually proceed
from the main riser to each fixture grouping. In any event, the fixture risers should
not depend on the branch risers for support, but should be supported with a pipe
bracket.
The size of basement mains and risers depends on the number of fixtures supplied.
However, a ¾-inch pipe is usually the minimum size used. This allows for deposits
on the pipe due to hardness in the water and will usually give satisfactory volume
and pressure.
In homes without basements, the water lines are preferably located in the crawl
space or under the slab. The water lines are sometimes placed in the attic; however,
because of freezing, condensation, or leaks, this placement can result in major
water damage to the home. In two-story or multistory homes, the water line placement
for the second floor is typically between the studs and, then, for the shortest
distance to the fixture, between the joists of the upper floors.
Hot and Cold Water Piping Materials
Care must be taken when choosing the piping materials. Some state and local plumbing
codes prohibit using some of the materials listed below in water distribution systems.
Polyvinyl Chloride (PVC). PVC is used to make plastic pipe. PVC piping has several applications in and around homes such as in underground sprinkler systems, piping for swimming pool pumping systems, and low-pressure drain systems PVC piping is also used for water service between the meter and building [3]. PVC, or polyvinyl chloride, is one of the most commonly used materials in the marketplace. It is in packaging, construction and automotive material, toys, and medical equipment.
PVC contains phthalates, which have been shown in experimental laboratory animal studies to damage the liver and reproductive organs. Phthalates may leach from the plastics and may be transferred to foods packaged in PVC. Phthalates show almost no toxicity in adult humans in acute (short-term) doses, even at high doses. However, experimental laboratory animal studies show that continuous chronic exposure can result in toxic effects even at very low dosages. Very young infants do not metabolize phthalates as well as do adults and may be at greater risk for harm. The availability of phthalates in the consumer environment results in prevalent exposure to almost all modern industrial consumers.
Lead is sometimes used as a hardening agent to manufacture PVC materials. Therefore, it is very important that third-party testing be done on PVC piping. PVC piping should have the stamp of both the testing laboratory and a potable water (PW) mark to indicate that it meets appropriate standards for use as potable water piping.
Chlorinated PVC. CPVC is a slightly yellow plastic pipe used inside homes.
It has a long service life, but is not quite as tough as copper. Some areas with
corrosive water will benefit by using chlorinated PVC piping. CPVC piping is designed
and recommended for use in hot and cold potable water distribution systems [4].
Copper. Copper comes in three grades:
- M for thin wall pipe (used mainly inside homes);
- L for thicker wall pipe (used mainly outside
for water services); and
- K, the thickest (used mainly between water
mains and the water meter).
Copper lasts a long time, is durable, and connects
well to valves. It should not be installed if the water has a pH of 6.5 or less.
Most public utilities supply water at a pH between 7.2 and 8.0. Many utilities that
have source water with a pH below 6.5 treat the water to raise the pH. Private well
water systems often have a pH below 6.5. When this is the case, installing a treatment
system to make the water less acidic is a good idea [5].
Galvanized Steel. Galvanized pipe corrodes rather easily. The typical life
of this piping is about 40 years. One of the primary problems with galvanized steel
is that, in saturated water, the pipe will become severely restricted by corrosion
that eventually fills the pipe completely. Another problem is that the mismatch
of metals between the brass valves and the steel results in corrosion. Whenever
steel pipe meets copper or brass, the steel pipe will rapidly corrode. Dielectric
unions can be used between copper and steel pipes; however, these unions will close
off flow in a short time. The problem with dielectric unions is that they break
the grounding effect if a live electrical wire comes in contact with a pipe. Some
cities require the two pipes to be bonded electrically to maintain the safety of
grounded pipes.
PEX. PEX is an acronym for a cross-formulated polyethylene. “PE” refers to
the raw material used to make PEX (polyethylene), and “X” refers to the cross-linking
of the polyethylene across its molecular chains. The molecular chains are linked
into a three-dimensional network that makes PEX remarkably durable within a wide
range of temperatures, pressures, and chemicals [6].
PEX is flexible and can be installed with fewer fittings than rigid plumbing systems.
It is a good choice for repiping and for new homes and works well for corrosive
water conditions. PEX stretches to accommodate the expansion of freezing water and
then returns to its original size when water thaws. Although it is highly freeze-resistant,
no material is freeze-proof.
