Search Options | ||||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us |
Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned scrams | 1.0 | 0 | 0 | 0 | 0 | 0 | 0 | 2.0 |
Critical hours | 2179.1 | 2049.6 | 1721.9 | 2160.0 | 0 | 1838.3 | 2184.0 | 2091.2 |
Indicator value | 2.7 | 1.8 | 1.7 | 0.9 | 0 | 0 | 0 | 2.3 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned power changes | 0 | 0 | 2.0 | 0 | 0 | 0 | 0 | 1.0 |
Critical hours | 2179.1 | 2049.6 | 1721.9 | 2160.0 | 0 | 1838.3 | 2184.0 | 2091.2 |
Indicator value | 0 | 0 | 1.7 | 1.7 | 2.4 | 2.4 | 0 | 1.1 |
Licensee Comments: none
Unplanned Scrams with Complications | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Scrams with complications | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (PWR) | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Safety System Functional Failures | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | 1.40E-07 | 9.70E-08 | 1.40E-07 | 1.10E-07 | 7.20E-08 | 9.70E-08 | 1.80E-07 | 1.60E-07 |
URI (ΔCDF) | -3.90E-07 | -3.90E-07 | -3.80E-07 | -3.80E-07 | -6.70E-08 | -6.70E-08 | -6.70E-08 | -6.70E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -2.50E-07 | -2.93E-07 | -2.40E-07 | -2.70E-07 | 5.00E-09 | 3.00E-08 | 1.13E-07 | 9.30E-08 |
Licensee Comments: none
Mitigating Systems Performance Index, High Pressure Injection System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | 2.20E-08 | 2.60E-08 | 3.60E-08 | 2.80E-08 | 1.10E-08 | 6.10E-09 | 5.60E-09 | 5.60E-09 |
URI (ΔCDF) | -7.40E-08 | -7.40E-08 | -7.40E-08 | -7.40E-08 | -1.50E-08 | -1.50E-08 | -1.50E-08 | -1.50E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -5.20E-08 | -4.80E-08 | -3.80E-08 | -4.60E-08 | -4.00E-09 | -8.90E-09 | -9.40E-09 | -9.40E-09 |
Licensee Comments: none
Mitigating Systems Performance Index, Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -1.10E-07 | 7.60E-08 | 1.10E-07 | 2.80E-08 | -1.70E-08 | -3.20E-08 | -7.70E-08 | -1.50E-07 |
URI (ΔCDF) | -6.20E-07 | -6.20E-07 | -6.10E-07 | -6.10E-07 | -2.30E-07 | -2.30E-07 | -2.30E-07 | -2.30E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -7.30E-07 | -5.44E-07 | -5.00E-07 | -5.82E-07 | -2.47E-07 | -2.62E-07 | -3.07E-07 | -3.80E-07 |
Licensee Comments: none
Mitigating Systems Performance Index, Residual Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | 2.00E-08 | 1.80E-08 | 1.80E-08 | 6.70E-09 | 1.80E-09 | 3.00E-09 | 7.80E-09 | 7.00E-09 |
URI (ΔCDF) | -3.80E-08 | -3.80E-08 | -3.80E-08 | -3.80E-08 | -9.00E-09 | -9.00E-09 | -9.00E-09 | -9.00E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.80E-08 | -2.00E-08 | -2.00E-08 | -3.13E-08 | -7.20E-09 | -6.00E-09 | -1.20E-09 | -2.00E-09 |
Licensee Comments: none
Mitigating Systems Performance Index, Cooling Water Systems | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | 4.20E-07 | 2.40E-07 | 2.60E-08 | 2.60E-08 | 8.90E-09 | 9.10E-09 | 8.80E-09 | 2.30E-08 |
URI (ΔCDF) | -3.80E-07 | -3.80E-07 | -3.80E-07 | -3.80E-07 | -1.60E-07 | -1.60E-07 | -1.60E-07 | -1.60E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 4.00E-08 | -1.40E-07 | -3.54E-07 | -3.54E-07 | -1.51E-07 | -1.51E-07 | -1.51E-07 | -1.37E-07 |
Licensee Comments: none
Reactor Coolant System Activity | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum activity | 0.000167 | 0.000174 | 0.000177 | 0.000179 | 0.000196 | 0.000183 | 0.000179 | 0.000175 | 0.000174 | 0.000186 | 0.000194 | 0.000203 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Reactor Coolant System Activity | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum activity | N/A | N/A | N/A | 0.000146 | 0.000152 | 0.000162 | 0.000172 | 0.000175 | 0.000179 | 0.000178 | 0.000181 | 0.000181 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | N/A | N/A | N/A | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Reactor Coolant System Leakage | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum leakage | 0.030 | 0.019 | 0.027 | 0.093 | 0.019 | 0.028 | 0.057 | 0.020 | 0.035 | 0.053 | 0.045 | 0.041 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 0.3 | 0.2 | 0.3 | 0.9 | 0.2 | 0.3 | 0.6 | 0.2 | 0.4 | 0.5 | 0.5 | 0.4 |
Reactor Coolant System Leakage | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum leakage | N/A | N/A | N/A | 0.051 | 0.023 | 0.047 | 0.029 | 0.014 | 0.041 | 0.033 | 0.053 | 0.032 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | N/A | N/A | N/A | 0.5 | 0.2 | 0.5 | 0.3 | 0.1 | 0.4 | 0.3 | 0.5 | 0.3 |
Licensee Comments: none
Drill/Exercise Performance | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful opportunities | 97.0 | 18.0 | 13.0 | 188.0 | 12.0 | 130.0 | 35.0 | 43.0 |
Total opportunities | 102.0 | 19.0 | 16.0 | 200.0 | 12.0 | 133.0 | 39.0 | 43.0 |
Indicator value | 94.6% | 94.5% | 94.0% | 94.0% | 93.0% | 94.4% | 94.0% | 95.0% |
Licensee Comments: none
ERO Drill Participation | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Participating Key personnel | 179.0 | 175.0 | 181.0 | 199.0 | 192.0 | 188.0 | 191.0 | 183.0 |
Total Key personnel | 183.0 | 183.0 | 183.0 | 200.0 | 193.0 | 190.0 | 191.0 | 183.0 |
Indicator value | 97.8% | 95.6% | 98.9% | 99.5% | 99.5% | 98.9% | 100.0% | 100.0% |
Licensee Comments: none
Alert & Notification System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful siren-tests | 792 | 798 | 798 | 756 | 882 | 755 | 756 | 798 |
Total sirens-tests | 793 | 798 | 798 | 756 | 882 | 756 | 756 | 798 |
Indicator value | 99.1% | 99.7% | 99.9% | 100.0% | 100.0% | 100.0% | 100.0% | 100.0% |
Licensee Comments: none
Occupational Exposure Control Effectiveness | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
High radiation area occurrences | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Action Matrix Summary | Inspection Findings Summary | PI Summary | Reactor Oversight Process
Last Modified: November 26, 2008