Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned scrams | 0 | 0 | 1.0 | 1.0 | 0 | 2.0 | 0 | 0 |
Critical hours | 2209.0 | 1843.0 | 1817.7 | 1863.9 | 2209.0 | 2020.5 | 2184.0 | 1988.0 |
Indicator value | 0 | 0 | 0.9 | 1.8 | 1.8 | 3.5 | 2.5 | 1.7 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Unplanned power changes | 1.0 | 0 | 0 | 1.0 | 2.0 | 2.0 | 2.0 | 0 |
Critical hours | 2209.0 | 1843.0 | 1817.7 | 1863.9 | 2209.0 | 2020.5 | 2184.0 | 1988.0 |
Indicator value | 1.6 | 0.8 | 0.9 | 1.8 | 2.7 | 4.4 | 5.9 | 5.0 |
Licensee Comments: none
Unplanned Scrams with Complications | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Scrams with complications | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (BWR) | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Safety System Functional Failures | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | 4.40E-08 | 5.90E-08 | 9.00E-08 | 9.80E-08 | 1.00E-07 | 6.40E-08 | 6.40E-08 | 3.10E-08 |
URI (ΔCDF) | 3.40E-07 | 5.30E-07 | 3.90E-07 | 5.40E-07 | 5.10E-07 | 5.10E-07 | 5.10E-07 | 3.40E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 3.84E-07 | 5.89E-07 | 4.80E-07 | 6.38E-07 | 6.10E-07 | 5.74E-07 | 5.74E-07 | 3.71E-07 |
Licensee Comments:
3Q/08: Revision 3 of the GGNS PRA was issued on June 30, 2008. Revision 3 was a major update that included the update of plant specific data, initiator frequencies (both plant specific and generic), common cause analyses, human reliability analyses; the addition of several new initiators; and changes to the modeling of offsite power. The revision has resulted in a new overall core damage frequency, changes to the Fussell-Vesely importance of all of the MSPI related basic events and changes to the probability of many of the MSPI related basic events.
Mitigating Systems Performance Index, High Pressure Injection System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -6.00E-10 | 5.60E-09 | 4.90E-09 | -2.80E-08 | -4.40E-08 | 4.90E-07 | 4.90E-07 | 1.80E-07 |
URI (ΔCDF) | 1.50E-08 | 7.60E-09 | 1.10E-08 | 2.60E-08 | 2.80E-08 | 2.00E-07 | 1.90E-07 | 6.60E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 1.44E-08 | 1.32E-08 | 1.59E-08 | -2.00E-09 | -1.60E-08 | 6.90E-07 | 6.80E-07 | 2.46E-07 |
Licensee Comments:
3Q/08: Revision 3 of the GGNS PRA was issued on June 30, 2008. Revision 3 was a major update that included the update of plant specific data, initiator frequencies (both plant specific and generic), common cause analyses, human reliability analyses; the addition of several new initiators; and changes to the modeling of offsite power. The revision has resulted in a new overall core damage frequency, changes to the Fussell-Vesely importance of all of the MSPI related basic events and changes to the probability of many of the MSPI related basic events.
Mitigating Systems Performance Index, Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -4.10E-08 | -4.20E-08 | 1.00E-07 | 9.50E-08 | 9.00E-08 | 3.90E-08 | 9.20E-09 | -1.50E-09 |
URI (ΔCDF) | -4.00E-07 | -3.90E-07 | -4.00E-07 | -3.90E-07 | -3.90E-07 | -3.80E-07 | -3.90E-07 | -2.10E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -4.41E-07 | -4.32E-07 | -3.00E-07 | -2.95E-07 | -3.00E-07 | -3.41E-07 | -3.81E-07 | -2.12E-07 |
Licensee Comments:
3Q/08: Revision 3 of the GGNS PRA was issued on June 30, 2008. Revision 3 was a major update that included the update of plant specific data, initiator frequencies (both plant specific and generic), common cause analyses, human reliability analyses; the addition of several new initiators; and changes to the modeling of offsite power. The revision has resulted in a new overall core damage frequency, changes to the Fussell-Vesely importance of all of the MSPI related basic events and changes to the probability of many of the MSPI related basic events.
Mitigating Systems Performance Index, Residual Heat Removal System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -8.50E-09 | -8.50E-09 | -7.60E-09 | -7.60E-09 | -7.30E-09 | -5.10E-09 | -1.40E-09 | -7.10E-10 |
URI (ΔCDF) | -1.00E-08 | -1.00E-08 | -1.00E-08 | -1.10E-08 | -1.10E-08 | -1.10E-08 | -1.10E-08 | -2.40E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.85E-08 | -1.85E-08 | -1.76E-08 | -1.86E-08 | -1.83E-08 | -1.61E-08 | -1.24E-08 | -2.47E-08 |
Licensee Comments:
3Q/08: Revision 3 of the GGNS PRA was issued on June 30, 2008. Revision 3 was a major update that included the update of plant specific data, initiator frequencies (both plant specific and generic), common cause analyses, human reliability analyses; the addition of several new initiators; and changes to the modeling of offsite power. The revision has resulted in a new overall core damage frequency, changes to the Fussell-Vesely importance of all of the MSPI related basic events and changes to the probability of many of the MSPI related basic events.