Kitec. Kitec is a multipurpose pressure pipe that uniquely unites the advantages
of both metal and plastic. It is made of an aluminum tube laminated to interior
and exterior layers of plastic. Kitec provides a composite piping system for a wide
range of applications, often beyond the scope of metal or plastic alone. Unlike
copper and steel materials, Kitec is noncorroding and resists most acids, salt solutions,
alkalis, fats, and oils.
Poly. Poly pipe is a soft plastic pipe that comes in coils and is used for
cold water. It can crack with age or wear through from rocks. Other weak points
can be the stainless steel clamps or galvanized couplings.
Polybutylene [Discontinued]. Polybutylene pipe is a soft plastic pipe. This
material is no longer recommended because of early chemical breakdown. Individuals
with a house, mobile home, or other structure that has polybutylene piping with
acetal plastic fittings may be eligible for financial relief if they have replaced
that plumbing system. For claims information, call 1-800-392-7591 or go to
www.pbpipe.com.
Hot Water Safety
In the United States, more than 112,000 people enter a hospital emergency room each
year with scald burns. Of these, 6,700 (6%), have to be hospitalized. Almost 3,000
of these scald burns come from tap water in the home. The three high risk groups
are children under the age of 5 years, the handicapped, and adults over the age
of 65 years. It only takes 1 second to get a serious third-degree burn from water
that is 156ºF (69ºC). Tap water is too hot if instant coffee granules melt in it.
Young children, some handicapped individuals, and elderly people are particularly
vulnerable to tap water burns. Children cannot always tell the hot water faucets
from the cold water faucets. Children have delicate skin and often cannot get out
of hot water quickly, so they suffer hot water burns most frequently. Elderly and
handicapped persons are less agile and more prone to falls in the bath tub. They
also may have diseases, such as diabetes, that make them unable to feel heat in
some regions of the body, such as the hands and feet. Third-degree burns can occur
quickly—in 1 second at 156ºF (69ºC), in 2 seconds at 149ºF (65ºC), in 5 seconds
at 140ºF (60ºC), and in 15 seconds at 133ºF (56ºC).
A tap-water temperature of 120ºF–130ºF (49ºC–54ºC) is hot enough for washing clothes,
bedding, and dishes. Even at 130ºF (54ºC), water takes only a few minutes of constant
contact to produce a third-degree burn. Few people bathe at temperatures above 110ºF
(43ºC), nor should they. Water heater thermostats should be set at about 120ºF (49ºC)
for safety and to save 18% of the energy used at 140ºF (60ºC). Antiscald devices
for faucets and showerheads to regulate water temperature can help prevent burns.
A plumber should install and calibrate these devices. Most hot water tank installations
now require an expansion tank to reduce pressure fluctuations and a heat trap to
keep hot water from escaping up pipes.
Types of Water Flow Controls
It is essential that valves be used in a water system to allow the system to be
controlled in a safe and efficient manner. The number, type, and size of valves
required will depend on the size and complexity of the system. Most valves can be
purchased in sizes and types to match the pipe sizes used in water system installations.
Listed below are some of the more commonly encountered valves with a description
of their basic functions.
Shutoff Valves. Shutoff valves should be installed between the pump and the
pressure tank and between the pressure tank and service entry to a building. Globe,
gate, and ball valves are common shutoff valves. Gate and ball valves cause less
friction loss than do globe valves; ball valves last longer and leak less than do
gate valves. Shutoff valves allow servicing of parts of the system without draining
the entire system.
Flow-control Valves. Flow-control valves provide uniform flow at varying
pressures. They are sometimes needed to regulate or limit the use of water because
of limited water flow from low-yielding wells or an inadequate pumping system. They
also may be needed with some treatment equipment. These valves are often used to
limit flow to a fixture. Orifices, mechanical valves, or diaphragm valves are used
to restrict the flow to any one service line or complete system and to assure a
minimum flow rate to all outlets.
Relief Valves. Relief valves permit water or air to escape from the system
to relieve excess pressure. They are spring-controlled and are usually adjustable
to relieve varying pressures, generally above 60 psi. Relief valves should be installed
in systems that may develop pressures exceeding the rated limits of the pressure
tank or distribution system. Positive displacement and submersible pumps and water
heaters can develop these excessive pressures. The relief valve should be installed
between the pump and the first shutoff valve and must be capable of discharging
the flow rate of the pump. A combined pressure and temperature relief valve is needed
on all water heaters. Combination pressure and vacuum relief valves also should
be installed to prevent vacuum damage to the system.
