Search Options | |||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us | ![]() |
Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned scrams | 0 | 0 | 0 | 0 | 0 | 1.0 | 0 | 0 |
Critical hours | 1332.8 | 2159.0 | 2184.0 | 2208.0 | 2209.0 | 1914.0 | 1305.4 | 2208.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0.8 | 0.9 | 0.9 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned power changes | 0 | 1.0 | 0 | 0 | 0 | 1.0 | 1.0 | 0 |
Critical hours | 1332.8 | 2159.0 | 2184.0 | 2208.0 | 2209.0 | 1914.0 | 1305.4 | 2208.0 |
Indicator value | 0.9 | 1.8 | 1.8 | 0.9 | 0.8 | 0.8 | 1.8 | 1.8 |
Licensee Comments: none
Unplanned Scrams with Complications | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Scrams with complications | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (PWR) | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Safety System Functional Failures | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -3.50E-08 | -3.50E-08 | -5.00E-08 | -5.00E-08 | -7.40E-08 | -7.40E-08 | -7.40E-08 | -5.90E-08 |
URI (ΔCDF) | 1.00E-06 | 1.00E-06 | 4.70E-07 | 4.70E-07 | 6.60E-07 | 7.20E-07 | 1.20E-07 | 5.90E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 9.65E-07 | 9.65E-07 | 4.20E-07 | 4.20E-07 | 5.86E-07 | 6.46E-07 | 4.60E-08 | 5.31E-07 |
Licensee Comments:
3Q/08: Risk Cap Invoked.
Mitigating Systems Performance Index, High Pressure Injection System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -1.80E-08 | -1.20E-08 | -9.10E-09 | -1.20E-08 | -6.20E-09 | -1.90E-09 | -4.20E-09 | 1.10E-09 |
URI (ΔCDF) | -8.10E-09 | -8.10E-09 | -8.20E-09 | -8.10E-09 | -8.90E-09 | -9.00E-09 | -8.80E-09 | -8.70E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -2.61E-08 | -2.01E-08 | -1.73E-08 | -2.01E-08 | -1.51E-08 | -1.09E-08 | -1.30E-08 | -7.60E-09 |
Licensee Comments: none
Mitigating Systems Performance Index, Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -4.00E-08 | -3.90E-08 | -5.30E-08 | -5.90E-08 | -8.40E-08 | -8.80E-08 | -8.80E-08 | -6.40E-08 |
URI (ΔCDF) | -1.30E-07 | -1.30E-07 | -1.20E-07 | -1.20E-07 | -1.30E-07 | -1.30E-07 | -1.30E-07 | -1.30E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.70E-07 | -1.69E-07 | -1.73E-07 | -1.79E-07 | -2.14E-07 | -2.18E-07 | -2.18E-07 | -1.94E-07 |
Licensee Comments: none
Mitigating Systems Performance Index, Residual Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -1.40E-08 | -1.40E-08 | -1.40E-08 | -1.40E-08 | -1.50E-08 | -1.10E-08 | -1.10E-08 | -1.10E-08 |
URI (ΔCDF) | -4.00E-08 | -4.00E-08 | -4.00E-08 | -4.00E-08 | -4.40E-08 | -4.60E-08 | -4.70E-08 | -4.70E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -5.40E-08 | -5.40E-08 | -5.40E-08 | -5.40E-08 | -5.90E-08 | -5.70E-08 | -5.80E-08 | -5.80E-08 |
Licensee Comments: none
Mitigating Systems Performance Index, Cooling Water Systems | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -3.20E-14 | -3.20E-14 | -3.20E-14 | -3.20E-14 | 7.10E-09 | 7.20E-09 | 7.20E-09 | 7.20E-09 |
URI (ΔCDF) | -1.30E-07 | -1.30E-07 | -1.30E-07 | -1.30E-07 | -1.10E-07 | -1.00E-07 | -1.00E-07 | -2.10E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.30E-07 | -1.30E-07 | -1.30E-07 | -1.30E-07 | -1.03E-07 | -9.28E-08 | -9.28E-08 | -1.38E-08 |
Licensee Comments: none
Reactor Coolant System Activity | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum activity | N/A | 0.000042 | 0.000059 | 0.000058 | 0.000077 | 0.000070 | 0.000055 | 0.000084 | 0.000079 | 0.000087 | 0.000084 | 0.000088 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | N/A | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Reactor Coolant System Activity | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum activity | 0.000079 | 0.000084 | 0.000100 | 0.000120 | 0.000102 | 0.000148 | N/A | 0.000055 | 0.000057 | 0.000056 | 0.000066 | 0.000061 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | N/A | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Reactor Coolant System Leakage | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum leakage | 0.152 | 0.290 | 0.060 | 0.103 | 0.030 | 0.045 | 0.047 | 0.035 | 0.034 | 0.036 | 0.040 | 0.035 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 1.5 | 2.9 | 0.6 | 1.0 | 0.3 | 0.5 | 0.5 | 0.4 | 0.3 | 0.4 | 0.4 | 0.4 |
Reactor Coolant System Leakage | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum leakage | 0.036 | 0.039 | 0.039 | 0.045 | 0.057 | 0.053 | 0 | 0.039 | 0.018 | 0.017 | 0.015 | 0.013 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 0.4 | 0.4 | 0.4 | 0.5 | 0.6 | 0.5 | 0 | 0.4 | 0.2 | 0.2 | 0.2 | 0.1 |
Licensee Comments: none
Drill/Exercise Performance | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful opportunities | 32.0 | 18.0 | 17.0 | 29.0 | 33.0 | 19.0 | 16.0 | 16.0 |
Total opportunities | 32.0 | 18.0 | 17.0 | 29.0 | 33.0 | 19.0 | 16.0 | 16.0 |
Indicator value | 99.2% | 99.1% | 99.1% | 99.1% | 99.0% | 99.0% | 99.5% | 100.0% |
Licensee Comments: none
ERO Drill Participation | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Participating Key personnel | 81.0 | 77.0 | 75.0 | 89.0 | 83.0 | 82.0 | 81.0 | 81.0 |
Total Key personnel | 81.0 | 78.0 | 76.0 | 89.0 | 83.0 | 82.0 | 81.0 | 81.0 |
Indicator value | 100.0% | 98.7% | 98.7% | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% |
Licensee Comments: none
Alert & Notification System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful siren-tests | 725 | 847 | 724 | 845 | 724 | 845 | 725 | 843 |
Total sirens-tests | 726 | 847 | 726 | 847 | 726 | 847 | 726 | 847 |
Indicator value | 99.7% | 99.7% | 99.6% | 99.8% | 99.8% | 99.7% | 99.8% | 99.7% |
Licensee Comments: none
Occupational Exposure Control Effectiveness | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
High radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Action Matrix Summary |
Inspection Findings Summary |
PI Summary |
Reactor Oversight Process
Last Modified: November 26, 2008