Allowable Shipment Frequencies for the Transport of Toxic Gases Near Nuclear Power Plants
(NUREG/CR-2650)
On this page:
Download complete document
The following links on this page are to documents in Adobe Portable Document
Format (PDF). See our Plugins, Viewers, and
Other Tools page for more information. For successful viewing of PDF documents on our site please be sure to use the latest version of Adobe.
Publication Information
Date Published: October 1982
Sandia National Laboratories
Albuquerque, New Mexico 87185
operated by Sandia Corporation
for the
U. S. Department of Energy
Prepared for
Division of Systems and Reliability Research
Office of Nuclear Regulatory Research
U. S. Nuclear Regulatory Commission
Washington, DC 20555
Under Memorandum of Understanding DOE-40-550-75
NRC FIN No. A1214
Availability
Notice
Abstract
One part of the safety analysis of offsite hazards for a
nuclear power plant is consideration of accidents which could
release toxic gases or vapors and thus jeopardize plant safety
through incapacitation of the control room operators. The purpose
of this work is to provide generic, bounding estimates of the
maximum allowable shipping frequencies for the transport of a
chemical near the plant, such that the regulatory criteria for the
protection of the operators are met. A probabilistic methodology
was developed and then applied to the truck and rail transport of
an example chemical, chlorine. The current regulatory criteria
are discussed in detail. For this study, a maximum allowable
probability of occurrence of operator incapacitation of 10-5 per
year was used in the example calculation for each mode of transport.
Comprehensive tables of conditional probabilities are presented.
Maximum allowable shipping frequencies are then derived. These
frequencies could be used as part of a generic, bounding criterion
for the screening of toxic hazards safety analyses.
Unless a transport survey assures shipping frequencies within 8 km of the plant on the order of or lower than 4/week for rail or 35/week for truck, the control room should be isolatable and the shipping frequency then determines the degree of isolation needed. The need for isolation implies the need for toxic chemical detection at the air intake.
For a self-detection case in which the smell threshold is significantly lower than the incapacitation threshold and the control room is isolatable, the corresponding shipping frequencies are
11/week for rail or 115/week for truck. Self-contained breathing
equipment is assumed to be used after 5 minutes.
|