Pressure-reducing Valves. A pressure-reducing valve is used to reduce line
pressure. On main lines, this allows the use of thinner walled pipe and protects
house plumbing. Sometimes these valves are installed on individual services to protect
plumbing.
Altitude Valves. Often an altitude valve is installed at the base of a hot
water tank to prevent it from overflowing. Altitude valves sense the tank level
through a pressure line to the tank. An adjustable spring allows setting the level
so that the valve closes and prevents more inflow when the tank becomes full.
Foot Valves. A foot valve is a special type of check valve installed at the
end of a suction pipe or below the jet in a well to prevent backflow and loss of
prime. The valve should be of good quality and cause little friction loss.
Check Valves. Check valves have a function similar to foot valves. They permit
water flow in only one direction through a pipe. A submersible pump may use several
check valves. One is located at the top of the pump to prevent backflow from causing
back spin of the impellers. Some systems use another check valve and a snifter valve.
They will be in the drop pipe or pitless unit in the well casing and allow a weep
hole located between the two valves to drain part of the pipe. When the pump is
started, it will force the air from the drained part of the pipe into the pressure
tank, thus recharging the pressure tank.
Frost-proof Faucets. Frost-proof faucets are installed outside a house with
the shutoff valve extending into the heated house to prevent freezing. After each
use, the water between the valve and outlet drains, provided the hose is disconnected,
so water is not left to freeze.
Frost-proof Hydrants. Frost-proof hydrants make outdoor water service possible
during cold weather without the danger of freezing. The shutoff valve is buried
below the frost line. To avoid submerging it, which might result in contamination
and back siphoning, the stop-and-waste valve must drain freely into a rock bed.
These hydrants are sometimes prohibited by local or state health authorities.
Float Valves. Float valves respond to a high water level to close an inlet
pipe, as in a tank-type toilet.
Miscellaneous Switches. Float switches respond to a high and/or low water
level as with an intermediate storage tank. Pressure switches with a low-pressure
cutoff stop the pump motor if the line pressure drops to the cutoff point. Low-flow
cutoff switches are used with submersible pumps to stop the pump if the water discharge
falls below a predetermined minimum operating pressure. High-pressure cut-off switches
are used to stop pumps if the system pressure rises above a predetermined maximum.
Paddle-type flow switches detect flow by means of a paddle placed in the pipe that
operates a mechanical switch when flow in the pipe pushes the paddle.
The inadvertent contamination of a public water supply as a result of incorrectly
installing plumbing fixtures is a potential public health problem in all communities.
Continuous surveillance by environmental health personnel is necessary to know whether
such public health hazards have developed as a result of additions or alterations
to an approved system. All environmental health specialists should learn to recognize
the three general types of defects found in potable water supply systems: backflow,
back siphonage, and overhead leakage into open potable water containers. If identified,
these conditions should be corrected immediately to prevent the spread of disease
or poisoning from high concentrations of organic or inorganic chemicals in the water.
Water Heaters
Water heaters (Figure
9.3) are usually powered by electricity, fuel oil, gas, or, in rare cases,
coal or wood. They consist of a space for heating the water and a storage tank for
providing hot water over a limited period of time. All water heaters should be fitted
with a temperature-pressure (T&P) relief valve no matter what fuel is used. The
installation port for these valves may be found on the top or on the side of the
tank near the top. T&P valves should not be placed close to a wall or door jamb,
where they would be inaccessible for inspection and use. Hot water tanks sometimes
are sold without the T&P valve, and it must be purchased separately. This fact alone
should encourage individual permitting and inspection by counties and municipalities
to ensure that they are installed. The T&P valve should be inspected at a minimum
of once per year.
A properly installed T&P valve will operate when either the temperature or the pressure
becomes too high due to an interruption of the water supply or a faulty thermostat.
Figure 9.3 shows the correct installation of a gas water heater. Particular
care should be paid to the exhaust port of the T&P valve.