Mitigating Systems Performance Index, Cooling Water Systems | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
UAI (ΔCDF) | -1.40E-09 | -1.40E-09 | -1.40E-09 | -1.40E-09 | -1.40E-09 | -1.40E-09 | -1.40E-09 | -1.70E-09 |
URI (ΔCDF) | -1.30E-07 | -1.20E-07 | -1.20E-07 | -1.20E-07 | -1.20E-07 | -1.20E-07 | -1.20E-07 | -9.20E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.31E-07 | -1.21E-07 | -1.21E-07 | -1.21E-07 | -1.21E-07 | -1.21E-07 | -1.21E-07 | -9.37E-08 |
Licensee Comments:
3Q/08: Revision 3 of the GGNS PRA was issued on June 30, 2008. Revision 3 was a major update that included the update of plant specific data, initiator frequencies (both plant specific and generic), common cause analyses, human reliability analyses; the addition of several new initiators; and changes to the modeling of offsite power. The revision has resulted in a new overall core damage frequency, changes to the Fussell-Vesely importance of all of the MSPI related basic events and changes to the probability of many of the MSPI related basic events.
Reactor Coolant System Activity | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum activity | 0.007000 | 0.005790 | 0.004680 | 0.004440 | 0.004620 | 0.004590 | 0.004790 | 0.002870 | 0.002660 | 0.005360 | 0.002100 | 0.002170 |
Technical specification limit | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 |
Indicator value | 3.5 | 2.9 | 2.3 | 2.2 | 2.3 | 2.3 | 2.4 | 1.4 | 1.3 | 2.7 | 1.1 | 1.1 |
Reactor Coolant System Activity | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum activity | 0.002670 | 0.002510 | 0.003380 | 0.002370 | 0.002660 | 0.002120 | 0.002210 | 0.002420 | 0.002430 | 0.004370 | 0.002590 | 0.003030 |
Technical specification limit | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 |
Indicator value | 1.3 | 1.3 | 1.7 | 1.2 | 1.3 | 1.1 | 1.1 | 1.2 | 1.2 | 2.2 | 1.3 | 1.5 |
Licensee Comments: none
Reactor Coolant System Leakage | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 | 7/07 | 8/07 | 9/07 |
Maximum leakage | 2.350 | 2.380 | 2.310 | 2.300 | 2.600 | 3.140 | 2.420 | 2.390 | 2.480 | 2.770 | 2.600 | 2.280 |
Technical specification limit | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 |
Indicator value | 7.8 | 7.9 | 7.7 | 7.7 | 8.7 | 10.5 | 8.1 | 8.0 | 8.3 | 9.2 | 8.7 | 7.6 |
Reactor Coolant System Leakage | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 | 7/08 | 8/08 | 9/08 |
Maximum leakage | 2.680 | 2.620 | 2.300 | 2.420 | 2.380 | 2.570 | 2.480 | 2.730 | 2.170 | 2.810 | 2.320 | 2.170 |
Technical specification limit | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 | 30.0 |
Indicator value | 8.9 | 8.7 | 7.7 | 8.1 | 7.9 | 8.6 | 8.3 | 9.1 | 7.2 | 9.4 | 7.7 | 7.2 |
Licensee Comments: none
Drill/Exercise Performance | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful opportunities | 43.0 | 11.0 | 28.0 | 24.0 | 77.0 | 20.0 | 55.0 | 10.0 |
Total opportunities | 45.0 | 12.0 | 29.0 | 24.0 | 78.0 | 22.0 | 57.0 | 10.0 |
Indicator value | 96.2% | 95.6% | 94.8% | 95.2% | 97.4% | 97.0% | 96.9% | 96.8% |
Licensee Comments:
2Q/08: April data corrected to reflect inaccurate notification form (not marked "Drill").
ERO Drill Participation | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Participating Key personnel | 90.0 | 90.0 | 92.0 | 90.0 | 83.0 | 74.0 | 80.0 | 84.0 |
Total Key personnel | 93.0 | 93.0 | 94.0 | 90.0 | 83.0 | 82.0 | 80.0 | 84.0 |
Indicator value | 96.8% | 96.8% | 97.9% | 100.0% | 100.0% | 90.2% | 100.0% | 100.0% |
Licensee Comments: none
Alert & Notification System | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
Successful siren-tests | 126 | 128 | 126 | 123 | 129 | 127 | 125 | 82 |
Total sirens-tests | 129 | 129 | 129 | 129 | 129 | 129 | 125 | 84 |
Indicator value | 98.8% | 98.8% | 98.3% | 97.5% | 98.1% | 97.9% | 98.4% | 99.1% |
Licensee Comments:
3Q/08: The September 2008 siren test was cancelled at the discretion of the Tensas Parish Office of Emergency Preparedness Emergency Coordinator (LA) and the Claiborne County Civil Defense Director (MS). The test was cancelled due to agencies responding to the aftermath of hurricane Gustav.
Occupational Exposure Control Effectiveness | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
High radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 | 3Q/08 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none