Search Options | ||||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us |
ACCESSION #: 9506220313 Cooper Industries Cooper-Bessemer Reciprocating Products Division 150 Lincoln Avenue Grove City, PA 16127-1898 412 458-8000 June 15, 1995 COOPER Cooper Energy Services Our Ref: QCG-10167 Document Control Desk U.S. Nuclear Regulatory Commission Enterprise Washington, D.C. 20555 Report #167 Dear Sir: In accordance with the requirements of the Nuclear Regulatory Commission Title 10, Chapter 1, Code of Federal Regulations, Part 21, Cooper- Bessemer Reciprocating Products Division, a division of Cooper Industries, hereby notifies the Commission of a potential defect in a component of a DSRV and DSR Enterprise Standby Diesel Generator System. There exists a potential problem with a Bellofram Air Cylinder, Cooper part number AJ-009-000 which is used to control a butterfly valve in the diesel engine intake air system. These air cylinders are installed on all nuclear Enterprise EDG's currently in service. UTILITY SITE SERIAL NO. MODEL LILCO Shoreham 74010-12 DSR-48 ENTERGY Grand Gulf 74033-34 DSRV-16-4 GULF STATES River Bend 74039-40 DSR-48 CP&L Shearon Harris 74046-48 DSRV-16-4 DUKE Catawba 75017-20, DSRV-16-4 74049 CLEVELAND ELEC Perry 75051-54 DSRV-16-4 TVA Bellefonte 75080-83 DSRV-16-4 TVA Hartsville 77024 DSRV-16-4 TU ELECTRIC Comanche Peak 76001-04 DSRV-16-4 GEORGIA POWER Vogtle 76021-24 DSRV-16-4 INTERNATIONAL SITES KOREA ELECTRIC KORI 3 & 4 79029-32 DSRV-16-4 KOREA ELECTRIC Yonggwang 1 & 2 81021-24 DSRV-16-4 TAIWAN Kuosheng 75005-08 DSR-48 TAIWAN Maanshan 78006-09 DSRV-16-4 Page 2 QCG-10167 June 15, 1995 On May 16, 1995, a newly installed air cylinder failed at Grand Gulf Nuclear Station on engine S/N 74033, during their refueling outage RF07, after fewer than 12 actuations the left bank air cylinder piston/rod assembly separated which allowed the butterfly valve to go closed. With the left bank butterfly valve closed, the engine tried to maintain load with the right bank cylinders, which caused the right bank turbocharger to be overloaded and the EDG was shut down. Inspection of the failed cylinder revealed that the piston/piston rod assembly had failed in the area where they were joined by projection welding. The root cause of this failure was a poor quality weld between the piston/piston rod. Cooper-Bessemer has discussed this failure with the manufacturer of the air cylinder, Bellofram Corporation, and has reviewed their processes utilized in manufacturing and testing of the affected cylinder. Bellofram Corporation reports no known failures in other commercial applications of this type of air cylinder. Cooper-Bessemer also has no previously reported failures of this cylinder. Based on this information from Bellofram, Cooper-Bessemer has judged this failure to be an isolated incident, with no further corrective action required at affected utilities or at Cooper-Bessemer. Our investigation into this matter was concluded on June 12, 1995. If you have any questions concerning this report, please contact Ronald G. Billig, Supervisor, Enterprise Engineering or John R. Schneider, Quality Assurance Manager at 412-458-8000. Sincerely, COOPER CAMERON CORPORATION John D. Mowery Vice President and General Manager JDM/kll cc: J. R. Schneider - CES/GC B. R. Sedelmyer - CES/GC A. D. Gillette - CES/GC D. T. Blizzard - CES/GC J. M. Horne - CES/GC R. G. Billig- CES/GC B. C. Guntrum - CES/Alameda R. L. Nimmo - CES/Alameda Lee Duck - CES/Alameda Page 3 June 15, 1995 QCG-10167 Copied to: S. S. OwYoung - CES/Alameda J. R. Andrews - CES/Alameda R. A. Johnston - CES/Alameda File: K5fa35 - Bellofram Air Cyl. Mr. Walter Haass - NRC One White Flint North Mailstop 9D4 Washington, DC 20555 Entergy