Figure 9.4 shows the placement of the T&P valve. This vent should be directed
to within 6 inches of the floor, and care must be taken to avoid reducing the diameter
of the vent and creating any unnecessary bends in the discharge pipe. Most codes
will allow only one 90° bend in the vent. The point is to avoid any constrictions
that could slow down the steam release from the tank to avoid explosive pressure
buildup.
Water heaters that are installed on wooden floors should have water collection pans
with a drainage tube that drains to a proper drain. The pan should be checked on
a regular basis.
Tankless Water Heaters
A tankless unit has a heating device that is activated by the flow of water when
a hot water valve is opened. Once activated, the heater delivers a constant supply
of hot water. The output of the heater, however, limits the rate of the heated water
flow. Demand water heaters are available in propane (LP), natural gas, or electric
models. They come in a variety of sizes for different applications, such as a whole-house
water heater, a hot water source for a remote bathroom or hot tub, or as a boiler
to provide hot water for a home heating system. They can also be used as a booster
for dishwashers, washing machines, and a solar or wood-fired domestic hot water
system [7].
The appeal of demand water heaters is not only the elimination of the tank standby
losses and the resulting lower operating costs, but also the fact that the heater
delivers hot water continuously. Most tankless models have a life expectancy of
more than 20 years. In contrast, storage tank water heaters last 10 to 15 years.
Most tankless models have easily replaceable parts that can extend their life by
many years more.
Drainage System
Water is brought into a house, used, and discharged through the drainage system.
This system is a sanitary drainage system carrying just interior wastewater.
Sanitary Drainage System
The proper sizing of the sanitary drain or house drain depends on the number of
fixtures it serves. The usual minimum size is 4 inches in diameter. The materials
used are usually cast iron, vitrified clay, plastic, and, in rare cases, lead. The
top two pipe choices for drain, waste, and vent (DWV) systems are PVC or ABS. For
proper flow in the drain, the pipe should be sized and angled so that the pipe is
approximately half full. This ensures proper scouring action so that the solids
contained in the waste will not be deposited in the pipe.
Using PVC in DWV pipe is a two-step process needing a primer and then cement. ABS
uses cement only. In most cases the decision will be made on the basis of which
material is sold in an area. Few areas stock both materials because local contractors
usually favor one or the other. ABS costs more than PVC in many areas, but Schedule
40 PVC DWV solid core pipe is stronger than ABS. Their durability is similar.
Size of House Drain. The Uniform Plumbing Code Committee has developed a
method of sizing house drains in terms of fixture units. One fixture unit equals
approximately 7½ gallons of water per minute. This is the surge flow rate of water
discharged from a wash basin in one minute. All other fixtures have been related
to this unit. Fixture unit values are shown in Table 9.1.
Table
9.1. Fixture Unit Values
Fixture
|
Units
|
Lavatory/washbasin
|
1
|
Kitchen sink
|
2
|
Bathtub
|
2
|
Laundry tub
|
2
|
Combination fixture
|
3
|
Urinal
|
5
|
Shower bath
|
2
|
Floor drain
|
1
|
Slop sink
|
3
|
Toilet
|
6 or 3
(based on type)
|
One bathroom group
|
8
|
180 square feet of
roof drained
|
1
|
Grade of House Drain. A house drain should
be sloped toward the sewer to ensure scouring of the drain. The usual pitch of a
house or building sewer is a ¼-inch drop in 1 foot of length. The size of the drain
is based on the fixture units flowing into the pipe and the slope of the drain.
Table 9.2 shows the required pipe size for the system.
Table 9.2. Sanitary House Drain Sizes
Diameter of Pipe,
Inches
|
Maximum Number of
Fixtures per Listed Drain Slope†
|
|
|
1/8
inch per foot
|
¼ inch per foot
|
½ inch per foot
|
1¼
|
1
|
1
|
1
|
1½
|
2
|
2
|
3
|
2
|
5
|
6
|
8
|
3
|
15
|
18
|
21
|
4
|
84
|
96
|
114
|
6
|
300
|
450
|
600
|
8
|
990
|
1,392
|
2,220
|
12
|
3,084
|
4,320
|
6,912
|
†Number of fixture units.
|
House Drain Installation. Typical branch connections to the main are shown in
Figure 9.5.
