Acceptance and Verification For Early Warning Fire Detection Systems
(NUREG/CR-1798)
On this page:
Download complete document
The following links on this page are to documents in Adobe Portable Document
Format (PDF). See our Plugins, Viewers, and
Other Tools page for more information. For successful viewing of PDF documents on our site please be sure to use the latest version of Adobe.
Publication Information
J.L. Boccio and R.E. Hall Brookhaven National Laboratory
Upton, New York 11973 and
I. Asp Gage-Babcock and Associates, Inc.
Mount Kisco, New York 10549
May 1980
Prepared for the
U.S. Nuclear Regulatory Commission
Washington, D.C. 20555
Under Interagency Agreement DE-ACO2-76CH00016
NRC FIN NO. A-3335
Availability
Notice
Abstract
This report has been written to provide an interim guide accounting for
the basic factors that should be considered in formulatina a fire detection
system selection criteria and the verification of such a system.
The fire detection system selection criteria that is proposed here still
requires a viable mix of good engineering judgement, the use of qualified
investigators, and excellent reporting and administrative procedures; all of
which should be coupled to the results of current research that has been discussed herein.
The fire detection analysis should address five major phases required in
a fire detection analysis, viz, (1) establishing area detector requirements,
(2) selection of specific detector types, (3) location and spacing of
detectors, (4) installation tests and maintenance, and (5) administrative
controls and reporting.
|