Operations P. O. Box 429 Echelon One 1340 Echelon Parkway Jackson, MS 39286-1995 Attn: T. H. Cloninger Vice Pres. Nucl. Eng. Carolina Power and Light Co. Harris Nuclear Project P. O. Box 165 New Hill, NC 27562 Attn: William Robinson Plant Gen. Mgr. Carolina Power and Light Co. P. O. Box 1551 Raleigh, NC 27602 Attn: W. S. Orser Exec. Vice President Carolina Power and Light Co. Shearon Harris Nuclear Project P. O. Box 165 New Hill, NC 27562 Attn: Mickey Hamby Carolina Power and Light Co. Brunswick Nuclear Plant NC Hwy. 87, 2-1/2 Mi. North Southport, NC 28461 Attn: Roy A. Anderson Vice President Page 4 June 15, 1995 QCG-10167 Copied to: Carolina Power and Light Co. Robinson Nuclear Project SC Hwy. 151 and 23, Box 790 Hartsville, SC 29550 Attn: C. S. Hinnant Vice President Cleveland Electric Illuminating Perry Nuclear Power Plant P. O. Box 97 Perry, OH 44081 Attn: M. Lister Cleveland Electric Illuminating Perry Nuclear Power Plant P. O. Box 97 Perry, OH 44081 Attn: Russell J. Tadych Manager, Quality Control Cleveland Electric Illuminating Perry Nuclear Power Plant P. O. Box 97 Perry, OH 44081 Attn: Harold M. Coon Cooper-Enterprise Clearinghouse Duke Engineering & Service 230 South Tryon St. P.O. Box 1004 Charlotte, NC 28201-1004 Attn: G. A. Harrison Duke Power Co. Nuclear Generation Dept. P. O. Box 1007 Charlotte, NC 28201-1007 Attn: Mgr., Nuclear Safety Duke Power Co. Nuclear Generation Dept. P. O. Box 1007 Charlotte, NC 28201-1007 Attn: W. T. Robertson V. P. Procurement Page 5 June 15, 1995 QCG-10167 Copied to: Entergy P. O. Box 429 Echelon One 1340 Echelon Parkway Jackson, MS 39286-1995 Attn: F. W. Titus Vice President, Engineering Entergy P. O. Box 756 Port Gibson, MS 39150 Attn: C. R. Hutchinson Vice Pres., Operations-GGNS Entergy P. O. Box 756 Port Gibson, MS 39150 Attn: D. L. Pace, Director Design Engineering-GGNS Entergy P. O. Box 756 Port Gibson, MS 39150 Attn: M. J. Meisner Director, NS & RA Manager, Quality Services Entergy Operations Box 756 Port Gibson, MS 39150 Southern Nuclear Operating Company Vogtle Project P. O. Box 1295 Birmingham, AL 35201 Attn: Mgr., Engineering and Licensing Georgia Power Co. Plant Vogtle P. O. Box 1600 Waynesboro, GA 30830 Attn: Mr. W. B. Shipman General Manager Page 6 June 15, 1995 QCG-10167 Copied to: Gulf States Utilities P. O. Box 220 St. Francisville, LA 70775 Attn: L. A. England Director Nuclear Licensing Long Island Power Authority Shoreham Nuclear Power Station North Country Rd. Wading River, NY 11792 Attn: Mgr. Licensing & Regulatory Compliance Department Tennessee Valley Authority 1101 Market Street, LP 4F Chattanooga, TN 37402 Attn: Mr. M. J. Fecht Manager, Nuclear Experience Review TU Electric - Production Division Group Vice President - Nuclear Skyway Tower 400 North Olive Street, L.B. 81 Dallas, TX 75201 Attn: C. L. Terry Mr. Koh, Kyoo-Kun Plant Mgr., Kori 3 & 4 Korea Electric Power Corp. 216 Ko-Ri Jangan-Up Yangsan-Gun Kyung-Nam, Korea 626-950 Mr. Hong, Jo Boo Manager, Nuclear Power Generation Dept. Korea Electric Power Corporation 167, Samsong-Dong, Kangnam KU Seoul, 137-791 Korea Mr. Lee, Hee-Sung Plant Mgr., Yonggwang Nuclear Unit 1 & 2 Korea Electric Power Co. 517, Kyema-Ri Hong Nong-Eup Yonggwang-Gun Jeon Nam Korea 513-880 Page 7 June 15, 1995 QCG-10167 Copied to: Mr. T. R. Ho, Superintendent Taiwan Power Company Kuosheng Nuclear Power Station 60 Pa-Tou Yeh-Liu Village Wan Li Hsiang, Taipei Hsien (20703), Taiwan, R.O.C. Mr. A. H. Jeng Director, Nuclear Safety Dept. Taiwan Power Company 242 Roosevelt Road, Section 3 Taipei 100, Republic of China Mr. S. H. Soong Station Superintendent Third Nuclear Power Station Taiwan Power Company P. O. Box 39 Heng-Chun, Ping-Tung Hsein Taiwan, 924 R.O.C. *** END OF DOCUMENT ***