Fixture and Branch Drains. A branch drain is a waste pipe that collects the
waste from two or more fixtures and conveys it to the sewer. It is sized in the
same way as the sewer, taking into account that all toilets must have a minimum
3-inch diameter drain, and only two toilets may connect into one 3-inch drain. All
branch drains must join the house drain with a Y-fitting as shown in
Figure 9.5. The same is true for fixture drains
joining branch drains. The Y-fitting is used to eliminate, as much as possible,
the deposit of solids in or near the connection. A buildup of these solids will
block the drain. Recommended minimum sizes of fixture drains are shown in
Table 9.2.
Traps
A plumbing trap is a device used in a waste system to prevent the passage of sewer
gas into the structure and yet not hinder the fixture’s discharge to any great extent.
All fixtures connected to a household plumbing system should have a trap installed
in the line. The effects of sewer gases on the human body are well known; many of
the gases are extremely harmful. In addition, certain sewer gases are explosive.
P-trap. The most commonly used trap is the P-trap (Figure
9.6). The depth of the seal in a trap is usually 2 inches. A deep seal trap
has a 4-inch seal.
As mentioned earlier, the purpose of a trap is to seal out sewer gases from the
structure. Because a plumbing system is subject to wide variations in flow, and
this flow originates in many different sections of the system, pressures vary widely
in the waste lines. These pressure differences tend to remove the water seal in
the trap. The waste system must be properly vented to prevent the traps from siphoning
dry, thus losing their water seal and allowing gas from the sewer into the building.
Objectionable Traps. The S-trap and the ¾ S-trap (Figure
9.7) should not be used in plumbing installations. They are almost impossible
to ventilate properly, and the ¾ S-trap forms a perfect siphon. Mechanical traps
were introduced to counteract this problem. It has been found, however, that the
corrosive liquids flowing in the system corrode or jam these mechanical traps. For
this reason, most plumbing codes prohibit mechanical traps.
The bag trap, an extreme form of S-trap, is seldom found.
Figure 9.7 also shows this type of S-trap.
Traps are used only to prevent the escape of sewer gas into the structure. They
do not compensate for pressure variations. Only proper venting will eliminate pressure
problems.
Ventilation
A plumbing system is ventilated to prevent trap seal loss, material deterioration,
and flow retardation.
Trap Seal Loss. The seal in a plumbing trap may be lost due to siphonage
(direct and indirect or momentum), back pressure, evapo ration, capillary attraction,
or wind effect. The first two are probably the most common causes of loss.
Figure 9.8 depicts this siphonage process;
Figure 9.9 depicts loss of trap seal.
If a waste pipe is placed vertically after the fixture trap, as in an S-trap, the
wastewater continues to flow after the fixture is emptied and clears the trap. This
is caused by the pressure of air on the water of the fixture being greater than
the pressure of air in the waste pipe. The action of the water discharging into
the waste pipe removes the air from that pipe and thereby causes a negative pressure
in the waste line.
In the case of indirect or momentum siphonage, the flow of water past the entrance
to a fixture drain in the waste pipe removes air from the fixture drain. This reduces
the air pressure in the fixture drain, and the entire assembly acts as an aspirator.
(Figures
9.10 and
9.11
show plumbing configurations that would allow this type of siphonage to occur.)
Back Pressure.
The flow of water in a soil pipe varies according to the fixtures being used. Small
flows tend to cling to the sides of the pipe, but large ones form a slug of waste
as they drop. As this slug of water falls down the pipe, the air in front of it
becomes pressurized. As the pressure builds, it seeks an escape point. This point
is either a vent or a fixture outlet. If the vent is plugged or there is no vent,
the only escape for this air is the fixture outlet.
The air pressure forces the trap seal up the pipe into the fixture. If the pressure
is great enough, the seal is blown out of the fixture entirely.
Figures 9.8 and
9.9 illustrate the potential for this type of problem. Large water flow
past the vent can aspirate the water from the trap, while water flow approaching
the trap can blow the water out of the trap.
Vent Sizing. Vent pipe installation is similar to that of soil and waste
pipe. The same fixture unit criteria are used. Table 9.3
shows minimum vent pipe sizes.
Table 9.3.
