On July 28, 2005, 4 months after a devastating incident in the Isomerization (Isom) Unit that killed 15 workers and injured 180, the BP Texas City refinery experienced a major fire in the Resid Hydrotreater Unit (RHU) that caused a reported $30 million in property damage. One employee sustained a minor injury during the emergency unit shutdown and there were no fatalities.
BP Texas City Refinery2005-4-B-TX-R1
Revise the maintenance quality control program to require positive material identification testing or another suitable material verification process for all critical service alloy steel piping components removed and reinstalled during maintenance and inform work crews of special material handling precautions.
Status: Open - Awaiting Response or Evaluation/Approval of Response
JV Industrial Companies2005-4-B-TX-R2
Develop / update the written piping component installation quality control procedure to require positive material identification testing or other suitable verification or tracking process for all alloy steel piping components removed during maintenance.