Minimum Fixture Service Pipe Diameters
[8]
Fixture
|
Supply Line, Inches
|
Vent Line, Inches
|
Drain Line, Inches
|
Bathtub
|
½
|
1½
|
1½
|
Kitchen sink
|
½
|
1½
|
1½
|
Lavatory
|
3/8
|
1¼
|
1¼
|
Laundry sink
|
½
|
1½
|
1½
|
Shower
|
½
|
2
|
2
|
Toilet tank
|
3/8
|
3
|
3
|
*Millimeters in parenthesis.
|
Vent pipes of less than 1¼ inches in diameter should
not be used. Vents smaller than this diameter tend to clog and do not perform their
function.
Individual Fixture Ventilation.
Figure 9.12 shows a typical installation of a wall-hung plumbing unit. This
type of ventilation is generally used for sinks, drinking fountains, and so forth.
Air admittance valves are often used for individual fixtures.
Figure 9.13 shows a typical installation of a bathtub or shower ventilation
system.
Figure 9.14 shows the proper vent connection for toilet fixtures and
Figure 9.15 shows a janitor’s sink or slop sink that has the proper P-trap.
For the plumbing fixture to work properly, it must be vented as in
Figures 9.13 and
9.14.
Unit Venting.
Figures 9.10 and
9.11 show a back-to-back shared ventilation system for various plumbing
fixtures. The unit venting system is commonly used in apartment buildings. This
type of system saves a great deal of money and space when fixtures are placed back-to-back
in separate apartments. It does, however, pose a problem if the vents are undersized
because they will aspirate the water from the other trap.
Figure 9.16 shows a double combination Y-trap used for joining the fixtures
to the common soil pipe fixture on the other side of the wall.
Wet Venting. Bathroom fixture groupings are commonly wet vented; that is,
the vent pipe also is used as a waste line.
Total Drainage System
The drain, soil waste, and vent systems are all connected, and the inspector should
remember the following fundamentals:
Working vents must provide air to all fixtures to ensure the movement of waste into
the sewer. Improperly vented fixtures will drain slowly and clog often. They also
present a health risk if highly toxic and explosive sewer gases enter the home.
Correct venting is shown in
Figures 9.10,
9.11,
9.12,
9.13,
9.14, and
9.15; incorrect venting is shown in
Figures 9.8 and
9.9.
A wet vent can result in one of the traps siphoning the other dry when large volumes
of water are poured down the drain. Wet vents are not permitted by many state plumbing
codes because of the potential for self-siphoning.
Backup of sewage into sinks, dishwashers, and other appliances is always a possibility
unless the system is equipped with air gaps or vacuum breakers. All connections
to the potable water system must be a minimum of two pipe diameters above the overflow
of the appliance and, in some cases, where flat surfaces are near, two and one-half
pipe diameters above the overflow of the appliance.
A simple demonstration of how easily siphoning can occur is to hold a glass of water
with food coloring in it with the tip of a faucet in the colored water. If the sink’s
vegetable sprayer is directed to a second glass and sprayed, in most cases, the
colored water will be aspirated into the faucet and then out of the sprayer into
the second glass. Weed or pest killer attachments that hook to garden hoses work
on the same principle.
Figure 9.17 shows an outside hose bib equipped with a vacuum breaker. In
the areas of the United States that freeze, these vacuum breakers must be removed
because they trap water in the area of the line that can freeze and burst. Many
vacuum breakers sold today automatically drain to prevent freeze damage.
Devices that pull water from a utility may create negative pressures that can damage
water piping and pull dangerous sub stances into the line at the same time. These
devices include power sprayers that hook to the home hose bib (outside faucets)
and pressurize the spray by creating a vacuum on the supply side.
Corrosion Control
To understand the proper maintenance procedures for the prevention and elimination
of water quality problems in plumbing systems, it is necessary to understand the
process used to determine the chemical aggressiveness of water. The process is used
to determine when additional treatment is needed. Water that is out of balance can
result in many negative outcomes, from toxic water to damaged and ruined equipment.
Water dissolves and carries materials when it is not saturated. An equilibrium among
pH, temperature, alkalinity, and hardness controls water’s ability to create scale
or to dissolve material. If water is saturated with harmless or beneficial substances,
such as calcium, then the threat of damage can be mitigated. The Langelier method,
developed in the early 1930s, is a process used in boiler management, municipal
water treatment, and swimming pools to provide this balance. In the Langelier index,
saturation over 0.3 is scale forming, and a saturation below 0.3 is corrosive.
The susceptibility of metal to corrosion is as follows (most susceptible to least
susceptible): magnesium, zinc, aluminum, cadmium, mild steel, cast iron, stainless
steel (active), lead-tin solder, lead, tin, brass, gun metal, aluminum bronze, copper,
copper-nickel alloy, Monel, titanium, stainless steel (passive), silver, gold, and
platinum.
Water Conservation
How much attention should be paid to fixtures that just drip a little bit of water
or that just will not quite shut off? At 30 drops per minute, you will lose and
pay for 54 gallons per month. At 60 drops per minute, you will lose and pay for
113 gallons per month. At 120 drops per minute, you will lose and pay for 237 gallons
per month.
This is only a small loss of water considering the 5 to 7 gallons per flush used
by a properly functioning toilet. If the toilet is not properly maintained, the
loss of water and its effect on the monthly water bill can be incredible. Lower
flow toilets have been mandated to save precious and limited resources. Most pre-1992
toilets used up to 7 gallons per flush. Toilets have since evolved to use 5.5, then
3.5, and now 1.6 gallons per flush.
With the changes in the water usage laws in 1992, there were many customer complaints,
and plumbers were in the bad position of installing products that nobody wanted
to use. New and updated products now work better than the old water wasters.
According to the EPA, in 2000, a typical U.S. family of four spent approximately
$820 every year on water and sewer fees, plus another $230 in energy for heating
water. In many cities, according to the U.S. EPA, water and sewer costs can be more
than twice those amounts. Many people do not realize how much money they can save
by taking simple steps to save water, and they do not know the cumulative effects
small changes can have on water resources and environmental quality. Fixing a leaky
faucet, toilet, or lawn-watering system can reduce water consumption. Changing to
water-efficient plumbing fixtures and appliances can result in major water and energy
savings [9,10].
Summer droughts remind many of the need to appreciate clean water as an invaluable
resource. As the U.S. population increases, the need for clean water supplies continues
to grow dramatically and puts additional stress on our limited water resources.
We can all take steps to save and conserve this valuable resource.
The EPA [11] suggests the following steps homeowners
should take right away to save water and money:
- Stop leaks!—Check
indoor water-using appliances and devices for leaks. Pay particular attention
to toilets that leak.
- Take showers—Showers
use considerably less water than do baths.
- Replace shower heads—Replacement
shower heads are available that reduce water use.
- Turn the water off when not needed—While
brushing your teeth, turn the water off until you need to rinse.
- Replace your old toilet—The
largest water user inside the home is the toilet. If a home was built before
1992 and the toilet has never been replaced, it is very likely that it is not
a water-efficient, 1.6 gallons-per-flush toilet. Choose a replacement toilet
carefully to ensure that what you make up per individual flush, you do not lose
because you must flush more often.
- Replace your clothes washer—The
second largest water user in the home is the washing machine. Energy Star-rated
washers that also have a water factor at or lower than 9.5 use 35%–50% less
water and 50% less energy per load. This saves money on both water and energy
bills.
- Plant the right plants with proper
landscape design and irrigation—Select plants that
are appropriate for the local climate. Having a 100% turf lawn in a dry desert
climate uses a significant amount of water. Also, home owners should consider
the benefits of a more natural landscape or wildscape.
- Water plants only as needed—Most
water wasted in the garden is by watering when plants do not need it or by not
maintaining the irrigation system. If manually watering, set a timer and move
the hose promptly. Make sure the irrigation controller has a rain shutoff device
and that it is appropriately scheduled. Drip irrigation should be considered
where practical. Newer irrigation systems have sensors to prevent watering while
it is raining.
Putting It All Together
The photographs below, taken during construction of a home by Habitat for Humanity,
show various plumbing elements discussed in this chapter.
Roughed-in clothes washer.
Hot and cold copper water lines and drain, P-trap and vent, and vent for the washer
drain. When a house is vacant for awhile, the P-trap should be filled with water
to prevent sewer gas from entering the home. Mineral oil added to the water can
slow the loss of fluid in the trap.
Roughed-in sink.
Hot and cold water pipes, soil pipe, and vent shown.
Roughed-in bathroom.
Vent for the sink and toilet, soil pipe, and cap for toilet connection shown.
A wax or plastic seal shaped like a donut will be placed on the cap before bolting
down the toilet.
Back of a fiberglass shower/bathtub combination.
Mixing and antiscald water flow control, vent for fixture, hot and cold water
lines, and bathtub overflow shown. At this point in construction, insulation might
be considered for the hot water lines.
Water service and waste water line.
Polyethylene water service pipe entering the home through the concrete basement
wall shown. White plastic adapter shown between the polyethylene water service pipe
and ¾ inch copper water line. A short distance above the adapter is a pressure reducing
valve. To the right of water line is the 4 inch PVC pipe waste water line.
References
- US Environmental Protection
Agency. United States Environmental Protection Agency guidance from hotline
compendium: lead ban. Washington, DC: US Environmental Protection Agency; 1988.
Available from URL:
http://www.epa.gov/safewater/wsg/wsg_H19.pdf.
- Uni-Bell PVC Pipe Association.
Handbook of PVC pipe design and construction. Dallas: Uni-Bell PVC Pipe Association;
2001. Available from URL:
http://www.uni-bell.org/pubs/handbook.pdf.
- Occupational Safety and
Health Administration. Safety hazard information bulletin on the use of polyvinyl
chloride (PVC) pipe in above ground installations. Washington, DC: Occupational
Safety and Health Administration; 1988.
http://www.osha.gov/dts/hib/hib_data/hib19880520.html.
- Copper Development Association.
Copper in your home: plumbing, heating, cooling. New York: Copper Development
Association; no date. Available from URL:
http://www.copper.org/copperhome/PHC/phc_home.html.
- Plastic Pipe and Fittings
Association. Cross-linked polyethylene. Glen Ellyn, IL: Plastic Pipe and Fittings
Association; no date. Available from URL:
http://www.ppfahome.org/pex/historypex.html.
- NAMCO. Determine the total
fixture unit load. Dallas: NAMCO; no date. Available
from URL:
http://www.namco-div.com/booster/sel%20criteria/fixtureload.htm.
- Public Health-Seattle
and King County. Public health plumbing program: water supply fixture units
(WSFU) and minimum fixture branch pipe sizes. Seattle, WA: Public Health-Seattle
and King County; no date. Available from URL:
http://www.metrokc.gov/health/plumbing/wsfu.htm.
- US Environmental Protection
Agency. Developing water system financial capacity. Washington, DC: US Environmental
Protection Agency; 2002. Available from
URL:http://www.epa.gov/safewater/dwa/electronic/
presentations/pwsoper/fincapacity.pdf.
- US Environmental Protection
Agency. Water and wastewater pricing. Washington, DC: US Environmental Protection
Agency; no date. Available from URL:
http://www.epa.gov/water/infrastructure/pricing/.
- US Environmental Protection
Agency. Using water wisely in the home. Washington, DC: US Environmental Protection
Agency; 2002. Available from URL:
http://www.epa.gov/owm/water-efficiency/waterconservation_final.pdf.
- Energy Efficiency and
Renewable Energy Clearinghouse. Demand (tankless or instantaneous) water heaters.
Merrifield, VA: Energy Efficiency and Renewable Energy Clearinghouse; no date.
Available from URL:
http://www.toolbase.org/
tertiaryT.asp?DocumentID=3206&&&CategoryID=0.
Additional
Sources of InformationNational Sanitation
Foundation. Available from URL:
http://www.nsf.org/international.
Underwriters Laboratories Inc. Available from URL:
http://www.ul.com.
American Society of Plumbing Engineers. Available from URL:
http://aspe.org.
Plumbing-Heating-Cooling Contractors Association. Available from URL:
http://www.phccweb.org.
American Backflow Prevention Association. Available from URL:
http://www.abpa.org.
American Society of Sanitary Engineering. Available from URL:
http://www.asse-plumbing.org.
American Water Works Association. Available from URL:
http://www.awwa.org.
For more water conservation tips and energy saving ideas for businesses, industries,
and individuals, visit the EPA’s Water Use Efficiency Program Web site (http://www.epa.gov/owm/water-efficiency/index.htm)
The EPA report, Cases in Water Conservation: How Efficiency Programs Help Water
Utilities Save Water and Avoid Costs, can be ordered by calling 513-489-8190 and
asking for EPA832-B-02-003. Available from URL:
http://www.epa.gov/owm/water-efficiency/utilityconservation.pdf.